DTR_BMU004E_02 VD014E/06 VD014E/06 DESIGN & TECHNICAL MANUAL Hybrid Flex Inverter System FUJITSU GENERAL LIMITED
CONTENTS 1. GENERAL INFORMATION 2. MODEL SELECTION 3. OUTDOOR UNITS 4. INDOOR UNITS 5. CONTROL SYSTEM 6. SYSTEM DESIGN 7.
Hybrid Flex Inverter System 1. GENERAL INFORMATION DTR_BMU004E_02--CHAPTER01 2013.12.
CONTENTS 1. GENERAL INFORMATION 1. FEATURES OF SYSTEM............................................................... 01 - 01 1-1.HIGH EFFICIENCY & COMPACT.............................................................. 01 - 01 1-2.FLEXIBLE DESIGN & EASY INSTALLATION........................................... 01 - 02 1-3. CENTRAL CONTROL................................................................................ 01 - 05 2. MODEL LINE UP......................................................................
GENERAL INFORMATION GENERAL INFORMATION 111FEATURES OF SYSTEM 11111HIGH EFFICIENCY & COMPACT HIGH EFFICIENCY Adopting a large heat exchanger, high efficiency ventilation fan, DC twin rotary compressor, etc. realizes high efficiency operation. Cooling SEER:17.0 Heating HSPF:9.8 3.89 0.0 15.0 16.0 17.0 SEER 0.0 8.0 9.0 10.0 HSPF TOP CLASS TOP CLASS COMPACT DESIGN Compact and lightweight outdoor unit is easy to carry in, it can be installed unnoticeably in various places.
FLEXIBLE DESIGN ●●7 types, 23 models of indoor units can be selected ranging from 7000Btu to 24000Btu in capacity. Compact Cassette Floor Slim Duct Wall Mounted ●●Up to 8 indoor units can be connected to one outdoor unit. ●●A maximum of 130% indoor unit connectable capacity. Match any room layout. Connectable indoor unit capacity Connectable indoor unit 80 to 130% 2 to 8 For any room layout-connectable capacity of indoor units is max 130% Total pipe length Actual pipe length 377ft.
GENERAL INFORMATION GENERAL INFORMATION EASY INSTALLATION ●●Corresponding to diverse installation environments by use of branch connection system. Current model : 4 Rooms multi x 2 New model Branch box BRANCH BOX ●●Branch box has an electronic expansion valve built-in, so it can control the refrigerant flow to each indoor unit. ●●Can be connected by flare connection and both ceiling suspension and wall mounting installation are available.
GENERAL INFORMATION GENERAL INFORMATION DECREASE OF INSTALLATION MISTAKE ●●This operation allows the air conditioner to automatically check the status of the outdoor unit and check for wiring mistakes.
Support comfort control system for the varied needs of the home and the condominium, etc. ●●Central remote controller is connected directly to the branch box, making the installation process easier. ●●Once the controller is connected, it can automatic register and display all the indoor units. CENTRAL REMOTE CONTROLLER (Option) Controllable 1 Multi system Max.
Air conditioning load factor ●● Users can choose from 4 low noise levels, depending on the installation environment. Heat load 100% Capacity Operating sound Down 0 58dB 0 (time) Low noise operation Minimum heat (All) operation zz ●●While this function is selected, all indoor units start the minimum heat operation when all the indoor units are stopped by operation of the [On/Off button]. ●● When the room temperature is higher than 50°F (10°C), MIN.
GENERAL INFORMATION GENERAL INFORMATION 222MODEL LINE UP 22222OUTDOOR UNIT LINE UP HP Capacity (Btu/h) Model name Connectable indoor unit 5 48000 AOU48RLXFZ1 2 to 8 MODEL DESIGNATION 1 A 2 O Type AO : Outdoor unit 3 U Destination U: FUJITSU 4 4 5 8 Model code (Btu/h) 48 : (48000) 6 7 R Function R: Heat pump 8 L X Function L: Inverter Function X: Extended line set - (01 - 07) - 9 F 10 11 Function Z: Zoning Model change code 1 Z Function F: Flexible 1 1.
GENERAL INFORMATION GENERAL INFORMATION 22222INDOOR UNIT LINE UP arious combinations of types and capacity 7 types 23 models, ranging from 7000Btu to V 24000Btu.
LINE UP Type Indoor units Wall mounted ASU7RLF1 ASU7RLF ASU9RLS2 ASU18RLF ASU9RLF1 ASU9RLF ASU12RLS2 ASU24RLF ASU12RLF1 ASU12RLF ASU15RLS2 Model Compact Cassette Slim Duct Floor Central remote controller UTY-DMMUM *1 *1 *1 *1 *1 *1 *1 Wired Remote Controller UTY-RNNUM *4 *2 *3 Simple Remote Controller UTY-RSNUM *4 *2 *3 UTY-LNHUM - - - - - AR-RAH1U - - - - - - AR-RED1U - - - - - - AR-REG1U - -
GENERAL INFORMATION GENERAL INFORMATION 22222SEPARATION TUBE Liquid pipe Separation tube Model : UTP-SX248A Gas pipe 22222BRANCH BOX Primary type Model : UTP-PU03A Secondary type Model : UTP-PU03B - (01 - 10) - 1.
GENERAL INFORMATION GENERAL INFORMATION 22222CASSETTE GRILLE LINE UP Type Cassette grille Indoor units Model Compact Cassette Slim Duct Floor UTG-CCGF - - Wall mounted ASU7RLF1 ASU7RLF ASU9RLS2 ASU18RLF ASU9RLF1 ASU9RLF ASU12RLS2 ASU24RLF ASU12RLF1 ASU12RLF ASU15RLS2 - - - - PARTS Cassette grille Model : UTG-CCGF - (01 - 11) - 1.
GENERAL INFORMATION GENERAL INFORMATION 22222 OTHERS LINE UP Indoor units Wall mounted Type Model Compact Cassette Slim Duct Floor ASU7RLF1 ASU7RLF ASU9RLS2 ASU9RLF1 ASU9RLF ASU12RLS2 ASU12RLF1 ASU12RLF ASU15RLS2 ASU18RLF Outdoor unit ASU24RLF Air outlet shutter plate UTR-YDZB - - - - - - - Insulation kit for high humidity UTZ-KXGC - - - - - - - Fresh air intake kit UTZ-VXAA - - - - - - - External control set UTD-ECS5A - - - - - - - Extern
GENERAL INFORMATION GENERAL INFORMATION PARTS Air outlet shutter plate Models : UTR-YDZB Insulation kit for high humidity Model : UTZ-KXGC Insulation Kit For Compact Cassette type For Compact Cassette type Fresh air intake kit Model : UTZ-VXAA External control set (x1) (x2) (x1) (x2) For Compact Cassette type External connect kit For Slim Duct type Model : UTY-XWZX (x1) Model : UTD-ECS5A External connect kit Model : UTY-XWZXZ3 (x1) For Outdoor unit For Compact Cassette, Wall Mounte
GENERAL INFORMATION GENERAL INFORMATION PARTS Communication kit Model : UTY-XCBXZ1 For Wall Mounted (ASU7RLF, ASU9RLF, ASU12RLF) type Communication kit Communication kit Model : UTY-XCBXZ2 For Wall Mounted (ASU7RLF1, ASU9RLF1, ASU12RLF1) type Model : UTY-TWBXF For Wall Mounted (ASU9RLS2, ASU12RLS2, ASU15RLS2) type - (01 - 14) - 1.
Hybrid Flex Inverter System 2. MODEL SELECTION DTR_BMU004E_02--CHAPTER02 2013.12.
CONTENTS 2. MODEL SELECTION 1. MODEL SELECTION PROCEDURE............................................. 02 - 01 2. MODEL LINE UP............................................................................ 02 - 02 2-1.OUTDOOR UNIT........................................................................................ 02 - 02 2-2.INDOOR UNIT............................................................................................ 02 - 02 2-3.OPTIONAL PARTS......................................................
111MODEL SELECTION PROCEDURE See 2-2.MODEL LINE UP(INDOOR UNIT) and 3-1. SELECTION PROCEDURE OF INDOOR UNIT AND OUTDOOR UNIT Selection of required optional parts ●●Cassette grille for Compact Cassette type See 2-3.MODEL LINE UP(OPTIONAL PARTS) Selection of Branch box See 2-3.MODEL LINE UP(OPTIONAL PARTS) Selection of Separation tube See 2-3.
2MODEL LINE UP 22222OUTDOOR UNIT 5 48000 54000 Model name AOU48RLXFZ1 Connectable indoor unit Number Capacity (%) 2 to 8 80 to 130 MODEL SELECTION MODEL SELECTION HP Rated capacity (Btu/h) Cooling Heating 22222INDOOR UNIT Type Compact Cassette Slim Duct Wall Mounted Floor Rated capacity (Btu/h) Cooling Heating 7000 8100 9000 10200 12000 13500 18000 20000 7000 8100 9000 10200 12000 13500 18000 20000 24000 27000 7000 8100 9000 10200 12000 13500 14000 18000 24000 9000 12000 14000 16300
Items Central Remote Controller Wired Remote Controller Simple Remote Controller Model name Remarks UTY-DMMUM UTY-RNNUM Accessory: Compact Cassette, Slim Duct UTY-RSNUM UTY-LNHUM Accessory: Wall Mounted (ASU18RLF, ASU24RLF) AR-RAH1U Accessory: Wall Mounted (ASU7RLF, ASU9RLF, ASU12RLF) Wireless Remote Controller IR Receiver Unit AR-RED1U Accessory: Wall Mounted (ASU9RLS2, ASU12RLS2, AR-REG1U Accessory: Wall Mounted (ASU7RLF1, ASU9RLF1, ASU12RLF1), Floor UTY-LRHUM ASU15RLS2) CASSETTE GRILLE It
333MODEL SELECTION AND CAPACITY CALCULATION 33333 SELECTION PROCEDURE OF INDOOR UNIT AND OUTDOOR UNIT MODEL SELECTION MODEL SELECTION Please select indoor units and outdoor units and make the capacity of each indoor unit be larger than cooling and heating load.
33333THE EXAMPLE OF CALCULATION 3333333COOLING EXAMPLE EXAMPLE 1 (When the connecting capacity for indoor unit is 100% or more) Branch box Outdoor unit Branch Piping length, L2=32.8ft. (10m) Branch box MODEL SELECTION MODEL SELECTION Main Piping length, L1=32.8ft.
EXAMPLE 2 (When the connecting capacity for indoor unit is 100% or less) Branch box Outdoor unit Branch Piping length, L2=32.8ft. (10m) MODEL SELECTION MODEL SELECTION Main Piping length, L1=32.8ft. (10m) Branch box Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Room 1 Room 2 Room 3 Room 4 Design conditions zz Design temperature ●● Indoor : 75°F DB / 63°F WB (23.9°C DB / 17.2°C WB) Outdoor : 86°F DB (30°C DB) Pipe length ●● Main piping length : L1=32.8ft.
Indoor unit connecting capacity (%) ●●● 100 Outdoor temperature (°F) ●●● ●●● 23 32 41 50 59 68 77 86 95 104 115 70°F DB 60°F WB TC IP 75°F DB 63°F WB TC IP ●●● ●●● 45.0 45.0 45.0 45.0 45.0 44.0 43.0 41.6 39.9 38.2 35.5 ●●● ●●● 49.5 49.5 49.5 49.5 49.5 49.1 48.5 47.4 46.1 42.7 37.5 ●●● ●●● 2.00 2.08 2.12 2.16 2.21 2.45 2.80 3.81 4.67 5.01 4.75 Indoor temperature 80°F DB 85°F DB 67°F WB 71°F WB TC IP TC IP ●●● ●●● 2.11 2.14 2.19 2.25 2.40 2.63 3.20 4.15 4.95 5.12 4.97 ●●● ●●● 53.2 53.2 53.2 53.2 53.
y i) Refer to 4. CAPACITY TABLE to find Y1 and Y2 using X1 and X 2. ii) Calculate capacity of outdoor unit using following equation: (X2, Y2) Y=(Y2-Y1) / (X 2-X1) (X-X1) + Y1 (X, Y) (X1, Y1) x Capacity ratio of indoor units to outdoor unit, X (%) Indoor unit connecting capacity (%) 120 X2 ●●● 100 X1 Outdoor temperature (°F) 23 32 41 50 59 68 77 86 95 104 115 ●●● ●●● 23 32 41 50 59 68 77 86 95 104 115 70°F DB 60°F WB TC IP 75°F DB 63°F WB TC IP 53.2 53.2 53.2 53.2 53.2 53.2 50.8 47.8 45.
3333333HEATING EXAMPLE EXAMPLE 3 (When the connecting capacity for indoor unit is 100% or more) Branch box Outdoor unit Branch Piping length, L2=32.8ft. (10m) Branch box MODEL SELECTION MODEL SELECTION Main Piping length, L1=32.8ft. (10m) Branch box Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7 Indoor unit 8 Room 1 Room 2 Room 3 Room 4 Room 5 Room 6 Room 7 Room 8 Design conditions zz Design temperature ●● Indoor : 65°F DB (18.
