2. MODEL SELECTION
MODEL : ARU24RLF
Outdoor
temperature
Indoor temperature (°CDB / °CWB)
21.1 / 15.6 22.2 / 16.1 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 31.1 / 22.2 32.2 / 22.8
(°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
-5.0 5.65 3.90 6.25 4.44 6.65 4.78 7.02 4.98 7.79 5.42 8.49 5.95 9.13 6.11
0.0 5.65 3.90 6.25 4.44 6.65 4.78 7.02 4.98 7.79 5.42 8.49 5.95 9.13 6.11
5.0 5.65 3.90 6.25 4.44 6.65 4.78 7.02 4.98 7.79 5.42 8.49 5.95 9.13 6.11
10.0 5.65 3.90 6.25 4.44 6.65 4.78 7.02 4.98 7.79 5.42 8.49 5.95 9.13 6.11
15.0 5.65 3.90 6.25 4.44 6.65 4.78 7.02 4.98 7.79 5.42 8.49 5.95 9.13 6.11
20.0 5.65 3.90 6.25 4.44 6.65 4.78 7. 02 4.98 7.79 5.42 8.49 5.95 8.63 6.04
25.0 5.65 3.90 6.25 4.44 6.65 4.78 7. 0 2 4.98 7.79 5.42 8.21 5.75 8.42 5.85
30.0 5.65 3.90 6.25 4.44 6.65 4.78 7. 0 2 4.98 7.79 5.42 7.93 5.59 8.14 5.74
35.0 5.65 3.90 6.25 4.44 6.65 4.78 7.02 4.98 7.41 5.22 7.72 5.48 7.86 5.66
40.0 5.65 3.90 6.25 4.44 6.48 4.75 6.62 4.83 6.98 4.99 7. 2 8 5.21 7.41 5.41
46.1 5.65 3.90 5.54 4.02 6.09 4.53 6.23 4.67 6.57 4.73 6.85 4.93 6.97 5.16
COOLING CAPACITY
in kW
TC : Total Capacity kW.
SHC : Sensible Heat Capacity kW.
The data is based on the following conditions.
Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit]
Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].