Design and Technical Manual

5. CONTROL SYSTEM
INSTALLATION
Connection Pattern
Note: Connection pattern is different according to type of Indoor unit.
Indoor unit types Connection Pattern
Compact Cassette type
Pattern A
Slim Duct type
Wall Mounted type
ASU7RLF1, ASU9RLF1, ASU12RLF1
Pattern BASU7RLF, ASU9RLF, ASU12RLF
ASU9RLS2, ASU12RLS2, ASU15RLS2
ASU18RLF, ASU24RLF
Pattern C
Floor type
Pattern A
Connect the end of remote controller cable directly to the exclusive terminal block.
PCB
M4 screw
Terminal block
Remote
controller
cable
Remote controller
terminal block
Indoor unit
Outdoor unit /
Power supply
terminal block
Note: It may be failed if it is connected to the outdoor unit or the terminal block for power supply.
Pattern B
1) Modify the remote controller cable as per below methods.
Use a tool to cut off the terminal on the end of the remote controller cable and then remove
the insulation from the cut end of the cable as shown in Fig.
Connect the remote controller cable and connecting cable as shown in Fig.
Be sure to insulate the connection between the cables.
13/16 in.
(20 mm)
Remote controller
cable
Connecting
cable
Insulated
connection
Red
Red
White
White
Black
Black
2) Method of connecting remote controller cable
Connecting cable made by above-mentioned 1) is connected with terminal (*1) of optional
communication kit.
Cable connected with terminal (*2) of communication kit is connected with PCB of Indoor unit.
*1: CN305 (for ASU7RLF, ASU9RLF, ASU12RLF: UTY-XCBXZ1)
CNC01 (for ASU9RLS2, ASU12RLS2, ASU15RLS2: UTY-TWBXF)
CNC01 (for ASU7RLF1, ASU9RLF1, ASU12RLF1: UTY-XCBXZ2)
*2: CN301 (for ASU7RLF, ASU9RLF, ASU12RLF: UTY-XCBXZ1)
CND01 (for ASU9RLS2, ASU12RLS2, ASU15RLS2: UTY-TWBXF)
CND01 (for ASU7RLF1, ASU9RLF1, ASU12RLF1: UTY-XCBXZ2)
Remote controller
cable
Connecting
cable
Communication kit Indoor unit PCB
Terminal
(*2)
Terminal
(*1)
- (05 - 22) -
CONTROL
SYSTEM