EXAMPLE 4 (When the connecting capacity for indoor unit is 100% or more) Branch box Outdoor unit Branch Piping length, L2=32.8ft. (10m) Branch box MODEL SELECTION MODEL SELECTION Main Piping length, L1=32.8ft. (10m) Branch box Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7 Indoor unit 8 Room 1 Room 2 Room 3 Room 4 Room 5 Room 6 Room 7 Room 8 Design conditions zz Design temperature ●● Indoor : 65°F DB (18.
Indoor unit connecting capacity (%) ●●● 100 Outdoor temperature DB WB °F °F ●●● ●●● 5 14 23 32 41 47 50 59 68 75 ●●● ●●● 3 12 19 28 37 43 47 50 59 65 60°F DB TC IP ●●● ●●● 35.8 43.7 49.1 53.6 58.0 63.1 63.5 64.1 64.8 65.2 65°F DB TC IP ●●● ●●● 5.55 5.60 5.70 5.76 5.76 5.70 5.56 5.19 4.63 4.05 (c') ●●● ●●● 34.1 41.6 47.1 51.5 55.3 59.4 59.7 60.1 60.7 61.4 ●●● ●●● 5.52 5.61 5.78 5.78 5.61 5.35 5.25 4.80 4.45 3.92 Indoor temperature 70°F DB 75°F DB TC IP TC IP ●●● ●●● 32.8 40.3 45.4 49.5 51.2 54.
y i) Refer to 4. CAPACITY TABLE to find Y1 and Y2 using X1 and X 2. ii) Calculate capacity of outdoor unit using following equation: (X2, Y2) Y=(Y2-Y1) / (X 2-X1) (X-X1) + Y1 (X, Y) (X1, Y1) x Capacity ratio of indoor units to outdoor unit, X (%) Indoor unit connecting capacity (%) 120 X2 ●●● 100 X1 Outdoor temperature DB WB °F °F 5 14 23 32 41 47 50 59 68 75 ●●● ●●● 5 14 23 32 41 47 50 59 68 75 3 12 19 28 37 43 47 50 59 65 ●●● ●●● 3 12 19 28 37 43 47 50 59 65 60°F DB TC IP 38.9 49.5 53.
444CAPACITY TABLE (OUTDOOR UNIT) 44444COOLING CAPACITY COOLING CAPACITY MODEL : AOU48RLXFZ1 Indoor unit connecting capacity (%) 130 120 110 100 90 80 Outdoor temperature (°F) 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 70°F DB 60°F WB TC IP 75°F DB 63°F WB TC IP 57.0 57.0 57.0 57.0 57.0 57.0 53.9 49.5 46.4 42.0 37.5 53.2 53.2 53.
COOLING CAPACITY Indoor unit connecting capacity (%) 130 120 110 100 90 80 Outdoor temperature (°C) -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 21.1°CDB 15.6°CWB TC IP 23.9°CDB 17.2°CWB TC IP 16.7 16.7 16.7 16.7 16.7 16.7 15.
44444HEATING CAPACITY HEATING CAPACITY MODEL : AOU48RLXFZ1 Indoor unit connecting capacity (%) Outdoor temperature DB WB 60°F DB TC IP 65°F DB TC IP °F °F 130 5 14 23 32 41 47 50 59 68 75 3 12 19 28 37 43 47 50 59 65 40.9 51.2 53.9 58.0 61.4 64.8 67.2 69.6 70.6 71.0 5.59 5.66 5.76 5.86 5.93 5.98 5.98 5.98 5.98 4.22 39.2 50.2 53.2 57.0 60.7 63.8 66.5 68.9 69.9 70.3 5.61 5.67 5.77 5.88 5.95 5.98 5.98 5.98 5.98 4.35 120 5 14 23 32 41 47 50 59 68 75 3 12 19 28 37 43 47 50 59 65 38.9 49.
HEATING CAPACITY Indoor unit connecting capacity (%) Outdoor temperature DB WB 15.6°C DB TC IP 18.3°C DB TC IP °C °C 130 -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9 -16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3 12.0 15.0 15.8 17.0 18.0 19.0 19.7 20.4 20.7 20.8 5.59 5.66 5.76 5.86 5.93 5.98 5.98 5.98 5.98 4.22 11.5 14.7 15.6 16.7 17.8 18.7 19.5 20.2 20.5 20.6 5.61 5.67 5.77 5.88 5.95 5.98 5.98 5.98 5.98 4.35 120 -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9 -16.1 -11.1 -7.2 -2.2 2.
555CAPACITY COMPENSATION COEFFICIENT 55555COMPENSATION COEFFICIENT OF PIPE LENGTH The figures give the compensation coefficient of pipe length owing to installation position. MODEL SELECTION MODEL SELECTION Total compensation coefficient of pipe length multiplies compensation coefficient of branch piping by compensation coefficient of main piping. "Total compensation coefficient = main piping x branch piping" *1 *1: Branch piping use the value of the longest piping length.
CAPACITY CHANGE RATE BY BRANCH PIPING LENGTH Change rate in cooling capacity Change rate in heating capacity ft. 9.8 16.4 32.8 49.2 m 3 5 10 15 % 100 98.3 94.2 90.0 % 100 98.9 96.2 93.5 100 Change rate in capacity (%) Branch piping length 95 Heating 90 0 0 16.4 32.8 5 10 Branch piping length Cooling 49.2 (ft.) 15 (m) Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø1/2in. (12.
55555 COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING To take the effects of accumulated frost and defrosting operation on heating capacity into consideration, the capacity of outdoor units should be corrected by compensation coefficient shown in the table below. Actual heating capacity = The value of capacity table x Capacity change rate by frosting CAPACITY CHANGE RATE BY FROSTING Outdoor temperature Capacity change rate by frosting °FDB / °FWB °CDB / °CWB % 5.0 / 3.0 23.0 / 19.0 32.0 / 28.0 35.
666CAPACITY TABLE (INDOOR UNIT) 66666COOLING CAPACITY COOLING CAPACITY in kBtu/h 6666666COMPACT CASSETTE TYPE Outdoor temperature Indoor temperature (°FDB / °FWB) 70.0 / 60.0 72.0 / 61.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 88.0 / 72.0 90.0 / 73.0 (°FDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC 23.0 5.60 4.23 6.16 4.71 6.59 5.09 7.00 5.46 7.74 5.99 8.42 6.27 9.10 SHC 6.46 32.0 5.60 4.23 6.16 4.71 6.59 5.09 7.00 5.46 7.74 5.99 8.42 6.27 9.10 6.46 41.
COOLING CAPACITY in kW Outdoor temperature Indoor temperature (°CDB / °CWB) 21.1 / 15.6 22.2 / 16.1 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 31.1 / 22.2 32.2 / 22.8 (°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -5.0 1.63 1.23 1.80 1.37 1.92 1.48 2.04 1.59 2.25 1.75 2.45 1.83 2.65 1.88 0.0 1.63 1.23 1.80 1.37 1.92 1.48 2.04 1.59 2.25 1.75 2.45 1.83 2.65 1.88 5.0 1.63 1.23 1.80 1.37 1.92 1.48 2.04 1.59 2.25 1.75 2.45 1.83 2.65 1.88 10.
COOLING CAPACITY in kBtu/h 6666666SLIM DUCT TYPE Outdoor temperature Indoor temperature (°FDB / °FWB) 70.0 / 60.0 72.0 / 61.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 88.0 / 72.0 90.0 / 73.0 (°FDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC 23.0 5.60 4.34 6.16 4.84 6.59 5.22 7.00 5.60 7.74 6.15 8.42 6.44 9.10 SHC 6.64 32.0 5.60 4.34 6.16 4.84 6.59 5.22 7.00 5.60 7.74 6.15 8.42 6.44 9.10 6.64 41.0 5.60 4.34 6.16 4.84 6.59 5.22 7.00 5.60 7.74 6.
COOLING CAPACITY in kBtu/h Outdoor temperature Indoor temperature (°FDB / °FWB) 70.0 / 60.0 72.0 / 61.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 88.0 / 72.0 90.0 / 73.0 (°FDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 23.0 19.28 13.30 21.32 15.14 22.71 16.30 24.00 17.01 26.59 18.48 28.98 20.29 31.14 20.86 32.0 19.28 13.30 21.32 15.14 22.71 16.30 24.00 17.01 26.59 18.48 28.98 20.29 31.14 20.86 41.0 19.28 13.30 21.32 15.14 22.71 16.30 24.00 17.
COOLING CAPACITY in kW Outdoor temperature Indoor temperature (°CDB / °CWB) 21.1 / 15.6 22.2 / 16.1 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 31.1 / 22.2 32.2 / 22.8 (°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC -5.0 1.63 1.26 1.80 1.41 1.92 1.52 2.04 1.63 2.25 1.79 2.45 1.88 2.65 SHC 1.94 0.0 1.63 1.26 1.80 1.41 1.92 1.52 2.04 1.63 2.25 1.79 2.45 1.88 2.65 1.94 5.0 1.63 1.26 1.80 1.41 1.92 1.52 2.04 1.63 2.25 1.79 2.45 1.88 2.65 1.94 10.
COOLING CAPACITY in kW Outdoor temperature Indoor temperature (°CDB / °CWB) 21.1 / 15.6 22.2 / 16.1 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 31.1 / 22.2 32.2 / 22.8 (°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -5.0 5.65 3.90 6.25 4.44 6.65 4.78 7.02 4.98 7.79 5.42 8.49 5.95 9.13 6.11 0.0 5.65 3.90 6.25 4.44 6.65 4.78 7.02 4.98 7.79 5.42 8.49 5.95 9.13 6.11 5.0 5.65 3.90 6.25 4.44 6.65 4.78 7.02 4.98 7.79 5.42 8.49 5.95 9.13 6.11 10.
COOLING CAPACITY in kBtu/h 6666666WALL MOUNTED TYPE Outdoor temperature Indoor temperature (°FDB / °FWB) 70.0 / 60.0 72.0 / 61.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 88.0 / 72.0 90.0 / 73.0 (°FDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC 23.0 5.50 4.26 6.06 4.78 6.51 5.24 7.00 5.64 7.66 5.97 8.35 6.43 9.01 SHC 6.74 32.0 5.50 4.26 6.06 4.78 6.51 5.24 7.00 5.64 7.66 5.97 8.35 6.43 9.01 6.74 41.0 5.50 4.26 6.06 4.78 6.51 5.24 7.00 5.64 7.66 5.
COOLING CAPACITY in kW Outdoor temperature Indoor temperature (°CDB / °CWB) 21.1 / 15.6 22.2 / 16.1 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 31.1 / 22.2 32.2 / 22.8 (°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC -5.0 1.61 1.25 1.77 1.40 1.91 1.54 2.04 1.65 2.24 1.75 2.45 1.88 2.64 SHC 1.98 0.0 1.61 1.25 1.77 1.40 1.91 1.54 2.04 1.65 2.24 1.75 2.45 1.88 2.64 1.98 5.0 1.61 1.25 1.77 1.40 1.91 1.54 2.04 1.65 2.24 1.75 2.45 1.88 2.64 1.98 10.
COOLING CAPACITY in kBtu/h Outdoor temperature Indoor temperature (°FDB / °FWB) 70.0 / 60.0 72.0 / 61.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 88.0 / 72.0 90.0 / 73.0 (°FDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC 23.0 5.50 4.26 6.06 4.78 6.51 5.24 7.00 5.64 7.66 5.97 8.35 6.43 9.01 SHC 6.74 32.0 5.50 4.26 6.06 4.78 6.51 5.24 7.00 5.64 7.66 5.97 8.35 6.43 9.01 6.74 41.0 5.50 4.26 6.06 4.78 6.51 5.24 7.00 5.64 7.66 5.97 8.35 6.43 9.01 6.
COOLING CAPACITY in kW Outdoor temperature Indoor temperature (°CDB / °CWB) 21.1 / 15.6 22.2 / 16.1 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 31.1 / 22.2 32.2 / 22.8 (°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC -5.0 1.61 1.25 1.77 1.40 1.91 1.54 2.04 1.65 2.24 1.75 2.45 1.88 2.64 SHC 1.98 0.0 1.61 1.25 1.77 1.40 1.91 1.54 2.04 1.65 2.24 1.75 2.45 1.88 2.64 1.98 5.0 1.61 1.25 1.77 1.40 1.91 1.54 2.04 1.65 2.24 1.75 2.45 1.88 2.64 1.98 10.
MODEL : ASU9RLS2 Outdoor temperature Indoor temperature (°FDB / °FWB) 70.0 / 60.0 72.0 / 61.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 88.0 / 72.0 90.0 / 73.0 (°FDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 23.0 7.11 5.52 7.83 6.21 8.42 6.77 9.00 7.29 9.90 7.72 10.80 8.53 11.66 8.74 32.0 7.11 5.52 7.83 6.21 8.42 6.77 9.00 7.29 9.90 7.72 10.80 8.53 11.66 8.74 41.0 7.11 5.52 7.83 6.21 8.42 6.77 9.00 7.29 9.90 7.72 10.80 8.53 11.66 8.
