Design and Technical Manual
Table Of Contents
6. SYSTEM DESIGN
STOP OPERATION MODE
It is possible to switch to Batch stop or Emergency stop and Normal operation by using external •
input.
Circuit diagram example
z
Contact capacity : 24VDC or more, 10mA or more.
Outdoor unit
control PC board
Connector
1
2
Signal
Field supply
*33ft. (10m)
Connected unit
Ex.) Switch
* Make the distance from the PC board to the connected unit within 33ft. (10m).
Use the following parts and construct a circuit as shown above. •
Set the "Batch stop" or "Emergency stop" pattern, refer to "5.FUNCTION SETTING" •
When function setting is "Batch stop" mode ●
Remote controller
ON ON
Input signal
ON
OFF
Air conditioner
Operation
Stop
Command
Batch stop
Normal
Remote control
operation validity
- (06 - 105) -
SYSTEM
DESIGN
SYSTEM
DESIGN