Design Technical Manual

Table Of Contents
DIMENSIONS
For M4x16 mm
screws
Hole pitch
(30)(25)
Hole: 2-Ø3/165
Hole: 2-Ø1/4 (7)
For code (
Ø3/165)
For code (> Ø3/165)
For code (
Ø1/4 (7))
For code (> Ø1/4 (7))
3-Ø3/16 (4.5)
3-7/8 (98)
2-Ø3/8 (10)
2-Ø5/16 (8)
4-3/4 (121) 3/8 (10)
1-11/16 (43)
Hole: 1/16 x 5/16 (2 x 8)
4-5/8 (117)
5-1/2 (140)
For open case
1-3/161
(30)
1-3/16
(25)
1
Unit : in. (mm)
PACKING LIST
The following installation parts are supplied. Use them as required.
Name and shape Quantity Application
Installation manual 1
Cable tie
4
For mounting the remote controller cable and transmission
cable.
Screw
(M4 × 16 mm)
3 For mounting the network convertor.
WIRING SPECIFICATIONS
Use Size Wire type Remarks
Transmission cable
22AWG
(0.33 mm
2
)
LEVEL4 (NEMA) non-polar 2 core,
twisted pair solid core Shielded
L
ON
W
ORKS
®
compatible cable
Remote controller cable
(2-wire type)
22 to 16AWG
(0.33 to 1.25 mm
2
)
Non-polar 2core
Use sheathed PVC cable or shielded
cable in accordance with the regional
cable standard.
Remote controller cable
(3-wire type)
22AWG
(0.33 mm
2
)
Polar 3 core
SPECIFICATIONS
Input Power (W) 2
Temperature: °F(°C)
Operating 32 to 114.8 (0 to 46)
Packaged 14 to 140 (-10 to 60)
Humidity (%) Packaged
0 to 95 (RH) ;
No condensation
Dimensions [H × W × D]: in. (mm)
5-1/2 × 4-5/8 × 1-11/16
(140 × 117 × 43)
Weight: oz. (g) 9 (250)
- (05 - 121) -
CONTROL
SYSTEM
CONTROL
SYSTEM