MODEL : ASU9RLS2 Outdoor temperature Indoor temperature (°CDB / °CWB) 21.1 / 15.6 22.2 / 16.1 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 31.1 / 22.2 32.2 / 22.8 (°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -5.0 2.09 1.62 2.30 1.82 2.47 1.99 2.64 2.14 2.90 2.27 3.17 2.50 3.42 2.56 0.0 2.09 1.62 2.30 1.82 2.47 1.99 2.64 2.14 2.90 2.27 3.17 2.50 3.42 2.56 5.0 2.09 1.62 2.30 1.82 2.47 1.99 2.64 2.14 2.90 2.27 3.17 2.50 3.42 2.56 10.0 2.
COOLING CAPACITY in kBtu/h Outdoor temperature Indoor temperature (°FDB / °FWB) 70.0 / 60.0 72.0 / 61.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 88.0 / 72.0 90.0 / 73.0 (°FDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 23.0 14.23 10.03 15.67 11.47 16.84 12.50 18.00 13.69 19.82 14.57 21.62 15.02 22.52 15.31 32.0 14.23 10.03 15.67 11.47 16.84 12.50 18.00 13.69 19.82 14.57 21.62 15.02 22.52 15.31 41.0 14.23 10.03 15.67 11.47 16.84 12.50 18.00 13.
COOLING CAPACITY in kW Outdoor temperature Indoor temperature (°CDB / °CWB) 21.1 / 15.6 22.2 / 16.1 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 31.1 / 22.2 32.2 / 22.8 (°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -5.0 4.17 2.94 4.59 3.36 4.94 3.66 5.28 4.01 5.81 4.27 6.34 4.40 6.60 4.49 0.0 4.17 2.94 4.59 3.36 4.94 3.66 5.28 4.01 5.81 4.27 6.34 4.40 6.60 4.49 5.0 4.17 2.94 4.59 3.36 4.94 3.66 5.28 4.01 5.81 4.27 6.34 4.40 6.60 4.49 4.
MODEL SELECTION 6666666FLOOR TYPE MODEL : AGU9RLF Outdoor temperature Indoor temperature (°FDB / °FWB) 70.0 / 60.0 72.0 / 61.0 75.0 / 63.0 80.0 / 67.0 85.0 / 71.0 88.0 / 72.0 90.0 / 73.0 (°FDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 23.0 7.20 5.51 7.92 6.14 8.48 6.63 9.00 7.11 9.95 7.81 10.83 8.17 11.70 8.42 32.0 7.20 5.51 7.92 6.14 8.48 6.63 9.00 7.11 9.95 7.81 10.83 8.17 11.70 8.42 41.0 7.20 5.51 7.92 6.14 8.48 6.63 9.00 7.11 9.
MODEL : AGU9RLF Outdoor temperature Indoor temperature (°CDB / °CWB) 21.1 / 15.6 22.2 / 16.1 23.9 / 17.2 26.7 / 19.4 29.4 / 21.7 31.1 / 22.2 32.2 / 22.8 (°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC -5.0 2.11 1.62 2.32 1.80 2.49 1.94 2.64 2.09 2.92 2.29 3.18 2.40 3.43 SHC 2.47 0.0 2.11 1.62 2.32 1.80 2.49 1.94 2.64 2.09 2.92 2.29 3.18 2.40 3.43 2.47 5.0 2.11 1.62 2.32 1.80 2.49 1.94 2.64 2.09 2.92 2.29 3.18 2.40 3.43 2.47 10.0 2.
66666HEATING CAPACITY HEATING CAPACITY in kBtu/h 6666666COMPACT CASSETTE TYPE Outdoor Temperature (°FDB) 5.0 14.0 23.0 32.0 41.0 47.0 50.0 59.0 68.0 75.0 (°FWB) 3.0 12.0 19.0 28.0 37.0 43.0 47.0 50.0 59.0 65.0 60.0 TC 6.39 7.16 7.96 8.69 9.32 9.54 9.54 9.54 9.54 9.54 Indoor temperature (°FDB) 65.0 70.0 75.0 TC TC TC 5.90 5.43 4.95 6.60 6.08 0.00 7.34 6.76 6.17 8.02 7.38 6.74 8.60 7.91 7.23 8.80 8.10 7.40 8.80 8.10 7.40 8.80 8.10 7.40 8.80 8.10 7.40 8.80 8.10 7.
HEATING CAPACITY in kW Outdoor Temperature (°CDB) -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9 (°CWB) -16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3 15.6 TC 1.87 2.09 2.33 2.54 2.73 2.79 2.79 2.79 2.79 2.79 Indoor temperature (°CDB) 18.3 21.1 23.9 TC TC TC 1.73 1.59 1.45 1.93 1.78 0.00 2.15 1.98 1.80 2.35 2.16 1.97 2.52 2.32 2.11 2.58 2.37 2.16 2.58 2.37 2.16 2.58 2.37 2.16 2.58 2.37 2.16 2.58 2.37 2.16 MODEL SELECTION MODEL SELECTION MODEL : AUU7RLF 25.6 TC 1.26 1.41 1.57 1.72 1.84 1.88 1.
HEATING CAPACITY in kBtu/h 6666666SLIM DUCT TYPE Outdoor Temperature (°FDB) 5.0 14.0 23.0 32.0 41.0 47.0 50.0 59.0 68.0 75.0 (°FWB) 3.0 12.0 19.0 28.0 37.0 43.0 47.0 50.0 59.0 65.0 60.0 TC 6.39 7.16 7.96 8.69 9.32 9.54 9.54 9.54 9.54 9.54 Indoor temperature (°FDB) 65.0 70.0 75.0 TC TC TC 5.90 5.43 4.95 6.60 6.08 5.55 7.34 6.76 6.17 8.02 7.38 6.74 8.60 7.91 7.23 8.80 8.10 7.40 8.80 8.10 7.40 8.80 8.10 7.40 8.80 8.10 7.40 8.80 8.10 7.40 MODEL SELECTION MODEL SELECTION MODEL : ARU7RLF 78.0 TC 4.
HEATING CAPACITY in kW Outdoor Temperature (°CDB) -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9 (°CWB) -16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3 15.6 TC 1.87 2.09 2.33 2.54 2.73 2.79 2.79 2.79 2.79 2.79 Indoor temperature (°CDB) 18.3 21.1 23.9 TC TC TC 1.73 1.59 1.45 1.93 1.78 0.00 2.15 1.98 1.80 2.35 2.16 1.97 2.52 2.32 2.11 2.58 2.37 2.16 2.58 2.37 2.16 2.58 2.37 2.16 2.58 2.37 2.16 2.58 2.37 2.16 MODEL SELECTION MODEL SELECTION MODEL : ARU7RLF 25.6 TC 1.26 1.41 1.57 1.72 1.84 1.88 1.
HEATING CAPACITY in kBtu/h 6666666WALL MOUNTED TYPE Outdoor Temperature (°FDB) 5.0 14.0 23.0 32.0 41.0 47.0 50.0 59.0 68.0 75.0 (°FWB) 3.0 12.0 19.0 28.0 37.0 43.0 47.0 50.0 59.0 65.0 60.0 TC 6.34 7.10 7.89 8.62 9.24 9.46 9.46 9.46 9.46 9.46 Indoor temperature (°FDB) 65.0 70.0 75.0 TC TC TC 5.88 5.42 4.98 6.58 6.06 5.58 7.32 6.74 6.20 7.99 7.37 6.78 8.57 7.90 7.27 8.77 8.10 7.44 8.77 8.10 7.44 8.77 8.10 7.44 8.77 8.10 7.44 8.77 8.10 7.44 MODEL SELECTION MODEL SELECTION MODEL : ASU7RLF1 78.0 TC 4.
HEATING CAPACITY in kW Outdoor Temperature (°CDB) -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9 (°CWB) -16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3 15.6 TC 1.86 2.08 2.31 2.53 2.71 2.77 2.77 2.77 2.77 2.77 Indoor temperature (°CDB) 18.3 21.1 23.9 TC TC TC 1.72 1.59 1.46 1.93 1.78 1.64 2.14 1.98 1.82 2.34 2.16 1.99 2.51 2.32 2.13 2.57 2.37 2.18 2.57 2.37 2.18 2.57 2.37 2.18 2.57 2.37 2.18 2.57 2.37 2.18 MODEL SELECTION MODEL SELECTION MODEL : ASU7RLF1 25.6 TC 1.30 1.46 1.62 1.77 1.90 1.94 1.
MODEL SELECTION MODEL : ASU7RLF Outdoor Temperature (°FDB) 5.0 14.0 23.0 32.0 41.0 47.0 50.0 59.0 68.0 75.0 (°FWB) 3.0 12.0 19.0 28.0 37.0 43.0 47.0 50.0 59.0 65.0 60.0 TC 6.34 7.10 7.89 8.62 9.24 9.46 9.46 9.46 9.46 9.46 Indoor temperature (°FDB) 65.0 70.0 75.0 TC TC TC 5.88 5.42 4.98 6.58 6.06 5.58 7.32 6.74 6.20 7.99 7.37 6.78 8.57 7.90 7.27 8.77 8.10 7.44 8.77 8.10 7.44 8.77 8.10 7.44 8.77 8.10 7.44 8.77 8.10 7.44 MODEL SELECTION HEATING CAPACITY in kBtu/h 78.0 TC 4.44 4.97 5.53 6.04 6.48 6.
MODEL SELECTION MODEL : ASU7RLF Outdoor Temperature (°CDB) -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9 (°CWB) -16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3 15.6 TC 1.86 2.08 2.31 2.53 2.71 2.77 2.77 2.77 2.77 2.77 Indoor temperature (°CDB) 18.3 21.1 23.9 TC TC TC 1.72 1.59 1.46 1.93 1.78 1.64 2.14 1.98 1.82 2.34 2.16 1.99 2.51 2.32 2.13 2.57 2.37 2.18 2.57 2.37 2.18 2.57 2.37 2.18 2.57 2.37 2.18 2.57 2.37 2.18 MODEL SELECTION HEATING CAPACITY in kW 25.6 TC 1.30 1.46 1.62 1.77 1.90 1.94 1.
HEATING CAPACITY in kBtu/h Outdoor Temperature (°FDB) 5.0 14.0 23.0 32.0 41.0 47.0 50.0 59.0 68.0 75.0 (°FWB) 3.0 12.0 19.0 28.0 37.0 43.0 47.0 50.0 59.0 65.0 60.0 TC 8.00 8.95 9.95 10.87 11.66 11.93 11.93 11.93 11.93 11.93 Indoor temperature (°FDB) 65.0 70.0 75.0 TC TC TC 7.41 6.83 6.29 8.30 7.65 7.04 9.23 8.51 7.83 10.08 9.29 8.55 10.81 9.97 9.17 11.07 10.20 9.38 11.07 10.20 9.38 11.07 10.20 9.38 11.07 10.20 9.38 11.07 10.20 9.38 MODEL SELECTION MODEL SELECTION MODEL : ASU9RLS2 78.0 TC 5.60 6.
HEATING CAPACITY in kW Outdoor Temperature (°CDB) -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9 (°CWB) -16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3 15.6 TC 2.34 2.62 2.92 3.19 3.42 3.50 3.50 3.50 3.50 3.50 Indoor temperature (°CDB) 18.3 21.1 23.9 TC TC TC 2.17 2.00 1.84 2.43 2.24 2.06 2.71 2.49 2.29 2.96 2.72 2.51 3.17 2.92 2.69 3.24 2.99 2.75 3.24 2.99 2.75 3.24 2.99 2.75 3.24 2.99 2.75 3.24 2.99 2.75 MODEL SELECTION MODEL SELECTION MODEL : ASU9RLS2 25.6 TC 1.64 1.84 2.04 2.23 2.40 2.45 2.
HEATING CAPACITY in kBtu/h Outdoor Temperature (°FDB) 5.0 14.0 23.0 32.0 41.0 47.0 50.0 59.0 68.0 75.0 (°FWB) 3.0 12.0 19.0 28.0 37.0 43.0 47.0 50.0 59.0 65.0 60.0 TC 15.65 17.52 19.48 21.27 22.82 23.35 23.35 23.35 23.35 23.35 Indoor temperature (°FDB) 65.0 70.0 75.0 TC TC TC 14.51 13.37 12.30 16.24 14.97 13.77 18.06 16.65 15.32 19.73 18.18 16.73 21.16 19.50 17.94 21.66 20.00 18.36 21.66 20.00 18.36 21.66 20.00 18.36 21.66 20.00 18.36 21.66 20.00 18.
HEATING CAPACITY in kW Outdoor Temperature (°CDB) -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9 (°CWB) -16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3 15.6 TC 4.59 5.13 5.71 6.24 6.69 6.84 6.84 6.84 6.84 6.84 Indoor temperature (°CDB) 18.3 21.1 23.9 TC TC TC 4.25 3.92 3.61 4.76 4.39 4.04 5.29 4.88 4.49 5.78 5.33 4.90 6.20 5.72 5.26 6.35 5.85 5.38 6.35 5.85 5.38 6.35 5.85 5.38 6.35 5.85 5.38 6.35 5.85 5.38 MODEL SELECTION MODEL SELECTION MODEL : ASU18RLF 25.6 TC 3.19 3.58 3.98 4.34 4.66 4.77 4.
