Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
SPECIFICATIONS
z
Control unit
Power supply (V) DC 12
Current (A) 0.10
Power consumption (W) 1.2
Temperature [°F (°C)]
Operating 32 to 114 (0–46)
Packaged 14 to 140 (-10–60)
Humidity (%) Packaged 0–95 (RH) No condensation
Dimensions [H × W × D] [in (mm)]
1-11/16 × 4-5/8 × 5-1/2
(43 × 117 × 140)
Weight [g (oz)] 7 (200)
Network
The electrical characteristics RS485
Maximum cable length (m) 250
z
Refrigerant pressure sensor
Power supply (V) DC 5
±
0.25
Current (mA) 10 or less
Pressure range (MPa) 0 to 5.0
Output voltage (V) DC 0.5 to 4.5
Accuracy (%FS) at 1013hPa, at 5V
Include thermal error
±
2.0
at -4 to 176 (-20 to 80°C)
Temperature [°F (°C)]
Ambient -22 to 176 (-30–80)
Fluid -40 to 248 (-40–120)
Airtight pressure (MPa) 5.5
Test pressure (MPa) 7.5
Burst pressure (MPa) 25 or more
z
Joint pipe
Applicable rifregrant R410A
Airtight proof (MPa)
The leakage rate shall be less than
1
10
-5
mmHgl/s.
Add mixgass (N
2
+R410A)
pressure to 4.15
Airtight pressure (MPa) 4.15
Proof pressure (MPa) 6.23
Burst pressure (MPa) 12.6
Dimensions of pipe
[L × D] [in (mm)]
2-12/16 × 1/4
(70 × Φ6.35)
- (05 - 103) -
CONTROL
SYSTEM
CONTROL
SYSTEM