Design and Technical Manual

6. SYSTEM DESIGN
BASE HEATER
A base heater is a heating element that may be installed to melt the ice that may accumulate in
the condenser drain pan.
This output signal is produced when the outdoor temperature drops down to 36°F (2°C), and
releases at 39°F (4°C).
Circuit diagram example
z
1
2
3
4
Connector
AC240V
Base heater
*2
*1
connected unit
P.C . B
*1: Connect to pin 1 and pin 3. No connection pin2 and pin4.
*2: The allowable Input Power is 25W or less.
1
2
3
4
Connector
AC240V
Base heater
*3
*1
connected unit
P.C . B
*3: If a load greater than 25W is applied, a contactor or relay should be used to operate and control the base
heater.
ON
OFF
Operation
Stop
Heater
Output signal
status
Parts (Optional)
z
Parts name External connect kit
Model name UT Y-XWZ XZ4
- (06 - 109) -