HEATING CAPACITY in kBtu/h 6666666FLOOR TYPE Outdoor Temperature (°FDB) 5.0 14.0 23.0 32.0 41.0 47.0 50.0 59.0 68.0 75.0 (°FWB) 3.0 12.0 19.0 28.0 37.0 43.0 47.0 50.0 59.0 65.0 60.0 TC 8.05 9.01 10.02 10.95 11.74 12.02 12.02 12.02 12.02 12.02 Indoor temperature (°FDB) 65.0 70.0 75.0 TC TC TC 7.43 6.83 6.24 8.32 7.65 9.24 9.25 8.51 7.77 10.10 9.29 8.48 10.83 9.97 9.10 11.09 10.20 9.31 11.09 10.20 9.31 11.09 10.20 9.31 11.09 10.20 9.31 11.09 10.20 9.
HEATING CAPACITY in kW Outdoor Temperature (°CDB) -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9 (°CWB) -16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3 15.6 TC 2.37 2.65 2.95 3.22 3.45 3.53 3.53 3.53 3.53 3.53 Indoor temperature (°CDB) 18.3 21.1 23.9 TC TC TC 2.18 2.01 1.84 2.45 2.25 2.71 2.72 2.50 2.28 2.97 2.73 2.50 3.19 2.93 2.68 3.26 3.00 2.74 3.26 3.00 2.74 3.26 3.00 2.74 3.26 3.00 2.74 3.26 3.00 2.74 MODEL SELECTION MODEL SELECTION MODEL : AGU9RLF 25.6 TC 1.60 1.79 1.99 2.17 2.33 2.39 2.
Hybrid Flex Inverter System 3. OUTDOOR UNIT & BRANCH BOX DTR_BMU004E_02--CHAPTER03 2013.12.
CONTENTS 3. OUTDOOR UNIT & BRANCH BOX 1. SPECIFICATIONS.......................................................................... 03 - 01 1-1.OUTDOOR UNIT........................................................................................ 03 - 01 1-2.ENERGY EFFICIENCIES........................................................................... 03 - 02 1-3.BRANCH BOX............................................................................................ 03 - 03 2. DIMENSIONS.........................
111SPECIFICATIONS Model name Power source Available Voltage Range Connectable indoor unit Cooling Max Capacity OUTDOOR UNITS Heating Cooling Input power *1 Heating Cooling Current *1 Heating Fan Type × Q'ty Airflow rate Motor Sound pressure level Heat exchanger Enclosure Weight Net Gross Net Gross Size Connection pipe Operation range Max Rated Max. Rated Max. Rated Max. Rated Max.
Combination of indoor unit Capacity Cooling Input power Current EER SEER Capacity OUTDOOR UNITS Heating Input power Current COP HSPF Btu/h kW kW A Btu/h/W Btu/h kW kW A W/W - non-Duct ASU12 x 4 48,000 14.1 5.19 23.0 9.25 17.0 54,000 15.8 4.89 21.7 3.23 9.8 Duct ARU12 x 4 48,000 14.1 5.52 24.5 8.70 14.7 54,000 15.8 5.02 22.3 3.15 9.3 Mix 48,000 14.1 5.35 23.7 8.97 15.8 54,000 15.8 4.96 22.0 3.19 9.5 Note : Specifications are based on the ARI Standard 210/240.
Model name Casing color Connectable indoor unit Max. combination Min. combination Power source Available voltage range Input Power Running current Refrigerant type Net Dimensions (H × W × D) Gross Net Weight Gross Connection pipe Operation range Liquid Gas Method Size Btu/h Btu/h W A in. (mm) lbs (kg) in. (mm) °F (°C) %RH UTP-PU03A (Primary) Paintingless 1 to 3 Units 62,000 7,000 1 Phase 208/230V 60Hz 187-264V 10 0.
222DIMENSIONS 22222OUTDOOR UNIT MODEL : AOU48RLXFZ1 1-7/16 (36) 15/16 (24) OUTDOOR UNITS 14-9/16 (370) 15/16 (24) 1-7/8 (48) OUTDOOR UNITS Top view 1-9/16 (40) 6-1/16 (154) 2 (51): Gas 16-1/8 (410) 25-9/16 (650) 1-11/16 (43): Liquid 6-9/16 (166) Unit : in.
22222BRANCH BOX MODELS : UTP-PU03A, UTP-PU03B 8-7/16 (214) Unit : in.
333INSTALLATION SPACE Caution ●●The installation space shown in the following examples is based on an ambient temperature under cooling operation of 95 °F DB (35 °C DB) at the air intake of the outdoor unit. Provide more space around the air intake than shown in the examples if the ambient temperature exceeds 95 °F DB (35 °C DB) or if the thermal load of all of the outdoor units exceeds the capacity.
3333333MULTIPLE OUTDOOR UNIT INSTALLATION Provide at least 1in. (25mm) of space between the outdoor units if multiple units are installed. ●● When routing the piping from the side of an outdoor unit, provide space for the piping. ●● No more than 3 units must be installed side by side. ●● When 3 units or more are arranged in a line, provide the space as shown in the following example when an obstruction is present also in the upward area.
33333BRANCH BOX The branch box can be installed onto the wall or hanging from the ceiling. ●● The branch box can be installed and set horizontally or vertically. ●● Provide a service access for maintenance and inspection purposes as shown in the figure ●● below. It is not necessary to provide drainage for the branch box. ●● The slope of the top side must be within ±5° in all directions of the horizontal plane.
3333333VERTICAL INSTALLATION A vertical installation can only be performed when mounting on the wall. ●● (A vertical installation cannot be hung from the ceiling.) Be sure to install the control box so that the top side faces up. ●● The positioning of the control box cannot be changed when performing a vertical installation.
444REFRIGERANT CIRCUIT Branch box 1 (primary type) Outdoor unit TH11 HEX TH10 3WV 0 TH10 Strainer 4WV HP-SW Strainer HEX TH10 0 TH11 TH12 HPS EEV4 Strainer Comp ressor EEV1 TH2 SCHEX HEX TH8 TH6 SV TH4 TH3 LPS TH5 EEV3 Strainer 3WV Strainer EEV3 TH7 Indoor unit 2 Indoor unit 3 0 TH12 TH9 OUTDOOR UNITS OS HEX TH1 OUTDOOR UNITS TH11 TH12 Indoor unit 1 Strainer TH9 Strainer EEV3 TH9 EEV2 Branch box 2 (secondary type) Accumu lator TH11 HEX TH10 0 TH12 TH10 St
SYMBOL DESCRIPTION MARK HEX OS SCHEX HPS HP-SW LPS 4WV 3WV EEV 1 EEV 2 SV TH 1 TH 2 TH 3 TH 4 TH 5 TH 6 TH 7 TH 8 DESCRIPTION Heat exchanger Oil separator Sub-cool heat exchanger High pressure sensor High pressure sensor switch Low pressure sensor 4-way valve 3-way valve Electric expansion valve 1 Electric expansion valve 2 Solenoid valve Discharge temperature thermistor Compressor temperature thermistor Suction temperature thermistor Outdoor temperature thermistor Heat exchanger (outlet) thermistor Sub
555WIRING DIAGRAM 55555OUTDOOR UNIT OUTDOOR UNITS OUTDOOR UNITS MODELS : AOU48RLXFZ1 - (03 - 12) - 3.
55555BRANCH BOX OUTDOOR UNITS OUTDOOR UNITS MODEL : UTP-PU03A (Primary) MODEL : UTP-PU03B (Secondary) - (03 - 13) - 3.
666OPERATION RANGE Operation mode Cooling / Dry Heating Operation range Indoor unit Outdoor unit 64 to 90°F DB 23 to 115°F DB (18 to 32°C DB) (-5 to 46°C DB) R.H. 80% or less 60 to 88°F DB 5 to 75°F DB (16 to 31°C DB) (-15 to 24°C DB) OUTDOOR UNITS OUTDOOR UNITS R.H. : Relative Humidity. - (03 - 14) - 3.
777NOISE LEVEL CURVE MODEL : AOU48RLXFZ1 Cooling zz Heating 80 80 70 70 N C -65 N C -60 N C -55 50 N C -50 N C -45 40 N C -40 N C -35 30 N C -30 N C -25 20 N C -20 60 N C -60 N C -55 50 N C -50 N C -45 40 N C -40 N C -35 30 N C -30 N C -25 20 N C -20 N C -15 N C -15 10 10 0 0 63 125 250 500 1,000 2,000 4,000 8,000 Octave band center frequency, Hz 63 125 250 500 1,000 2,000 4,000 8,000 Octave band center frequency, Hz - (03 - 15) - 3.
SOUND LEVEL CHECK POINT Air flow OUTDOOR UNITS OUTDOOR UNITS Microphone 40in. (1 m) - (03 - 16) - 3.
8ELECTRIC CHARACTERISTICS 88888OUTDOOR UNIT Power Supply Model name OUTDOOR UNITS AOU48RLXFZ1 Hz 60 Electric Characteristics Full Load Characteristics Voltage MCA TOCA MSC (V) (A) (A) (A) 208/230 26.5 45 23.4 Comp Wiring Specifications *1 MAX. CKT. BKR (A) Power Cable AWG size Earth Cable AWG size Cross-section Cross-section 40 8 8 resser Outdoor Fan Motor Limited Wiring RLA Output FLA Length*2 (A) (kW) (A) 21 0.11 0.9 49/55 (ft.
999SAFETY DEVICES 99999OUTDOOR UNIT Safety device Protector Main PCB AC 250V 3.15A INV PCB DC 400V 5A Filter AC 250V 10A AC 250V 3.15A Filter AC 500V 50A OUTDOOR UNITS Compressor Protector High Pressure Protection Low Pressure Protection Overcurrent protection Temperature protection Off : 239°F (115°C) On : 158°F (70°C) Off : 609psi (4.2MPa) On : 464psi (3.2MPa) Off : 7.25psi (0.05MPa) 99999BRANCH BOX Safety device Fuse UTP-PU03A, UTP-PU03B AC 250V 3.
Hybrid Flex Inverter System 4. INDOOR UNITS DTR_BMU004E_02--CHAPTER04 2013.12.
CONTENTS 4. INDOOR UNITS 1. FEATURES.................................................................................... 04 - 01 1-1. COMPACT CASSETTE TYPE................................................................. 04 - 01 1-2. SLIM DUCT TYPE.................................................................................... 04 - 02 1-3. WALL MOUNTED TYPE ......................................................................... 04 - 03 1-4. FLOOR TYPE ..................................................
CONTENTS 4. INDOOR UNITS 9. NOISE LEVEL CURVE................................................................... 04 - 78 9-1. COMPACT CASSETTE TYPE................................................................. 04 - 78 9-2. SLIM DUCT TYPE.................................................................................... 04 - 80 9-3. WALL MOUNTED TYPE.......................................................................... 04 - 83 9-4. FLOOR TYPE...........................................................
111 FEATURES 11111COMPACT CASSETTE TYPE MODELS : AUU7RLF, AUU9RLF, AUU12RLF, AUU18RLF FEATURES Quiet quality zz High efficiency design by 2 stage structure Wind velocity INDOOR UNITS Fast Previous turbo fan 2-stage turbo fan In the case of a conventional fan, the air outlet range was narrow as the airflow moved to the motor side which meant the velocity of air passing through the heat exchanger was uneven.
11111SLIM DUCT TYPE MODELS : ARU7RLF, ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF Slim design and wide range of static pressure for flexible installation. FEATURES Air - intake zz This model is slim design, it can install at the place where a ceiling is narrow. Air intake direction can be selected to match the installation site. Drain port Height 7-13/16 in.
11111WALL MOUNTED TYPE MODELS : ASU7RLF1, ASU9RLF1, ASU12RLF1 FEATURES High efficient compact design zz More comfortable airflow Making the tube thin: Thin: 0.276inch (7mm) ▼ 0.197inch (5mm) Volume reduction of heat INDOOR UNITS 30% INDOOR UNITS exchanger: Quiet operation zz INDOOR UNIT Airflow mode can be set in 4 steps and more detailed airflow setting is possible. 21dB only at cooling operation (22dB at heating operation). Fan speed Noise level Quiet 21dB(A) (ASU7/9/12RLF1) MIN.
MODELS : ASU7RLF, ASU9RLF, ASU12RLF Compact and Stylish design indoor unit FEATURES High density heat transfer tube zz arrangement Ø5 Making the tube Thin: 0.276in. (7mm)→ Easy maintenance zz Removable & washable panel 0.197in. (5 mm) INDOOR UNITS exchanger: 30% Dry operation Dry operation removes moisture and keeps the air conditioner clean.
