Design Technical Manual

Table Of Contents
z
Example 6 (OK)
Capacity ratio
92%
Outdoor unit
Header
Separation
tube
Indoor unit 1
RB unit 1
RB unit 2
Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6
Model
Cooling
capacity
(Btu/h)
Total
capacity
(Btu/h)
Connectable indoor unit
capacity
Judgement
Min. Max.
Outdoor unit AOUA96T 96000 96000
50%
48000
150%
144000

48000 < 88000 < 144000 → OK
Indoor unit 1 AUUA18 18000
88000
Indoor unit 2 AUUA14 14000
Indoor unit 3 AUUA14 14000
Indoor unit 4 AUUA14 14000
Indoor unit 5 AUUA14 14000
Indoor unit 6 AUUA14 14000
RB unit 1 RU01AH -
18000
7500
27000

7500 < 18000 < 27000 → OK
RB unit 2 RU01CH -
70000
7500
96000

7500 < 70000 < 96000 → OK
- (06 - 07) -