Design and Technical Manual
Table Of Contents
6. SYSTEM DESIGN
Again, referring to the Settings List shown below, press the SELECT button (SW932), and 5)
display the code number of the function you want to set on the LED962.
Ex.) To select the Emergency Stop function
LED961 LED962 LED961 LED962
Next, press the ENTER button (SW933), and conrm the selection of the function you want to
set.
LED961 LED962
LED961 LED962
A ashing display on the LED962 changes to an illuminated display.
This completes FUNCTION SETTING.
To exit FUNCTION SETTING, press the ENTER button (SW933) in the setting completed 6)
status shown in step 5) above.
*2 : 5 seconds after, even if ENTER button(SW933) is not pressed , LED961 changes to a ashing display
automatically.
LED961 LED962
LED961 LED962
*2
Then, press the MODE/EXIT button (SW931) to exit FUNCTION SETTING MODE.
LED961 LED962
LED961 LED962
To set another function, press the ENTER button (SW933) in the setting completed status 7)
shown in step 5) above.
LED961 LED962
LED961 LED962
Repeat steps 4) and 5) above to set other functions.
When all settings are complete, perform the operation described in step 6) above to exit.
RESET THE POWER AFTER SETTING UP FUNCTION OF
OUTDOOR UNIT
Important
If the reset is not performed, function can not be read in normally.
¾
After all the functions have been set, the circuit breaker needs to be switched off
¾
for at least 2 minutes.
After the 2 minutes has passed, power can be restored.
The set function is stored in the PCB and will remain in memory even when the
¾
power is turned off.
However setting function is effective after power reset.
Record the function set in the outdoor unit on a label, etc., and afx the label to the
unit so it can be used for after-sales service operations.
- (06 - 52) -
SYSTEM
DESIGN
SYSTEM
DESIGN