MODELS : ASU9RLS2, ASU12RLS2, ASU15RLS2 FEATURES Thin & Slim design zz Thin and slim design is realized by Ø5mm heat exchanger and high efficiency wind blower. Big open panel and High density multi path heat exchanger Large intake Refrigerant Ø3/16in. (Ø5mm) Open panel Large fan 7-5/16 in. (185mm) Distributor 4-path 13/16 in. (20mm) INDOOR UNITS Powerful operation zz *Only available with Wireless RC.
MODELS : ASU18RLF, ASU24RLF Simple & Elegant Appearance Design FEATURES Compact & Slim design zz 39-5/16in. (998 mm) “ Vertical airflow” provides powerful floor level heating zz ft.(m) 16 (24/30) INDOOR UNITS INDOOR UNITS 7 (2.1) 3 (1) 0 46o Outside air conditions: 35.6oF (2o C) 60% Operation contents: Heating Set temperature (Max set temp) 86oF (30oC), Air flow Hi Vertical flap : Downward Horizontal flap : Center 10 (3) 20 (6) 92 90 88 86 33 32 31 30 30 (9) 40 (12) ft.
11111FLOOR TYPE MODELS : AGU9RLF, AGU12RLF, AGU15RLF FEATURES 2-Fan & Wide airflow zz Cooling Prevents cold air from falling Heating at operation start at stable operation at operation start Prevents cold draft from window Window at stable operation Unit: in. (mm) Beneath standard window Standard concave portion Wall Half concealed Min.37 (940) 27-9/16 (700) 23-5/8 (600) 29-1/8 (740) Min. 23-1/4 (590) Min. 27-9/16 (700) Min. 28-3/4 (730) Max. 5-7/8 (150) 7-7/8 (200) Max.
222 SPECIFICATIONS Model name Power source Available voltage range AUU7RLF Btu/h kW Btu/h kW W A Cooling Rated Capacity Heating Rated Input Power Running current Cooling Fan Airflow rate Heating High Med Low Quiet High Med Low Quiet INDOOR UNITS Fan Type × Q'ty Fan Motor Output Cooling Sound pressure level Heating W High Med Low Quiet High Med Low Quiet Dimension (H×W×D) Heat exchanger Dimensions ( H×W×D ) Weight Connection pipe Operation range Drain hose Cassette grille CFM (m3/h) Fin pitch R
22222SLIM DUCT TYPE ARU7RLF Cooling Rated Capacity Heating Rated Input Power Running current Fan High Med Cooling Low Quiet Airflow rate High Med Heating Low Quiet Fan type ×Q'ty Fan motor output INDOOR UNITS Recommended static pressure Sound pressure level High Med Cooling Low Quiet High Med Heating Low Quiet Dimension(H × W × D) Heat exchanger Enclosure Fin pitch Rows × Stages Pipe type Fin Type Material Color Net Dimensions ( H × W ×D ) Gross Weight Connection pipe Drain hose Net Gross Size
22222WALL MOUNTED TYPE Cooling Rated Capacity Heating Rated INDOOR UNITS Input Power Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type × Q'ty Fan motor output High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H × W × D) Heat exchanger Enclosure Fin pitch Rows × Stages Pipe type Fin Type Material ASU7RLF1 Btu/h kW Btu/h kW W A CFM (m3/h) W dB(A) in.
Cooling Rated Capacity Heating Rated INDOOR UNITS Input Power Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type × Q'ty Fan motor output High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H × W × D) Heat exchanger Enclosure Fin pitch Rows × Stages Pipe type Fin Type Material ASU7RLF Btu/h kW Btu/h kW W A CFM (m3/h) W dB(A) in. (mm) FPI Color Dimensions Net (H × W × D) Gross Net Weight Gross in.(mm) lbs.
Cooling Rated Capacity Heating Rated INDOOR UNITS Input power Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type × Q'ty Fan motor output High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H × W × D) Heat exchanger Enclosure Fin pitch Rows × Stages Pipe type Fin Type Material ASU9RLS2 Btu/h kW Btu/h kW W A CFM (m3/h) W dB(A) in.(mm) FPI Color Dimensions Net (H × W × D) Gross Net Weight Gross in.(mm) lbs.
Model name Power source Available voltage range Capacity Heating Rated INDOOR UNITS Input Power Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type × Q'ty Fan motor output High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H × W × D) Heat exchanger Enclosure Fin pitch Rows × Stages Pipe type Fin Type Material Btu/h kW Btu/h kW W A CFM (m3/h) W dB(A) in.
22222FLOOR TYPE Cooling Rated Capacity Heating Rated INDOOR UNITS Input Power Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type × Q'ty Fan motor output High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H × W × D) Fin pitch Heat Rows × Stages exchanger Pipe type Fin Type Material Enclosure Color Dimensions Net (H × W × D) Gross Net Weight Gross Btu/h kW Btu/h kW W A CFM (m3/h) W dB(A) in. (mm) FPI in.(mm) lbs.
Type Compact Cassette Slim Duct INDOOR UNITS Wall Mounted Floor Model name Hz AUU7RLF AUU9RLF AUU12RLF AUU18RLF ARU7RLF ARU9RLF ARU12RLF ARU18RLF ARU24RLF ASU7RLF1 ASU9RLF1 ASU12RLF1 ASU7RLF ASU9RLF ASU12RLF ASU9RLS2 ASU12RLS2 ASU15RLS2 ASU18RLF ASU24RLF AGU9RLF AGU12RLF AGU15RLF 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 Power Supply Voltage (V) 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 2
444DIMENSIONS 44444COMPACT CASSETTE TYPE MODELS : AUU7RLF, AUU9RLF, AUU12RLF, AUU18RLF • Cassette grille mounting state Maintenance space Be sure to leave maintenance space for future service at the designated position. Min.
INSTALLATION PLACE Unit : in. (mm) Strong and durable ceiling 11 (262) or more H 40 (1000) or more 95 (2400) or more 40 (1000) or more INDOOR UNITS INDOOR UNITS Obstruction Floor Model name Standard mode High Ceiling mode H (The maximum height from floor to ceiling) Unit: in.
44444SLIM DUCT TYPE MODELS : ARU7RLF, ARU9RLF, ARU12RLF Unit : in. (mm) 2 (51) 6 (152) 6-17/8 (174) 22-5/8 (574) View A 2-13/16 (71) Rear view 1-3/16 (30) 1-7/8 (47) 2-3/16 (55) 25-9/16 (650) 28-7/8 (734) 3-7/32 (82) 2-3/16 (55) 6-9/16 (167) Side view 1-11/16 (43) 13/16 (20) 25-9/16 (650) 26-1/8 (664) 27-9/16 (700) Front view Bottom view Refrigerant pipe flare connection Drain hose connection Liquid Gas Drain hose ARU7, ARU9, ARU12 ø 1/4 in. (ø 6.35 mm) ø 3/8 in. (ø 9.
MODEL : ARU18RLF 2-13/16 (71) Rear view 6 (152) 2 (51) 6-7/8 (174) 30-1/2 (774) Unit : in.
MODEL : ARU24RLF 6-7/8 (174) 2-13/16 (71) 2 (51) 6 (152) 38-3/8 (974) Unit : in. (mm) View A 1-3/16 (30) Rear view (Drain hose) 3-15/16 (100) x 10 = 39-3/8 (1000) 2-3/16 (55) 3-7/16 (87) 4-11/16 (119) 2-3/16 (56) 6-9/16 (167) Side view 1-11/16 (43) 13/16 (20) 43-5/16 (1100) Front view Bottom view Refrigerant pipe flare connection Drain hose connection Liquid Gas Drain hose ARU24 ø 1/4 in. (ø 6.35 mm) ø 5/8 in. (ø 15.88 mm) I.D.: Ø 1 in.(Ø 25 mm), O.D.: Ø 1-1/4 in.
Unit : in.
Unit : in. (mm) MAINTENANCE SPACE Provide a service access for inspection purposes as shown below. Do not place any wiring or illumination in the service space, as they will impede service. Service access Unit 12 (300) or more 4 (100) or more Control box 12 (300) or more INDOOR UNITS INDOOR UNITS Service space - (04 - 22) - 4.
44444WALL MOUNTED TYPE MODELS : ASU7RLF1, ASU9RLF1, ASU12RLF1 Unit : in.
INSTALLATION PLACE Unit : in. (mm) 1 (25) or more 3 (52) or more 6 (130) or more 71 (1800) or more INDOOR UNITS 60 (1500) or more INDOOR UNITS 3 (70) or more 3 (63) or more 2 (45) or more Outline of unit - (04 - 24) - 4.
MODELS : ASU7RLF, ASU9RLF, ASU12RLF Unit : in.
INSTALLATION PLACE 3 (63) or more 2 (45) or more Unit : in. (mm) 2 (48) or more 3 (70) or more 4 (100) or more 60 (1500) or more - (04 - 26) - 4.
MODELS : ASU9RLS2, ASU12RLS2, ASU15RLS2 11-1/8 (282) Unit : in.
INSTALLATION PLACE INDOOR UNITS INDOOR UNITS Outline of Unit 5 (120) or more 4 (100) or more Unit : in. (mm) 2 (50) or more 2 (50) or more 7 (160) or more 7 (160) or more 71 (1800) or more 14 (337) 3 (55) 60 (1500) or more - (04 - 28) - 10 (247) 4.
MODELS : ASU18RLF, ASU24RLF Unit : in.
INSTALLATION PLACE 4 (80) or more 3 (63) or more Unit : in. (mm) 3 (53) or more 4 (80) or more 5 (120) or more 60 (1500) or more - (04 - 30) - 4.
44444FLOOR TYPE MODELS : AGU9RLF, AGU12RLF, AGU15RLF Unit : in. (mm) INDOOR UNITS INDOOR UNITS 23-5/8 (600) 7-7/8 (200) 29-1/8 (740) Side view Front view INSTALLATION PLACE 4 (80) or more 4 (100) or more 4 (80) or more 2 (50) or more 4 (100) or below from the floor - (04 - 31) - 4.
555 WIRING DIAGRAMS 55555COMPACT CASSETTE TYPE INDOOR UNITS INDOOR UNITS MODELS : AUU7RLF, AUU9RLF, AUU12RLF, AUU18RLF - (04 - 32) - 4.
55555SLIM DUCT TYPE INDOOR UNITS INDOOR UNITS MODELS : ARU7RLF, ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF - (04 - 33) - 4.
55555WALL MOUNTED TYPE INDOOR UNITS INDOOR UNITS MODELS : ASU7RLF1, ASU9RLF1, ASU12RLF1 - (04 - 34) - 4.
INDOOR UNITS INDOOR UNITS MODELS : ASU7RLF, ASU9RLF, ASU12RLF - (04 - 35) - 4.
INDOOR UNITS INDOOR UNITS MODELS : ASU9RLS2, ASU12RLS2, ASU15RLS2 - (04 - 36) - 4.
INDOOR UNITS INDOOR UNITS MODELS : ASU18RLF, ASU24RLF - (04 - 37) - 4.
55555FLOOR TYPE INDOOR UNITS INDOOR UNITS MODELS : AGU9RLF, AGU12RLF, AGU15RLF - (04 - 38) - 4.
666 AIR VELOCITY AND TEMPERATURE DISTRIBUTIONS 66666COMPACT CASSETTE TYPE Conditions Fan speed : High Operation mode : FAN MODEL : AUU7RLF, AUU9RLF Air velocity distribution zz Top view Vertical airflow direction louver : Up (ft.) (m) 13 4 10 3 7 2 3 1 Unit : ft./s (m/s) 1 (0.25) 2 (0.5) 7 (2.0) 0 3 (1.0) 7 (2.0) 2 (0.5) 0 INDOOR UNITS INDOOR UNITS 3 (1.0) 1 (0.25) 2 (0.5) 1 (0.25) 7 (2.0) 7 (2.0) 3 (1.0) 3 1 7 2 2 (0.5) 10 3 1 (0.25) 13 4 3 (1.
Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical airflow direction louver: Downward (4Way) Air velocity distribution zz Side view Vertical airflow direction louver : Down (ft.) (m) 2.7 8 2.5 7 2 Unit : ft./s (m/s) 7 (2.0) 7 (2.0) 5 (1.5) 5 (1.5) 3 (1.0) 3 (1.0) 2 (0.5) 1 0 0 INDOOR UNITS 3 2 (0.5) 1 (0.25) 1 (0.25) 4 3 2 1 0 1 2 3 4 (m) 13 10 7 3 0 3 7 10 13 (ft.
Conditions Fan speed : High Operation mode : FAN MODEL : AUU12RLF Air velocity distribution zz Top view Vertical airflow direction louver : Up (ft.) (m) 13 Unit : ft./s (m/s) 4 10 3 7 2 3 1 2 (0.5) 3 (1.0) 7 (2.0) 0 2 (0.5) 0 7 (2.0) 7 (2.0) 3 (1.0) 1 1 (0.25) 2 (0.5) 1 (0.25) 3 3 (1.0) 7 (2.0) INDOOR UNITS INDOOR UNITS 1 (0.25) 3 (1.0) 7 2 10 3 2 (0.5) 1 (0.25) 13 4 4 13 3 10 2 1 7 3 0 0 1 2 3 7 3 10 4 (m) 13 (ft.
Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical airflow direction louver: Downward (4Way) Air velocity distribution zz (ft.) (m) 9 2.7 8 2.5 7 2 Unit : ft./s (m/s) 5 (1.5) 5 (1.5) 3 (1.0) 1 0 0 1 (0.25) 4 13 INDOOR UNITS 2 (0.5) 3 1 (0.25) 2 10 7 1 3 0 0 1 3 2 3 7 10 4 (m) 13 (ft.) INDOOR UNITS 3 3 (1.0) 2 (0.5) Air temperature distribution zz (ft.) (m) 9 2.7 8 2.
Conditions Fan speed : High Operation mode : FAN MODEL : AUU18RLF Air velocity distribution zz Top view Vertical airflow direction louver : Up (ft.) (m) 13 Unit : ft./s (m/s) 4 1 (0.25) 10 3 7 2 2 (0.5) 3 1 7 (2.0) 0 2 (0.5) 0 3 (1.0) 1 (0.25) 3 7 (2.0) 1 (0.25) 3 (1.0) 7 (2.0) INDOOR UNITS INDOOR UNITS 3 (1.0) 2 (0.5) 7 (2.0) 1 3 (1.0) 7 2 10 3 2 (0.5) 1 (0.25) 13 4 4 13 3 2 10 1 7 3 0 0 1 2 3 3 7 10 4 (m) 13 (ft.
Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical airflow direction louver: Downward (4Way) Air velocity distribution zz (ft.) (m) 9 2.7 8 2.5 7 2 Unit : ft./s (m/s) 7 (2.0) 7 (2.0) 5 (1.5) 5 (1.5) 3 (1.0) 3 (1.0) 2 (0.5) 1 0 0 1 (0.25) 4 13 INDOOR UNITS 2 (0.5) 3 1 (0.25) 2 10 7 1 3 0 0 1 3 2 3 7 10 4 (m) 13 (ft.) INDOOR UNITS 3 Air temperature distribution zz (ft.) (m) 9 2.7 8 2.
66666SLIM DUCT TYPE with Auto louver grille kit MODEL : ARU7RLF Conditions Fan speed : High Operation mode : Fan Voltage : 230V Note: This data is measured installing the Auto louver grille kit(option). Air velocity distribution zz (ft.) (m) Top view 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Center 3 1 7 2 Unit : ft./s (m/s) 7 (2) 3 (1) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.) Unit : ft.
Reference Data Conditions Fan speed : High Operation mode : Heating Voltage : 230V Note: This data is measured installing the Auto louver grille kit(option). Air velocity distribution zz (ft.) (m) Unit : ft./s (m/s) 10 3 2.5 Vertical airflow direction louver : Down 7 2 Horizontal airflow direction louver : Center 3 1 0 0 INDOOR UNITS 7 (2) 3 (1) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.
Conditions Fan speed : High Operation mode : Fan Voltage : 230V MODEL : ARU9RLF Note: This data is measured installing the Auto louver grille kit(option). Air velocity distribution zz (ft.) (m) Top view 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Center 3 1 7 2 Unit : ft./s (m/s) 7 (2) 3 (1) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.) Unit : ft./s (m/s) (ft.) (m) 16 5 13 4 2 (0.
Reference Data Conditions Fan speed : High Operation mode : Heating Voltage : 230V Note: This data is measured installing the Auto louver grille kit(option). Air velocity distribution zz (ft.) (m) Unit : ft./s (m/s) 10 3 2.5 Vertical airflow direction louver : Down 7 2 Horizontal airflow direction louver : Center 3 1 0 0 INDOOR UNITS 7 (2) 3 (1) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.
Conditions Fan speed : High Operation mode : Fan Voltage : 230V MODELS : ARU12RLF Note: This data is measured installing the Auto louver grille kit(option). Air velocity distribution zz (ft.) (m) Top view 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Center 3 1 7 2 Unit : ft./s (m/s) 7 (2) 3 (1) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.) Unit : ft./s (m/s) (ft.) (m) 16 5 13 4 2 (0.
Reference Data Conditions Fan speed : High Operation mode : Heating Voltage : 230V Note: This data is measured installing the Auto louver grille kit(option). Air velocity distribution zz (ft.) (m) Unit : ft./s (m/s) 10 3 8 2.5 Vertical airflow direction louver : Down 7 2 Horizontal airflow direction louver : Center 3 1 0 0 7 (2) 3 (1) 2 (0.5) 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.
Conditions Fan speed : High Operation mode : Fan Voltage : 230V MODELS : ARU18RLF Note: This data is measured installing the Auto louver grille kit(option). Air velocity distribution zz (ft.) (m) Top view 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Center 3 1 7 2 Unit : ft./s (m/s) 7 (2) 3 (1) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.) (ft.) (m) Unit : ft./s (m/s) 16 5 13 4 2 (0.
Reference Data Conditions Fan speed : High Operation mode : Heating Voltage : 230V Note: This data is measured installing the Auto louver grille kit(option). Air velocity distribution zz (ft.) (m) Unit : ft./s (m/s) 10 3 8 2.5 Vertical airflow direction louver : Down 7 2 Horizontal airflow direction louver : Center 3 1 0 0 7 (2) 3 (1) 2 (0.5) 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.
Conditions Fan speed : High Operation mode : Fan Voltage : 230V MODEL : ARU24RLF Note: This data is a measurement of Auto louver grille kit(option) by installing it. Air velocity distribution zz (ft.) (m) Top view 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Center 3 1 7 2 Unit : ft./s (m/s) 7 (2) 3 (1) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.) (ft.) (m) Unit : ft./s (m/s) 16 5 2 (0.
Conditions Fan speed : High Operation mode : Heat Voltage : 230V Reference Data Note: This data is a measurement of Auto louver grille kit(option) by installing it. Air velocity distribution zz (ft.) (m) Unit : ft./s (m/s) 10 3 8 2.5 Vertical airflow direction louver : Down 7 2 Horizontal airflow direction louver : Center 3 1 0 0 7 (2) 3 (1) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 10 (m) 0 3 7 10 13 16 20 23 26 29 32 (ft.
66666WALL MOUNTED TYPE Conditions Fan speed : High Operation mode : Fan MODEL : ASU7RLF1 (ft.) (m) Unit : ft./s (m/s) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center 7 2 3 1 0 0 3 1 7 2 7 (2.0) 3 (1.0) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 (m) 0 3 7 10 13 16 20 23 26 29 (ft.) 10 3 7 2 Top view 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Right & Left 3 1 7 2 10 3 3 (1.
Conditions Fan speed : High Operation mode : Fan MODEL : ASU9RLF1 (ft.) (m) Unit : ft./s (m/s) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center 7 2 3 1 0 0 3 1 7 2 7 (2.0) 3 (1.0) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 (m) 0 3 7 10 13 16 20 23 26 29 (ft.) 10 3 7 2 Top view 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Right & Left 3 1 7 2 10 3 INDOOR UNITS INDOOR UNITS (ft.
Conditions Fan speed : High Operation mode : Fan MODEL : ASU12RLF1 (ft.) (m) Unit : ft./s (m/s) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center 7 2 3 1 0 0 3 1 7 2 7 (2.0) 3 (1.0) 2 (0.5) 0 1 2 3 4 5 6 7 8 9 (m) 0 3 7 10 13 16 20 23 26 29 (ft.) 10 3 7 2 Top view 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Right & Left 3 1 7 2 10 3 3 (1.0) 7 (2.
Conditions Fan speed : High Operation mode : Fan MODELS : ASU7RLF Unit : ft./s (m/s) (ft.) (m) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center 7 2 3 1 0 0 3 1 7 2 2 (0.5) 3 (1.0) 7 (2.0) (m) 0 1 2 3 4 5 6 7 8 0 3 7 10 13 16 20 23 26 (ft.) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Right & Left 10 3 7 2 3 1 0 0 INDOOR UNITS INDOOR UNITS (ft.) (m) 7 (2.0) 2 (0.5) 3 (1.
Conditions Fan speed : High Operation mode : Fan MODELS : ASU9RLF Unit : ft./s (m/s) (ft.) (m) 7 2 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Center 3 1 7 2 Top view 3 (1.0) 7 (2.0) 2 (0.5) (m) 0 1 2 3 4 5 6 7 8 0 3 7 10 13 16 20 23 26 (ft.) Top view 10 3 7 2 3 1 Vertical airflow direction louver : Up 0 0 Horizontal airflow direction louver : Right & Left 3 1 7 2 10 3 INDOOR UNITS INDOOR UNITS (ft.
Conditions Fan speed : High Operation mode : Fan MODELS : ASU12RLF Unit : ft./s (m/s) (ft.) (m) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center 7 2 3 1 0 0 3 1 7 2 3 (1.0) 7 (2.0) 2 (0.5) (m) 0 1 2 3 4 5 6 7 8 0 3 7 10 13 16 20 23 26 (ft.) 10 3 7 2 3 1 0 0 INDOOR UNITS INDOOR UNITS (ft.) (m) 7 (2.0) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Right & Left 2 (0.5) 3 (1.
Conditions Fan speed : High Operation mode : Fan MODEL : ASU9RLS2 Unit : ft./s (m/s) (ft.) (m) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center 7 2 3 1 0 0 3 1 7 2 2 (0.5) 3 (1) 1 (0.25) (m) 0 1 2 3 4 5 6 7 8 0 3 7 10 13 16 20 23 26 (ft.) Top view 10 3 7 2 3 1 INDOOR UNITS INDOOR UNITS (ft.
Conditions Fan speed : High Operation mode : Fan MODEL : ASU12RLS2, ASU15RLS2 Unit : ft./s (m/s) (ft.) (m) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center 7 2 3 1 0 0 3 1 7 2 1 (0.25) 2 (0.5) 3 (1) (m) 0 1 2 3 4 5 6 7 8 0 3 7 10 13 16 20 23 26 (ft.) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Right & Left 10 3 7 2 3 1 INDOOR UNITS INDOOR UNITS (ft.) (m) 3 (1) 0 2 (0.
Conditions Fan speed : High Operation mode : Fan MODEL : ASU18RLF (ft.) (m) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center 7 2 3 1 0 0 3 1 7 2 Unit : ft./s (m/s) 3 (1.0) 7 (2.0) 2 (0.5) 1 2 3 4 5 6 7 8 0 3 7 10 13 16 20 23 26 (ft.) 3 7 2 3 1 0 0 3 1 Unit : ft./s (m/s) INDOOR UNITS INDOOR UNITS (ft.) (m) 10 2 (0.5) 7 (2.
Conditions Fan speed : High Operation mode : Fan MODEL : ASU24RLF (ft.) (m) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center 7 2 3 1 0 0 3 1 7 2 Unit : ft./s (m/s) 7 (2.0) 2 (0.5) 3 (1.0) 1 2 3 4 5 6 7 8 0 3 7 10 13 16 20 23 26 (ft.) 3 7 2 Unit : ft./s (m/s) INDOOR UNITS INDOOR UNITS (ft.) (m) 10 2 (0.5) 7 (2.0) Top view Vertical airflow direction louver : Up 3 1 0 0 3 1 3 (1.
66666FLOOR TYPE MODELS : AGU9RLF, AGU12RLF, AGU15RLF Unit : ft./s (m/s) (ft.) (m) 7 2 3 1 0 0 3 1 Conditions Fan speed : High Operation mode : Fan Fan select : UPPER & LOWER 3(1.0) 2(0.5) Top view Horizontal airflow direction louver : Center UPPER 7 2 1 2 3 4 (m) 3 7 10 13 (ft.) Unit : ft./s (m/s) INDOOR UNITS (ft.) (m) 7 2 3(1.0) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Right & Left 3 1 0 0 3 1 3(1.0) 7 LOWER 2 2(0.5) 2(0.
777FAN PERFORMANCE CURVE 77777 SLIM DUCT TYPE MODEL : ARU7RLF 0.44 (110) SP mode09 upper limit 0.32 (80) Quiet (SP mode09) 0.28 (70) SP mode09 lower limit 0.24 (60) 0.20 (50) 0.16 (40) 0.12 (30) 0.08 (20) 0.04 (10) Normal SP upper limit Hi (Normal SP) Quiet (Normal SP) SP mode00 upper limit Quiet (SP mode00) INDOOR UNITS External Static Pressure [in.WG (Pa)] Hi (SP mode09) 0.
Cooling zz 120 Capacity (%) 100 80 Capacity 60 40 20 294 (500) 353 (600) Air Flow [CFM (m3/h)] 412 (700) 471 (800) 412 (700) 471 (800) INDOOR UNITS 235 (400) INDOOR UNITS 0 Heating zz 120 Capacity (%) 100 Capacity 80 60 40 20 0 235 (400) 294 (500) 353 (600) Air Flow [CFM (m3/h)] - (04 - 67) - 4.
MODEL : ARU9RLF 0.44 (110) Hi (SP mode09) 0.32 (80) 0.28 (70) Quiet (SP mode09) SP mode09 lower limit 0.24 (60) 0.20 (50) 0.16 (40) 0.12 (30) 0.08 (20) 0.04 (10) Normal SP upper limit Hi (Normal SP) SP mode00 upper limit Quiet (Normal SP) Hi (SP mode00) Quiet (SP mode00) 177 (300) 235 (400) INDOOR UNITS External Static Pressure [in.WG (Pa)] SP mode09 upper limit 0.
