Design Technical Manual

Table Of Contents
RB UNIT (MULTI TYPE)
z
Example 7 (OK)
Capacity ratio
100%
Outdoor unit 1Outdoor unit 2
Indoor unit 1
RB unit 1
Indoor unit 2 Indoor unit 3 Indoor unit 4
Model
Cooling
capacity
(Btu/h)
Total
capacity
(Btu/h)
Connectable indoor
unit capacity
Judgement
Min. Max.
Outdoor unit 1 AOUA72T 72000
144000
50%
72000
150%
216000

72000 < 144000 < 216000 → OK
Outdoor unit 2 AOUA72T 72000
Indoor unit 1 AUUB36 36000
144000
Indoor unit 2 AUUB36 36000
Indoor unit 3 AUUB36 36000
Indoor unit 4 AUUB36 36000
RB unit 1 RU04BH -
144000
22500
191000

22500 < 144000 < 191000 → OK
36000
7500
60000

7500 < 36000 < 60000 → OK
36000
7500
60000
36000
7500
60000
36000
7500
60000
- (06 - 08) -
SYSTEM
DESIGN
SYSTEM
DESIGN