Design Technical Manual

Table Of Contents
1. SEPARATION TUBE
CONNECTION CAPACITY
Total cooling capacity of indoor units (x)
(kBtu/h)
Separation tube
For 2 pipes For 3 pipes
x < 96.5
UTR-BP090X or
UTP-AX090A
UTP-BX090A
96.5 ≤ x < 193
UTR-BP180X or
UTP-AX180A
UTP-BX180A
193 ≤ x
UTR-BP567X or
UTP-A X567A
UTP-BX567A
The total cooling capacity (x) is the total capacity for all indoor units downstream of the
separation tube.
z
For 2 pipes
UTR-BP090X UTR-BP180X
Separation Tube (liquid pipe)
15 ≤ x < 96.5 7.5 ≤ x < 89
7.5 ≤ x < 48
96.5 ≤ x < 193
89 ≤ x < 185.5
7.5 ≤ x < 96.5
Separation Tube (liquid pipe)
Separation Tube (gas pipe)
15 ≤ x < 96.5
7.5 ≤ x < 89
7.5 ≤ x < 48
96.5 ≤ x < 193
89 ≤ x < 185.5
7.5 ≤ x < 96.5
Separation Tube (gas pipe)
UTR-BP567X
Separation Tube (liquid pipe)
193 ≤ x 185.5 ≤ x
7.5 ≤ x < 325
Separation Tube (gas pipe)
193 ≤ x 185.5 ≤ x
7.5 ≤ x < 325
Unit: KBtu/h