Design and Technical Manual

4. INDOOR UNITS
FLOOR TYPE2-4.
Model name AGU09RLF AGU12RLF AGU15RLF
Power source 1ø 208/230V 60Hz
Available voltage range 187-264V
Capacity
Cooling Rated
Btu/h 9,000 12,000 14,000
kW 2.64 3.51 4.10
Heating Rated
Btu/h 10,200 13,500 16,300
kW 3.00 3.96 4.80
Input Power W 16 20 23
Running current A 0.15 0.18 0.20
Fan
Airow
rate
Cooling
High
CFM
(m
3
/h)
312 (530) 353 (600) 383 (650)
Med 259 (440) 288 (490) 306 (520)
Low 212 (360) 224 (380) 235 (400)
Quiet 159 (270) 159 (270) 159 (270)
Heating
High 312 (530) 353 (600) 383 (650)
Med 270 (460) 300 (510) 318 (540)
Low 224 (380) 241 (410) 253 (430)
Quiet 159 (270) 159 (270) 159 (270)
Fan type × Q'ty Crossow x 2
Fan motor output W 16
Sound pressure level
Cooling
High
dB(A)
39 42 44
Med 34 36 38
Low 28 30 31
Quiet 22 22 22
Heating
High 39 42 44
Med 35 38 39
Low 30 32 33
Quiet 22 22 22
Heat
exchanger
Dimension (H × W × D) in. (mm) 14-7/8 x 21-5/8 x 1-1/16 (378 × 550 × 26.6)
Fin pitch FPI 21
Rows × Stages 2 x 18
Pipe type Copper tube
Fin Type Aluminium
Enclosure
Material Polystyrene
Color
WHITE
(Approximate colour of MUNSELL N9.25/)
Dimensions
(H × W × D)
Net
in.(mm)
23-5/8 x 29-1/8 x 7-7/8 (600 × 740 × 200)
Gross 27-9/16 x 32-5/16 x 12-3/16 (700 × 820 × 310)
Weight
Net
lbs.(kg)
31 (14)
Gross 37 (17)
Connection
pipe
Size
Liquid
in.(mm)
Ø1/4in. (Ø 6.35)
Gas Ø3/8in. (Ø 9.52) Ø1/2in. (Ø 12.70)
Method Flare
Drain hose
Material PVC
size in.[mm] Ø 9/16(I.D.), Ø 11/16(O.D.) [Ø 13.8 (I.D.), Ø 16.7 (O.D.)]
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 86 (16 to 30)
Remote controller type Wireless [Wired (option)]
Note: Specications are based on the following conditions.
Power source of specications: 230V
Cooling: Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95°F(35°C)DB/75°F(23.C)WB.
Heating: Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB.
Pipe length: 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit]
Height difference: 0 ft.(0m) [Outdoor unit - Indoor unit].
The protective function might work when using it out the operation range.
- (04 - 14) -
INDOOR
UNITS
INDOOR