Design Technical Manual

Table Of Contents
z
Example 16 (OK)
Capacity ratio
104%
Outdoor unit
Indoor unit 1
RB unit 1
RB unit 3
RB unit 2
Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 9Indoor unit 6 Indoor unit 10Indoor unit 7 Indoor unit 8
Model
Cooling
capacity
(Btu/h)
Total
capacity
(Btu/h)
Connectable indoor
unit capacity
Judgement
Min. Max.
Outdoor unit AOUA72T 72000 72000
50%
36000
150%
108000

36000 < 75000 < 108000 → OK
Indoor unit 1 AUUA7 7500
75000
Indoor unit 2 AUUA7 7500
Indoor unit 3 AUUA7 7500
Indoor unit 4 AUUA7 7500
Indoor unit 5 AUUA7 7500
Indoor unit 6 AUUA7 7500
Indoor unit 7 AUUA7 7500
Indoor unit 8 AUUA7 7500
Indoor unit 9 AUUA7 7500
Indoor unit 10 AUUA7 7500
RB unit 1 RU04BH -
52500
45000
191000

45000 < 52500 < 191000 → OK
7500
7500
60000

7500 ≤ 7500 < 60000 → OK
7500
7500
60000
7500
7500
60000
RB unit 2 RU04BH -
7500
7500
60000

7500 ≤ 7500 < 60000 → OK
7500
7500
60000
7500
7500
60000
7500
7500
60000
RB unit 3 RU04BH -
22500
22500
191000

22500 ≤ 22500 < 191000 → OK
7500
7500
60000

7500 ≤ 7500 < 60000 → OK
7500
7500
60000
7500
7500
60000
- (06 - 17) -
SYSTEM
DESIGN
SYSTEM
DESIGN