4.3.2-A. Fix the unit (When hanging from the ceiling)
CAUTION
Do not hang from the ceiling when performing a vertical installation.
(1) Secure the hangers (accessories) with the screws
(2 pieces, Ø 4 x 10, accessories). (4 places)
Hanger (4 places)
Screw
(2) Secure the attachment section with the hanging bolt.
(Use M8 or M10 (5/16 or 3/8 in.) for the hanging bolt)
(3) Secure the hangers with hexagonal nuts (fi eld supply)
and the washers (accessories) as shown in the fi gure
below.
(4) Once you have checked the unit is fl at, fasten the
hexagonal nuts.
(The unit’s slope must be within ±5° in all directions.)