Service Manual

OK
DC
Heat exchanger liquid outlet thermistor
Heat exchanger liquid pipe thermistor short or open detected
1. Connector connection failur, open
2. Thermistor failure
3. Main PCB failure
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN63:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Indoor Unit : Operation LED 8 times Flash, Timer LED 3 Times Flash,
Economy LED Continuous Flash.
Outdoor Unit : E. 83. 1
Error Code : 83
If the voltage does not appear, replace Main PCB
,
and execute the check operation again.
02-42
Liquid Pipe Thermistor Error
Trouble shooting 25
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Heat exchanger liquid outlet thermistor (CN63:1-2)
CN63
THERMISTOR
THERMISTOR
(SC. GAS. OUT.)
(HEX. PIPE. OUT.)
BLACK
BLACK
123
4
123
4
5
5
BLACK
BLACK