2. MODEL SELECTION
CAPACITY COMPENSATION COEFFICIENT5.
COMPENSATION COEFFICIENT OF PIPE LENGTH5-1.
The gures give the compensation coefcient of pipe length owing to installation position.
Total compensation coefcient of pipe length multiplies compensation coefcient of branch
piping by compensation coefcient of main piping.
"Total compensation coefcient = main piping x branch piping"
*1
*1: Branch piping use the value of the longest piping length.
CAPACITY CHANGE RATE BY MAIN PIPING LENGTH
Change rate in capacity
z
Main piping length
ft. 16.4 32.8 49.2 65.6 82.0 98.4 114. 8 131.2 147.6 164.0 180.4
m 5 10 15 20 25 30 35 40 45 50 55
Change rate in
cooling capacity
% 100 98.0 96.0 94.0 92.0 90.0 88.0 86.0 84.0 82.0 80.0
Change rate in
heating capacity
% 100 99.6 99.2 98.9 98.5 9 8.1 97.7 97. 3 97. 0 96.6 96.2
0
0 16.4 32.8 49.2 180.4 ft.
m
164.0147.6131.2114. 898.482.065.6
55504540353025201510
75
80
85
90
95
100
5
Change rate in capacity (%)
Main piping length
Cooling
Heating