Example 3 (Prohibited)
Capacity ratio
146%
Outdoor unit
Indoor unit 1
RB unit 1 RB unit 2
Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7 Indoor unit 8
Model
Cooling
capacity
(Btu/h)
Total
capacity
(Btu/h)
Connectable indoor unit
capacity
Judgement
Min. Max.
Outdoor unit AOUA96T 96000 96000
50%
48000
150%
144000

48000 < 140000 < 144000 → OK
Indoor unit 1 AUUA12 12000
140000
Indoor unit 2 AUUA12 12000
Indoor unit 3 AUUA14 14000
Indoor unit 4 AUUA18 18000
Indoor unit 5 AUUA18 18000
Indoor unit 6 AUUA18 18000
Indoor unit 7 AUUA18 24000
Indoor unit 8 AUUA24 24000
RB unit 1 RU01AH -
38000
7500
27000
<

27000 < 38000 → Prohibited
RB unit 2 RU01CH -
102000
7500
96000
<

96000 < 102000 → Prohibited