Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
z
Example 18 (Prohibited)
Capacity ratio
122%
Outdoor unit
Indoor unit 1
RB unit 1
RB unit 3 RB unit 4
Header
RB unit 2
Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 9Indoor unit 6 Indoor unit 10Indoor unit 7 Indoor unit 8
Model
Cooling
capacity
(Btu/h)
Total
capacity
(Btu/h)
Connectable indoor
unit capacity
Judgement
Min. Max.
Outdoor unit AOUA72T 72000 72000
50%
36000
150%
108000
≤
≤
36000 < 88000 < 108000 → OK
Indoor unit 1 AUUA14 14000
88000
Indoor unit 2 AUUA14 14000
Indoor unit 3 AUUA7 7500
Indoor unit 4 AUUA7 7500
Indoor unit 5 AUUA7 7500
Indoor unit 6 AUUA7 7500
Indoor unit 7 AUUA7 7500
Indoor unit 8 AUUA7 7500
Indoor unit 9 AUUA7 7500
Indoor unit 10 AUUA7 7500
RB unit 1 RU01AH -
14000
7500
27000
≤
≤
7500 < 14000 < 27000 → OK
RB unit 2 RU01AH -
14000
7500
27000
≤
≤
7500 < 14000 < 27000 → OK
RB unit 3 RU04BH -
30000
22500
191000
Prohibited
Because multi type of RB unit is
installed in the down stream of
header.
7500
7500
60000
7500
7500
60000
7500
7500
60000
7500
7500
60000
RB unit 4 RU04BH -
30000
22500
191000
Prohibited
Because multi type of RB unit is
installed in the down stream of
header.
7500
7500
60000
7500
7500
60000
7500
7500
60000
7500
7500
60000
- (06 - 19) -
SYSTEM
DESIGN
SYSTEM
DESIGN