Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
1) Equation for capacity calculation of outdoor unit.
2) Cooling capacity table of 14Ton outdoor units: AOUA168TLBVG (AOUA96TLBV +
AOUA72TLBV)
Total rated
cooling capacit y
of indoor unit
Outdoor
temp.
Indoor temperature (
°FDB / °FWB
)
68 / 59 80 / 67 82 / 68 86 / 72 90 / 73
(°FDB) TC IP TC IP TC IP TC IP TC IP
201.6
(120%)
50
128.5 7.5 8 198.0 11.19 200.5 11.18 210.9 11.13 213.5 11.11
.
. . . . . . . . . .
.
. . . . . . . . . .
95
128.5 10.05 177.1 14.46 179.1 14.51 187.3 14.70 189.3 14.75
.
. . . . . . . . . .
115
128.5 14.03 158.4 17.42 160.3 17.49 167.8 17.7 6 169.7 17.8 3
184.8
(110%)
50
117.8 7.02 184.8 10.57 193.3 11.02 205.6 11.16 20 8.1 11.14
.
. . . . . . . . . .
.
. . . . . . . . . .
95
117.8 9.27 173.6 14.37 175.6 14.42 183.6 14.61 185.6 14.66
.
. . . . . . . . . .
115
117.8 12.50 155.5 17.31 157.4 17.3 8 164.8 17.6 5 166.6 17.71
Capacity ratio of indoor units to outdoor unit X1 = 110 % X = 114.3 % X2 = 120 %
Capacity of outdoor units (kBtu/h) Y1 = 175.6 Y Y2 = 179.1
Y= (179.1-175.6) / (120-110)
(114.3-110) + 175.6 =
177.1 (kBtu/h)
3) Cooling capacity table of 16Ton outdoor units: AOUA192TLBVG (AOUA120TLBV +
AOUA72TLBV)
Total rated
cooling capacit y
of indoor unit
Outdoor
temp.
Indoor temperature (
°FDB / °FWB
)
68 / 59 80 / 67 82 / 68 86 / 72 90 / 73
(°FDB) TC IP TC IP TC IP TC IP TC IP
211.2
(110%)
50
134.6 7.8 8 211.2 11.87 220.9 12.37 236.5 12.66 239.5 12.65
.
. . . . . . . . . .
.
. . . . . . . . . .
95
153.7 11.75 198.6 16.26 200.8 16.33 209.7 16.60 212.0 16.67
.
. . . . . . . . . .
115
153.7 16.58 177.6 19.42 179.6 19.50 187.7 19.83 189.8 19.91
192.0
(100%)
50
139.8 8.15 192.0 10.87 200.8 11. 3 3 229.5 12.67 232.3 12.66
.
. . . . . . . . . .
.
. . . . . . . . . .
95
139.8 10.77 192.0 15.78 196.2 16.18 205.0 16.46 207. 2 16.53
.
. . . . . . . . . .
115
139.8 14.47 173.9 19.26 175.9 19.34 183.8 19.68 185.8 19.76
Capacity ratio of indoor units to outdoor unit X = 100 %
Capacity of outdoor units (kBtu/h) Y = 196.2
Y=
196.2 (kBtu/h)
Fig.2 Method for calculation of capacity of outdoor unit from capacity tables
X
2
Y
2
X
1
Y
1
YX
(X
1
, Y
1
)
(X
2
, Y
2
)
(X, Y)
x
y
i) Refer to 4. CAPACITY TABLE
(OUTDOOR UNIT) to nd Y
1
and Y
2
using
X
1
and X
2
.
ii) Calculate capacity of outdoor unit using
following equation:
Y=(Y
2
-Y
1
) / (X
2
-X
1
)
(X-X1) + Y
1
Capacity ratio of indoor units to outdoor unit, X (%)
Capacity of outdoor unit, Y (kBtu/h)
- (02 - 12) -
MODEL
SELECTION
MODEL
SELECTION