Cooling zz 120 Capacity Capacity (%) 100 80 60 40 20 294 (500) 353 (600) Air Flow [CFM (m3/h)] 412 (700) 471 (800) 412 (700) 471 (800) INDOOR UNITS 235 (400) Heating zz 120 100 Capacity (%) INDOOR UNITS 0 80 Capacity 60 40 20 0 235 (400) 294 (500) 353 (600) Air Flow [CFM (m3/h)] - (04 - 69) - 4.
MODEL : ARU12RLF 0.44 (110) 0.32 (80) 0.28 (70) Quiet (SP mode09) 0.24 (60) 0.20 (50) Normal SP upper limit 0.16 (40) Quiet (Normal SP) 0.12 (30) 0.08 (20) SP mode09 lower limit Hi (Normal SP) SP mode00 upper limit Hi (SP mode00) INDOOR UNITS External Static Pressure [in.WG (Pa)] 0.36 (90) 0.04 (10) Quiet (SP mode00) 0 (0) 177 (300) 235 (400) 294 (500) 353 (600) 412 (700) 471 (800) Air Flow [CFM (m3/h)] Available air flow rate range (High level) *1 0.44 (110) 0.
Cooling zz 120 Capacity (%) 100 Capacity 80 60 40 20 0 412 (700) Air Flow [CFM (m3/h)] 471 (800) 530 (900) 471 (800) 530 (900) INDOOR UNITS 353 (600) Heating zz 120 100 Capacity (%) INDOOR UNITS 294 (500) Capacity 80 60 40 20 0 294 (500) 353 (600) 412 (700) Air Flow [CFM (m3/h)] - (04 - 71) - 4.
MODEL : ARU18RLF 0.44 (110) 0.32 (80) Quiet (SP mode09) 0.28 (70) SP mode09 lower limit 0.24 (60) Normal SP upper limit Quiet (Normal SP) 0.20 (50) 0.16 (40) 0.12 (30) 0.08 (20) Hi (Normal SP) SP mode00 upper limit Hi (SP mode00) 0.04 (10) Quiet INDOOR UNITS External Static Pressure [in.WG (Pa)] 0.36 (90) (SP mode00) 0 (0) 353 (600) 412 471 530 (700) (800) (900) 589 647 706 (1000) (1100) (1200) 3 Air Flow [CFM (m /h)] Available air flow rate range (High level) *1 0.
Cooling zz 120 Capacity (%) 100 Capacity 80 60 40 20 471 (700) (800) 530 (900) Air Flow [CFM (m3/h)] 589 647 (1000) (1100) INDOOR UNITS 412 INDOOR UNITS 0 Heating zz 120 Capacity (%) 100 Capacity 80 60 40 20 0 412 (700) 471 530 589 647 (800) (900) (1000) (1100) Air Flow [CFM (m3/h)] - (04 - 73) - 4.
MODEL : ARU24RLF 0.24 (60) Hi (SP mode05) Quiet (SP mode05) Hi (Normal SP) 0.20 (50) 0.16 (40) Normal SP upper limit 0.12 (30) Quiet (Normal SP) 0.08 (20) 0.04 (10) SP mode00 upper limit SP mode05 lower limit Hi (SP mode00) Quiet (SP mode00) 471 530 589 (800) (900) (1000) 647 706 765 (1100) (1200) (1300) Air Flow [CFM (m3/h)] 824 883 942 (1400) (1500) (1600) Available air flow rate range (High level) *1 0.32 (80) 0.28 (70) Hi (SP mode05) 0.24 (60) Hi (SP mode04) 0.
Cooling zz 120 Capacity Capacity (%) 100 80 60 40 20 530 589 (800) (900) (1000) 647 706 765 (1100) (1200) (1300) Air Flow [CFM (m3/h)] 824 883 942 (1400) (1500) (1600) 824 883 942 (1400) (1500) (1600) INDOOR UNITS 471 Heating zz 120 100 Capacity (%) INDOOR UNITS 0 Capacity 80 60 40 20 0 471 530 589 (800) (900) (1000) 647 706 765 (1100) (1200) (1300) Air Flow [CFM (m3/h)] - (04 - 75) - 4.
888AIRFLOW Model Operation Fan mode speed Cooling AUU7RLF Heating Cooling AUU9RLF Heating Compact Cassette INDOOR UNITS Cooling AUU12RLF Heating Cooling AUU18RLF Heating Air flow Type Model Operation Fan mode speed m3/h l/s CFM High 540 150 318 Med 490 136 288 Low 440 122 259 Quiet 390 108 230 High 540 150 318 Med 490 136 288 Low 440 122 259 Low Quiet 390 108 230 Quiet High 540 150 318 High Med 490 136 288 Low 440 122 259 Quiet 390 108 230
Model Operation Fan mode speed Cooling ASU7RLF1 Heating Cooling ASU9RLF1 Heating INDOOR UNITS Cooling ASU12RLF1 Heating Cooling Wall Mounted ASU7RLF Heating Cooling ASU9RLF Heating Cooling ASU12RLF Heating Cooling ASU9RLS2 Heating Air flow 3 m /h l/s CFM High 560 156 330 Med 500 139 294 Low 430 119 253 Quiet 310 86 182 High 560 156 330 Med 500 139 294 Low 430 119 253 Quiet 330 92 High 600 Med 520 Low 430 119 253 Quiet 310 86 182 High 600 167
999NOISE LEVEL CURVE 99999COMPACT CASSETTE TYPE MODEL : AUU7RLF Cooling zz Heating 80 70 70 Octave band sound pressure level, dB:(0dB=0.0002µbar) Octave band sound pressure level, dB:(0dB=0.
MODEL : AUU12RLF Cooling zz Heating 80 80 70 70 N C -65 N C -60 N C -55 50 N C -50 H igh N C -45 40 N C -40 N C -35 30 N C -30 Quiet N C -25 20 N C -20 60 N C -60 N C -55 50 N C -50 N C -45 H igh 40 N C -40 N C -35 30 INDOOR UNITS Octave band sound pressure level, dB:(0dB=0.0002µbar) Octave band sound pressure level, dB:(0dB=0.
99999SLIM DUCT TYPE MODEL : ARU7RLF Cooling zz Heating 80 80 70 70 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 HIGH 30 NC-30 NC-25 20 QUIET NC-20 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 HIGH 30 NC-30 NC-25 QUIET 20 NC-20 NC-15 10 10 0 0 63 125 250 500 1,000 2,000 4,000 63 8,000 125 Octave band center frequency, Hz 250 500 1,000 2,000 4,000 8,000 Octave band center frequency, Hz MODEL : ARU9RLF Cooling zz Heating 80 80 70 70 N C -65 Octave b
MODEL : ARU12RLF Cooling zz Heating 80 80 70 70 N C -65 N C -55 50 N C -50 N C -45 40 N C -40 N C -35 30 H igh N C -30 N C -25 20 Quiet N C -20 60 N C -60 N C -55 50 N C -50 N C -45 40 N C -40 N C -35 30 H igh INDOOR UNITS Octave band sound pressure level, dB:(0dB=0.0002µbar) Octave band sound pressure level, dB:(0dB=0.
MODEL : ARU24RLF Cooling zz Heating 80 80 70 70 N C -65 N C -60 N C -55 50 N C -50 N C -45 40 N C -40 H igh N C -35 30 N C -30 Quiet N C -25 20 N C -20 60 N C -60 N C -55 50 N C -50 N C -45 40 N C -40 H igh N C -35 30 INDOOR UNITS 60 Octave band sound pressure level, dB:(0dB=0.0002µbar) Octave band sound pressure level, dB:(0dB=0.
99999WALL MOUNTED TYPE MODEL : ASU7RLF1 Cooling zz Heating zz 80 80 70 70 N C -6 5 N C -6 0 N C -5 5 50 N C -5 0 N C -4 5 HIGH 40 N C -4 0 N C -3 5 30 N C -3 0 N C -2 5 QUIET 20 N C -2 0 60 N C -6 0 N C -5 5 50 N C -5 0 N C -4 5 40 N C -4 0 HIGH N C -3 5 30 N C -3 0 N C -2 5 20 N C -2 0 N C -1 5 10 N C -1 5 QUIET 10 0 INDOOR UNITS Octave band sound pressure level, dB:(0dB=0.0002µbar) Octave band sound pressure level, dB:(0dB=0.
MODEL : ASU12RLF1 Cooling zz Heating zz 80 80 70 70 N C -6 5 N C -6 0 N C -5 5 50 N C -5 0 HIGH N C -4 5 40 N C -4 0 N C -3 5 30 N C -3 0 N C -2 5 20 N C -2 0 QUIET 60 N C -6 0 N C -5 5 50 N C -5 0 N C -4 5 HIGH 40 N C -4 0 N C -3 5 30 N C -3 0 INDOOR UNITS 60 Octave band sound pressure level, dB:(0dB=0.0002µbar) Octave band sound pressure level, dB:(0dB=0.
MODEL : ASU7RLF Cooling zz Heating 80 80 70 70 N C -65 N C -55 50 N C -50 N C -45 H igh 40 N C -40 N C -35 30 N C -30 N C -25 20 N C -20 Quiet 60 N C -60 N C -55 50 N C -50 N C -45 40 H igh N C -40 N C -35 30 N C -30 N C -25 20 Quiet N C -20 N C -15 N C -15 10 0 0 63 125 250 500 1,000 2,000 4,000 63 8,000 125 Octave band center frequency, Hz 250 500 1,000 2,000 4,000 8,000 Octave band center frequency, Hz MODEL : ASU9RLF Cooling zz Heating 80 80 7
MODEL : ASU12RLF Cooling zz Heating 80 80 70 70 N C -65 N C -60 N C -55 50 N C -50 H igh N C -45 40 N C -40 N C -35 30 N C -30 N C -25 20 N C -20 Quiet 60 N C -60 N C -55 50 N C -50 N C -45 H igh 40 N C -40 N C -35 30 N C -30 N C -25 20 Quiet N C -20 N C -15 N C -15 10 10 0 0 63 125 250 500 1,000 2,000 4,000 8,000 Octave band center frequency, Hz 63 125 250 500 1,000 2,000 4,000 8,000 Octave band center frequency, Hz - (04 - 86) - 4.
MODEL : ASU9RLS2 Cooling zz Heating 80 80 70 70 N C -60 N C -55 50 N C -50 N C -45 40 N C -40 H igh N C -35 30 N C -30 N C -25 20 N C -20 Quiet 60 N C -60 N C -55 50 N C -50 N C -45 40 N C -40 H igh N C -35 30 N C -30 N C -25 20 N C -20 N C -15 Quiet N C -15 10 0 0 63 125 250 500 1,000 2,000 4,000 8,000 63 125 Octave band center frequency, Hz 250 500 1,000 2,000 4,000 8,000 Octave band center frequency, Hz MODEL : ASU12RLS2 Cooling zz Heating 80 80 7
MODEL : ASU15RLS2 Cooling zz Heating 80 80 70 70 N C -65 N C -60 N C -55 50 N C -50 N C -45 H igh 40 N C -40 N C -35 30 N C -30 N C -25 20 N C -20 Quiet 60 N C -60 N C -55 50 N C -50 N C -45 H igh 40 N C -40 N C -35 30 N C -30 N C -25 20 N C -20 Quiet N C -15 N C -15 10 10 0 0 63 125 250 500 1,000 2,000 4,000 8,000 Octave band center frequency, Hz 63 125 250 500 1,000 2,000 4,000 8,000 Octave band center frequency, Hz - (04 - 88) - 4.
MODEL : ASU18RLF Cooling zz Heating 80 80 70 70 N C -65 N C -55 H igh 50 N C -50 N C -45 40 N C -40 N C -35 30 N C -30 Quiet N C -25 20 N C -20 60 N C -60 N C -55 50 N C -50 H igh N C -45 40 N C -40 N C -35 30 INDOOR UNITS Octave band sound pressure level, dB:(0dB=0.0002µbar) Octave band sound pressure level, dB:(0dB=0.
99999FLOOR TYPE MODEL : AGU9RLF Cooling zz Heating 80 80 70 70 NC-65 NC-60 NC-55 50 NC-50 NC-45 High 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 Quiet 60 NC-60 NC-55 50 NC-50 NC-45 High 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 NC-15 0 INDOOR UNITS Octave band sound pressure level, dB:(0dB=0.0002µbar) Octave band sound pressure level, dB:(0dB=0.
MODEL : AGU15RLF Cooling zz Heating 80 70 70 NC-65 NC-60 NC-55 50 NC-50 High NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 Quiet 60 NC-60 NC-55 50 NC-50 NC-45 High 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 NC-15 0 NC-15 Quiet 10 INDOOR UNITS 60 Octave band sound pressure level, dB:(0dB=0.0002µbar) Octave band sound pressure level, dB:(0dB=0.
