Design and Technical Manual

3. OUTDOOR UNIT & BRANCH BOX
Select the breaker based on MCA and MAX.CKT.BKR of the table above.
Select the wire size based on the larger value of MCA or TOCA of the table above.
*1 Wiring Spec : These values are recommended data. Please select the wiring spec in accordance with local rules.
*2 Limited Wiring Length : This wiring length is in case voltage drop less than 2%. When wiring length extend longer,
select the wiring size of larger diameter.
RLA : Rated Load Amp of compressor under the standard condition.
MCA : Min Circuit Amp = Max Operating Current (Full Load)
MSC : Max Starting Current
TOCA : Total Value of Each Over Current Set
MAX.CKT.BKR : Maximum Circuit Breaker
ELECTRIC CHARACTERISTICS8.
OUTDOOR UNIT8-1.
Rated Value Electric Characteristics
Power Supply Full Load Characteristics Wiring Specications *1
Comp
resser
Outdoor Fan Motor
Model name Hz
Voltage
(V)
MCA
(A)
TOCA
(A)
MSC
(A)
MAX.
CKT.
BKR
(A)
Power Cable Earth Cable
Limited Wiring
Length*2
RLA
(A)
Output
(kW)
FLA
(A)
AWG size
Cross-section
AWG size
Cross-section
AOU48RLXFZ1 60 208/230 26.5 45 23.4 40 8 8
49/55 (ft.)
15/17 (m)
21 0.11 0.9
BRANCH BOX8-2.
Rated Value Electric Characteristics
Power Supply Full Load Characteristics Wiring Specications *1
Model name Hz
Voltage
(V)
MCA
(A)
TOCA
(A)
MAX.CKT.
BKR
(A)
Power Cable Earth Cable
AWG size
Cross-section
AWG size
Cross-section
UTP-PU03A
(Primary)
60 208/230 3 10 15 14 14
UTP-PU03B
(Secondary)
60 208/230 3 10 15 14 14
- (03 - 17) -
OUTDOOR
UNITS
OUTDOOR
UNITS