Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
● Select the circuit breaker based on MCA and MAX.CKT.BKR of the table above.
● Select the wire diameter based on the larger value of MCA or TOCA of the table above and select
a wire diameter which withstands the breaker capacity.
● Select the correct cable type and size according to the country or region’s regulations.
● Limited Wiring Length is in case voltage drop less than 2%. When wiring length extend longer,
select the wiring size of larger diameter.
RLA : Rated Load Amp of compressor under the standard condition.
MCA : Min Circuit Amp = Max Operating Current (Full Load)
MSC : Max Starting Current
TOCA : Total Value of Each Over Current Set
MAX.CKT.BKR : Maximum Circuit Breaker
8. ELECTRIC CHARACTERISTICS
Rated Value Electric Characteristics
Power Supply Full Load Characteristics
Wiring
Specications
Comp
-resser
Outdoor Fan
Motor
Ton Model name Hz
Voltage
(V)
MCA
(A)
TOCA
(A)
MSC
(A)
MAX.CKT.BKR
(A)
RLA
(A)
Output
(kW)
FLA
(A)
6 AOUA72TLBV 60 208/230 41 45 33.2 50 17 0.74 3.0
8 AOUA96TLBV 60 208/230 41 45 33.2 50 25 0.74 3.0
10 AOUA120TLBV 60 208/230 50 55 40.0 60 32 0.74 3.4
Rated Value Electric Characteristics
Power Supply Full Load Characteristics
Ton Set model name Model name Hz
Voltage
(V)
MCA
(A)
TOCA
(A)
MSC
(A)
12 AOUA144TLBVG
AOUA72TLBV
AOUA72TLBV
60 208/230 82 90 66.4
14 AOUA168TLBVG
AOUA96TLBV
AOUA72TLBV
60 208/230 82 90 66.4
16 AOUA192TLBVG
AOUA120TLBV
AOUA72TLBV
60 208/230 91 100 73.2
18 AOUA216TLBVG
AOUA120TLBV
AOUA96TLBV
60 208/230 91 100 73.2
20 AOUA240TLBVG
AOUA120TLBV
AOUA120TLBV
60 208/230 100 110 80
22 AOUA264TLBVG
AOUA96TLBV
AOUA96TLBV
AOUA72TLBV
60 208/230 123 135 99.6
24 AOUA288TLBVG
AOUA96TLBV
AOUA96TLBV
AOUA96TLBV
60 208/230 123 135 99.6