6. SYSTEM DESIGN
SETTINGS LIST
LED961
CODE No.
Setting Mode
LED962
CODE No.
Setting Function
Factory
setting
Remarks
1 1
Cooling
capacity shift
0 0 Standard
l
Use it when becoming cooling capacity
shortage.
Use High power mode 2 when becoming
cooling capacity shortage in High power
mode 1.
0 1 High power mode 1
0 2 High power mode 2
2 0
Switching
between
batch stop or
emergency stop
0 0 Batch stop
l
This mode selects the pattern of the stop
function to be operated by the external
input terminal (CN934).
•Batch stop: The stop of all indoor units
connected to same refrigerant system due
to input signal coming from CN934.
•Emergency stop: When emergency
stop is actuated, the indoor unit does not
accept the operation command from the
remote controller. On the other hand,
when the emergency stop is released (no
input from CN934), the air conditioner
does not return to the original operation
until operate indoor unit by the remote
controller.
0 1 Emergency stop
2 1
Operation
mode selecting
method
0 0
Priority given to the
rst command
l
Select the priority setting of the operation
mode.
•Priority given to the rst command:
Priority is given to the operation mode
which is set rst.
•Priority given to external input of outdoor
unit: Priority is given to the operation
mode which is set by the external input
terminal (CN932).
0 1
Priority given to
external input of
outdoor unit
2 8 Forbidden
0 0 Forbidden
l
Setting forbidden
0 1 Forbidden
2 9 Forbidden
0 0 Forbidden
l
Setting forbidden
0 1 Forbidden
3 0
Energy saving
level setting
0 0 Level 1 (stop)
The capacity limit can be selected when
operating with the “Energy Saving Peak
Cut function.”
The operation selection can be done by
external input terminal(CN933).
The lower the level, the more the effect
of energy saving, but the cooling/heating
performance decreases.
0 1
Level 2
(Limited at 50%)
0 2
Level 3
(Limited at 75%)
l
0 3
Level 4
(Limited at 100%)
3 4
Frost protection
fan mode
0 0 On
l
This mode is the function to prevent
frosting to the propeller fan of outdoor unit
during heating operation.
0 1 Off
4 1
Low noise
mode setting
0 0 Off (Normal)
l
When "Low noise mode ON" is selected,
the operating noise will be suppressed.
Without external input terminal: It operates
by selecting Low noise mode ON.
With external input terminal: The operation
selection can be done by external input
terminal(CN931) by selecting Low noise
mode OFF.
0 1 On (Low noise mode)
4 2
Low noise
mode
operation level
setting
0 0
Level 1
(-3dB)
l
The noise level when operating in the low
noise mode can be set.
Cooling/heating performance decreases
by lowering operation noise level.
0 1
Level 2
(-6dB)
0 2
Level 3
(-9dB)
- (06 - 53) -