Design and Technical Manual
Table Of Contents
6. SYSTEM DESIGN
DUCT STATIC PRESSURE SETTING5-10.
MODELS : ARU7RLF, ARU9RLF, ARU12RLF, ARU18RLF,
ARU24RLF
The air ow setting other than the default value of 0.1inWG (25 Pa) may be changed to the
required external static pressure.
Setting of the air ow can be changed with the wireless remote controller, wired remote
controller, and simple remote controller.
How to set air ow (external static pressure)
W ● ireless remote controller
Air ow is set by function number 26 (static pressure).
Refer to "BUTTON NANE AND FUNCTION", "FUNCTION SETTING" and "FUNCTION
DETAILS" in 5-3 INDOOR UNIT (setting by wireless remote controller).
Wired remote controller ●
Air ow is set by function number 26 (static pressure).
Refer to "BUTTON NANE AND FUNCTION", "FUNCTION SETTING" and "FUNCTION
DETAILS" in 5-4. INDOOR UNIT (setting by wired remote controller).
Simple remote controller ●
Air ow is set by function number 26 (static pressure).
Refer to "BUTTON NANE AND FUNCTION", "FUNCTION SETTING" and "FUNCTION
DETAILS" in 5-5 INDOOR UNIT (setting by simple remote controller).
FAN PERFORMANCE CURVE ●
Refer to Chapter 4. INDOOR UNITS
Note
If air flow setting is unmatched, it is caused to be air flow down or water leakage due to ●
wrong operation.
Range of static pressure at ARU24 model is different from the others. ●
- (06 - 92) -
SYSTEM
DESIGN
SYSTEM
DESIGN