Design and Technical Manual

6. SYSTEM DESIGN
PEAK CUT MODE
Operation that suppressed the current value can be performed by means of the following on-
site work.
The air conditioner is set to the Peak cut mode when closing the contact input of a
commercial ON/OFF switch to a connector on the outdoor control PC board.
Circuit diagram example
z
Contact capacity : 24VDC or more, 10mA or more.
Outdoor unit
control PC board
Connector
1
2
Signal
Field supply
*33ft. (10m)
Connected unit
Ex.) Switch
* Make the distance from the PC board to the connected unit within 33ft. (10m).
Use the following parts and construct a circuit as shown above.
Input Signal∙∙∙ON : Peak cut mode, Input Signal∙OFF : Normal operation
*Set the "Peak cut mode" level, refer to "5.FUNCTION SETTING".
ON
OFF
ON
OFF
Input Signal
Peak cut mode
Parts (Optional)
z
Parts name External connect kit
Model name UT Y-XWZ XZ3
- (06 - 104) -