Design Technical Manual

Table Of Contents
z
Type : Outdoor
Object
name
Code
(II)
Function
Unit
Inactive Active
Text-1 Tex t-2 Text-3 Text- 4 Text- 5 Tex t- 6 Text-7 Text- 8
BI
30
Outdoor unit error status
Normal Fault
31
Forced OFF status
Reset Set
BO 30
Forced OFF setting
Reset Set
MI
30
Outdoor unit priority
operation status *1
Cool Heat Neutral None
31
Outdoor unit error code
Refer to FGL original error code
32
Capacity Save Status
Not Set 100% 90% 80% 70% 60% 50% 40%
33
Outdoor low noise
operation setting *2
MO
30
Outdoor low noise
operation setting *
3
Stop
Level-1
Quiet
Level-1
Ability
Level-2
Quiet
Level-2
Ability
Level-3
Quiet
Level-3
Ability
32
Capacity Save Setting
Not Set 100% 90% 80% 70% 60% 50% 40%
*1) Priority operation status is for Heat Pump type VRF
In other types of systems, this status is not necessary.
*2) Refer to the "Outdoor unit low noise operation value table" for the texts used with the "Outdoor low noise operation
status"
*3) Outdoor unit rmware may need to be updated for this function to work.
Contact your local sales company for detail.
z
Type : Gateway
Object
name
Code
(II)
Function
Unit
Inactive Active
Text-1 Text-2 Text-3 Tex t- 4 Text- 5 Tex t- 6
Device
- Device information
BI
00 LON
®
Network Adaptor error status
Normal Abnormal
01 Gateway error status
Normal Abnormal
02 ES Status
Not Used
Energy
Saving
BO
02 ES Setting
Not Used
Energy
Saving
MI
00 LON
®
Network Adaptor unit error code
Refer to FGL original error code
01 Gateway error code
Refer to FGL original error code
02 ECA *1 status
Invalid
Invalid
(Stop)
Include
Indoor
Unit Only
Exclude
Indoor
And RB
Unit
Include
Indoor
And RB
Unit
Include
RB Unit
Only
MO
01 ECA *1 setting
Stop
Include
Indoor
Unit Only
Exclude
Indoor
And RB
Unit
Include
Indoor
And RB
Unit
Include
RB Unit
Only
Notication
00-99 Notication class
CAL
00 Calendar “Holiday-1”
01 Calendar “Holiday-2”
02-31 Calendar “Special day-1” - ”Special
day-30
Schedule
00-99 Schedule timer
*1) ECA: Electricity Charge Apportionment.
To protect the compressor of the outdoor unit, carefully read and understand the following cautions that may a󰀨ect the
operation of the compressor before executing the setting.
• When regularly making the following settings to the same outdoor unit by using schedule function etc., leave the
following interval.
<Corresponding function>
More than 6 minutes must elapse
More than 3 minutes must elapse
· Set outdoor unit forced o󰀨 mode·Reset outdoor unit forced o󰀨 mode