2.
ABOUT THE UNIT
2.1. Precautions for using R410A refrigerant
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
1 Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models, some of the piping
and installation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace
the conventional piping and fl are nuts with the R410A piping and fl are nuts.
2 Be careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when storing
the piping, securely seal the openings by pinching, taping, etc.
2.2. Special tools for R410A
Tool name Contents of change
Gauge manifold
Pressure is high and cannot be measured with a conventional (R22) gauge. To prevent
erroneous mixing of other refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (30 in.Hg to 768 psi) for high
pressure. –0.1 to 3.8 MPa (30 in.Hg to 551 psi) for low pressure.
Charge hose To increase pressure resistance, the hose material and base size were changed.
Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter.
Gas leakage detector Special gas leakage detector for HFC refrigerant R410A.
2.3. Accessories
Name and shape Q’ty Application Name and shape Q’ty Application
Installation Manual
1
This manual Washer
8
For suspending the
Branch box from
ceiling
Coupler heat insulation
(large)
4
For indoor and outdoor
side pipe joint (gas pipe)
Tapping screw
(Ø 4×10)
8
For installing the
Hanger
Coupler heat insulation
(small)
4
For indoor and outdoor
side pipe joint (liquid pipe)
Tapping screw
(Ø 4×25)
8
For installing the
Branch box on the wall
Insulation (long)
3
For use on the section
where the insulation
fi ts onto this equipment
(indoor unit side)
Binder
1
For remote controller
cable binding
Insulation (short)
3
For use on the section
where the insulation
fi ts onto this equipment
(outdoor unit side)
Seal
1
To prevent small
animals from entering
inside
Insulation
3
To be used with this
equipment’s (indoor unit
side) piping
Adapter
12.7 (1/2)
➝
9.52 (3/8)
[mm(in.)]
3
For indoor unit
connection
Hanger
4
For suspending the
Branch box from ceiling
Adapter
12.7 (1/2)
➝
15.88 (5/8)
[mm(in.)]
3
For indoor unit
connection
9380120001-06 EN.indd 49380120001-06 EN.indd 4 6/16/2558 BE 8:19 PM6/16/2558 BE 8:19 PM