Design and Technical Manual

6. SYSTEM DESIGN
PIPING INSULATION
(1) Install the coupler heat insulation (large and small) and insulation (long and short) on each pipe as
shown in the gures below.
(2) Attach the butting surface with no gap to eliminate any gap between the insulations.
(3) During the pipe insulation work, prevent air from getting inside the insulation with an adhesive tape
(eld supply).
Indoor unit side
z
Coupler heat insulation (large)
Adhesive tape (eld supply)
Adhesive tape (eld supply)
Adhesive tape (eld supply)
Insulation (long)
Coupler heat insulation (small)
Butting surfaces
Outdoor unit side
z
Coupler heat insulation (small)
Coupler heat insulation (large)
Butting surfaces
[First piece]
Insulation (short)
Insulation (short)
[Second piece]
Insulation (short)
Adhesive tape
(eld supply)
Insulation (short) x 2
(cover with 2 pieces of
insulation)
NON-CONNECTING PIPES
(1) Install the coupler heat insulation (large and small) and insulation (long) as shown in the gure on
the right.
(2) Apply an adhesive tape (eld supply) to prevent air from getting inside the insulation.
Insulation (long)
Adhesive tape (eld supply)
Adhesive tape (eld supply)
- (06 - 36) -