Design Technical Manual

Table Of Contents
BACnet
®
OBJECT LIST
z
Type : Indoor
Object
name
Code
(II)
Function
Unit
Inactive Active
Text-1 Tex t-2 Tex t- 3 Tex t- 4 Tex t-5 Text- 6 Text-7
AI
10 Set temp. status
Degree
11 Space temp.
Degree
12 Auto temp. (Low limit status)
Degree
13 Auto temp. (High limit status)
Degree
14 Cool/Dry temp. (Low limit status)
Degree
15 Cool/Dry temp. (High limit status)
Degree
16 Heat temp. (Low limit status)
Degree
17 Heat temp. (High limit status)
Degree
AO
10 Temp. setting
Degree
11 Auto temp. (Low limit setting)
Degree
12 Auto temp. (High limit setting s)
Degree
13 Cool/Dry temp. (Low limit setting )
Degree
14 Cool/Dry temp. (High limit setting )
Degree
15 Heat temp. (Low limit setting )
Degree
16 Heat temp. (High limit setting )
Degree
AV
10 ECA *1 operation data
BI
10 Operation status
OFF ON
14 Filter sign status
Unsigned Signed
15 Indoor unit error status
Normal Fault
16 Antifreeze operation status
Reset Set
17 SAVE operation status
Normal SAVE
18 Forced thermostat o󰀨 status
Reset Set
19 Emergency stop status
Normal Stop
20 Mode mismatch status
Normal Mismatch
21 Protect antifreeze status
Reset Set
22 Temp. limit valid status
Invalid Valid
BO
10 Operation setting
OFF ON
14 Filter sign resetting
Reset Not reset
15 Antifreeze operation setting
Reset Set
16 SAVE operation setting
Reset Set
17 Forced thermostat OFF setting
Reset Set
18 Emergency stop setting
Reset Set
19 Temp. limit valid setting
Invalid Valid
MI
10 Operation mode status
Cool Heat Fan Dry Auto
11 Fan speed status
Low High Med Auto Quiet Med-Low Med-High
12 Indoor unit error code
Refer to FGL original error code
13 R.C. prohibition status
Refer to R.C. prohibition setting chart
14 Vertical airow direction status
1 2 3 4 Swing
15 Horizontal airow direction status
1 2 3 4 5 Swing
16 Special driving status
Normal Defrost
Oil
Recovery
17 Managed mode
None Master Slave External
MO
10 Operation mode setting
Cool Heat Fan Dry Auto
11 Fan speed setting
Low High Med Auto Quiet Med-Low Med-High
12 R.C. prohibition setting
Refer to R.C. prohibition setting chart
13 Vertical airow direction setting
1 2 3 4 Swing
14 Horizontal airow direction setting
1 2 3 4 5 Swing
TL
10 ECA *1 operation data log
*1) ECA: Electricity Charge Apportionment.
- (05 - 162) -
CONTROL
SYSTEM
CONTROL