Design and Technical Manual
Table Of Contents
4. INDOOR UNITS
SAFETY DEVICES10.
Model and type PCB fuse
Fan motor
thermal
protector
Terminal
thermal fuse
Float
switch
Compact Cassette
AUU7RLF
250V 3.15A
OFF: 268
+ 30
- 34
°F
(131
+ 17
- 19
°C)
ON: 210
+ 38
- 34
°F
(99
+ 21
- 19
°C)
―
○
AUU9RLF
AUU12RLF
AUU18RLF
Slim Duct
ARU7RLF
250V 3.15A
OFF: 275 ± 27°F
(135 ± 15°C)
ON: 239 ± 27°F
(115 ± 15°C)
―
○
ARU9RLF
ARU12RLF
ARU18RLF
ARU24RLF
Wall Mounted
ASU7RLF1
250V 3.15A
OFF: 221 ± 18°F
(105 ± 10°C)
ON: 194 ± 18°F
(90 ± 10°C)
― ―
ASU9RLF1
ASU12RLF1
ASU7RLF
250V 3.15A
OFF: 230 ± 27°F
(110 ± 15°C)
ON: 203 ± 27°F
(95 ± 15°C)
OFF: 216°F
(OFF: 102°C)
―
ASU9RLF
ASU12RLF
ASU9RLS2
OFF: 320 ± 45°F
(160 ± 25°C)
ON: 230 ± 45°F
(110 ± 25°C)
ASU12RLS2
ASU15RLS2
ASU18RLF
250V 3.15A
OFF: 302 ± 27°F
(150 ± 15°C)
ON: 248 ± 27°F
(120 ± 15°C)
OFF: 216°F
(OFF: 102°C)
―
ASU24RLF
Floor
AGU9RLF
250V 3.15A
OFF: 302 ± 27°F
(150 ± 15°C)
ON: 248 ± 27°F
(120 ± 15°C)
OFF: 216°F
(OFF: 102°C)
―AGU12RLF
AGU15RLF
- (04 - 95) -
INDOOR
UNITS
INDOOR
UNITS