99999SOUND LEVEL CHECK POINT 60in. (1.5m) INDOOR UNITS Microphone INDOOR UNITS COMPACT CASSETTE TYPE Microphone - (04 - 92) - 4.
SLIM DUCT TYPE Microphone Microphone Center Center Side view Front view WALL MOUNTED TYPE Microphone Microphone 40in. (1m) - (04 - 93) - 4. INDOOR UNITS INDOOR UNITS Measuring duct 32in. (0.8m) INDOOR UNITS Measuring duct 40in. (1m) 60in. (1.5m) 79in.
FLOOR TYPE Microphone Microphone 40in. (1m) Air Flow INDOOR UNITS INDOOR UNITS Air Flow 40in. (1m) - (04 - 94) - 4.
Model and type PCB fuse Fan motor thermal protector Terminal thermal fuse Float switch 250V 3.15A OFF: 268 + 30 - 34°F (131 + 17- 19°C) ON: 210 + 38 - 34°F (99 + 21- 19°C) ― ○ 250V 3.15A OFF: 275 ± 27°F (135 ± 15°C) ON: 239 ± 27°F (115 ± 15°C) ― ○ ― ― OFF: 216°F (OFF: 102°C) ― 250V 3.15A OFF: 302 ± 27°F (150 ± 15°C) ON: 248 ± 27°F (120 ± 15°C) OFF: 216°F (OFF: 102°C) ― 250V 3.
Hybrid Flex Inverter System 5. CONTROL SYSTEM DTR_BMU004E_02--CHAPTER05 2013.12.
CONTENTS 5. CONTROL SYSTEM 1. CONTROL SYSTEM...................................................................... 05 - 01 1-1. LINE UP OF CONTROLLERS................................................................ 05 - 01 1-2. CONTROL SYSTEM DESIGN................................................................ 05 - 02 1-3. SYSTEM CONFIGURATION EXAMPLES.............................................. 05 - 03 1-4. CONTROL EQUIPMENT DESIGN LIMITATION..................................... 05 - 05 2.
111CONTROL SYSTEM 11111LINE UP OF CONTROLLERS FEATURES OF CONTROL SYSTEM Air Conditioning Central Control Air Conditioning Individual Control Central controller specially designs for centralized control. A range of remote controllers suitable for range of individual control situations, using various built-in timers. Central Remote Controller Wired Remote Controller UTY-DMMUM UTY-RNNUM Control of indoor units with simple operation and weekly timer.
11111CONTROL SYSTEM DESIGN ADVANCED INTEGRATED CONTROL SYSTEM Air Conditioning Central Control Air Conditioning Individual Control System Outdoor Unit Branch box (Primary) Wired Remote Controller UTY-RNNUM Central Remote Controller UTY-DMMUM Simple Remote Controller UTY-RSNUM Branch box (Secondary 1) CONTROL SYSTEM CONTROL SYSTEM Wireless Remote Controller Transmission line Remote controller line UTY-LNHUM AR-RAH1U AR-RED1U AR-REG1U Central remote controller line Branch box (Secondary 2) I
11111SYSTEM CONFIGURATION EXAMPLES INDIVIDUAL CONTROL Wired Remote Controller ●● Wired, simple, and wireless remote controllers can be used jointly. ●● Two remote controllers can be connected with single indoor unit. Branch box (Primary) Branch box (Secondary 1) Branch box (Secondary 2) Outdoor unit Wired Remote Controller Simple Remote Controller ●● Enables easy control of basic functions by the hotel or office guest. ●● Two remote controller can be connected with single indoor unit.
INDOOR UNIT TYPE AND THE APPLICABLE CONTROL METHOD Indoor units ASU7RLF1 ASU9RLF1 ASU12RLF1 Wallmounted ASU7RLF ASU9RLS2 ASU18RLF ASU9RLF ASU12RLS2 ASU24RLF ASU12RLF ASU15RLS2 Model Compact Cassette Slim Duct Floor Central Remote Controller UTY-DMMUM *1 *1 *1 *1 *1 *1 *1 Wired Remote Controller UTY-RNNUM *4 *2 *3 Simple Remote Controller UTY-RSNUM *4 *2 *3 UTY-LNHUM – – – – – AR-RAH1U – – – – – – AR-RED1U –
11111CONTROL EQUIPMENT DESIGN LIMITATION Central Controller Central Remote Controller Wired Remote Controller Simple Remote Controller Controller Model The number that can be connected UTY-DMMUM 1 / Multi system UTY-RNNUM 2 / Indoor unit UTY-RSNUM 2 / Indoor unit UTY-LNHUM Individual Controller Wireless Remote Controller AR-RAH1U AR-REG1U - AR-RED1U 1 / Indoor unit CONTROL SYSTEM UTY-LRHUM CONTROL SYSTEM IR Receiver Unit - (05 - 05) - 5.
222CONTROL UNITS Central Remote Controller zz Wired Remote Controller zz Simple Remote Controller zz Wireless Remote Controller zz IR Receiver Unit zz Central Control CONTROL SYSTEM CONTROL SYSTEM Central Remote Controller Individual Control Wired Remote Controller Simple Remote Controller Wireless Remote Controller IR Receiver Unit - (05 - 06) - 5.
22222CENTRAL REMOTE CONTROLLER MODEL : UTY - DMMUM ●●Large and full-dot liquid crystal screen ●●Screen with backlight can be seen even in the dark ●●Wide and large keys easy to press, user-intuitive arrow key FEATURES Batched control of up to 8 indoor units. The temperature, airflow volume, and remote control prohibition settings of all indoor units can be batched.
MAIN FUNCTIONS Outdoor unit low noise operation zz Air conditioning load factor ●● Users can choose from 4 low noise levels, depending on the installation environment. Heat load 100% Capacity 58dB 0 (time) Low noise operation Minimum heat (All) operation zz ●●While this function is selected, all indoor units start the minimum heat operation when all the indoor units are stopped by operation of the [On/Off button]. ●● When the room temperature is higher than 50°F (10°C), MIN.
FUNCTIONS 1 2 6 7 3 CONTROL SYSTEM 5 9 1 Display panel (with backlight) 6 Screen switch button (Right) 2 Screen switch button (Left) 7 Power indicator 3 Menu button 8 On / Off button 4 Cancel button 9 Enter button 5 Cursor button ELECTRICAL WIRING Example: Wiring diagram when 3 units of branch boxes are connected Branch box (Primary) Branch box (Secondary 1) Branch box (Secondary 2) REMOTE CONTROL REMOTE CONTROL REMOTE CONTROL 1 2 3 1 2 3 1 2 3 Remote controller cable 1 2 3
INSTALLATION 1) Remove the insulation of the remote controller cable. 55 (2-3/16) 45 (1-3/4) 30 (1-3/16) Unit : mm (in.) 8 (5/16) 8 8 (5/16) 1. 12V (Red) (5/16) 2. Signal (White) 3. COM (Black) 2) Insert the flat-blade screwdriver and remove the front case and rear case by twisting it slightly. Hooks (2 places) Rear case Front case 3) I nstall the rear case to the wall, box, etc. with 2 screws (M4 × 16 mm). Fix the 2 screws in either horizontal or vertical position. A.
5) C onnect the cable to the terminals on the front case. Fix the cable together with the sheath with the binder. Cut off the excess binder. Terminal screw Tightening torque 0.8 to 1.2N • m (7 to 10 lbf • in) Binder 1. 12V (Red) Remote controller cable (sheath) 2. Signal (White) Good 3. COM (Black) Hole for binder 2 mm (1/16 in.) No good No good CAUTION 6) Attach the front case. CONTROL SYSTEM CONTROL SYSTEM ●● Be careful to avoid breaking the cable by over-tightening the binder.
DIMENSIONS Unit : in. (mm) Front View 3/8 (9) 3/16 (4.5) 3-5/16 (83.5) 3/16 (4.5) Side View 1/2 (12.5) 3/16 (4.5) 4-3/4 (120) 1-13/16 (45.3) 7/8 (23) 5/8 (15.3) 13/16 (21.3) 4-3/4 (120) 1-5/16 (33.5) 2-1/2 (63.
22222WIRED REMOTE CONTROLLER MODEL : UTY - RNNUM FEATURES ●●Various timer setup (ON / OFF / WEEKLY) are possible. ●●Equipped with weekly timer as standard function. (Start / Stop function is twice per day for a week) ●●When setting up a timer, start / stop and a temperature setup can be changed. ●●When a failure occurs,the error code is displayed. ●●Error history.(Last 16 error codes can be accessed.
FUNCTIONS 11 START/STOP button 22 SET TEMP. button 33 MODE button 44 FAN button 55 Vertical air flow direction and swing button 66 Horizontal air flow direction and swing button 77 Built-in thermo sensor 88 TIMER MODE (CLOCK ADJUST) button 99 DAY (DAY OFF) button 7 Display 16 2 8 9 10 11 1 3 4 6 5 12 14 15 13 Display panel 17 20 21 19 18 Pressed to start and stop operation. Selects the setting temperature. Selects the operating mode ( AUTO , COOL , DRY , FAN , HEAT ).
SYSTEM DIAGRAM 1 remote controller zz 2 remote controllers Indoor unit Indoor unit A B C Primary Remote controller A , B , C : Remote controller cable.
INSTALLATION Connection Pattern zz Note: Connection pattern is different according to type of Indoor unit. Indoor unit types Compact Cassette type Slim Duct type ASU7RLF1, ASU9RLF1, ASU12RLF1 ASU7RLF, ASU9RLF, ASU12RLF Wall Mounted type ASU9RLS2, ASU12RLS2, ASU15RLS2 ASU18RLF, ASU24RLF Floor type Connection Pattern Pattern A Pattern B Pattern C Pattern A zz Connect the end of remote controller cable directly to the exclusive terminal block.
Pattern C zz 1) Modify the remote controller cable as per below methods. ●●Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ●●Connect the remote controller cable and connecting cable as shown in Fig. ●●Be sure to insulate the connection between the cables. 13/16 in.
PACKING LIST Quantity Remote controller cable 1 [33ft(10m)] Screw (M4 x 16mm) 2 Binder 1 Connecting cable *1 1 CONTROL SYSTEM Screw *1 (M4 x 14mm) 1 Cable clamper *1 1 Installation manual 1 Operating manual 1 Application For connecting the remote controller For installing the remote controller For remote controller and remote controller cable binding For connecting the remote controller cable to the Wall mounted type indoor unit For installing the remote controller cable to the indoor
22222SIMPLE REMOTE CONTROLLER MODEL : UTY - RSNUM FEATURES ●●Easy operation. ●●Built-in background light function. ●●Easy installation with a slim shape with no bulge in the back. ●●Error history.(Last 16 error codes can be accessed.) ●●Can be installed onto SW-BOX. (applies to European and other country's standard) User-friendly operation zz ●●Provides access to basic operations, such as Start / Stop, Fan speed, operation mode and room temperature setting.
FUNCTIONS 2 3 11 START/STOP button 22 Display background light 33 Operation lamp 44 FAN button 55 SET TEMP. button 66 MODE button 77 Standby indicator 88 Power source indicator 99 Central control indicator 1 4 5 6 Display panel 7 8 13 9 10 Pressed to start and stop operation. Lights during operation. Lights during operation. Selects the fan speed ( AUTO LOW , HIGH , MED , QUIET ). , Selects the setting temperature.
ELECTRICAL WIRING 1 remote controller zz 2 remote controllers Indoor unit Indoor unit REMOTE CONTROLLER REMOTE CONTROLLER 1 2 3 1 2 3 1 2 3 1 2 3 Secondary Primary Remote controller Remote controllers DIMENSIONS 7/16 (11) hole x 2 3/8 (9) 1/2 (12.5) 2-3/8 (60) 3/16 (4.5) 3/16 (4) 1/4 (6) 3-5/16 (83.5) 4-3/4 (120) 1-7/8 (47.5) 11/16 (18) 9/16 (14) CONTROL SYSTEM Unit : in. (mm) 2-15/16 (75) 1-15/16 (49) 1-9/16 (39) 15/16 (23.
INSTALLATION Connection Pattern zz Note: Connection pattern is different according to type of Indoor unit. Indoor unit types Compact Cassette type Slim Duct type ASU7RLF1, ASU9RLF1, ASU12RLF1 ASU7RLF, ASU9RLF, ASU12RLF Wall Mounted type ASU9RLS2, ASU12RLS2, ASU15RLS2 ASU18RLF, ASU24RLF Floor type Connection Pattern Pattern A Pattern B Pattern C Pattern A zz Connect the end of remote controller cable directly to the exclusive terminal block.
Pattern C zz 1) Modify the remote controller cable as per below methods. ●●Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ●●Connect the remote controller cable and connecting cable as shown in Fig. ●●Be sure to insulate the connection between the cables. 13/16 in.
PACKING LIST Name and shape Quantity Remote controller cable 1 [33ft(10m)] Screw (M4 x 16mm) 2 Binder 1 Connecting cable *1 1 1 Cable clamper *1 1 Installation manual 1 Operating manual 1 For connecting the remote controller For installing the remote controller For remote controller and remote controller cable binding For connecting the remote controller cable to the Wall mounted type indoor unit For installing the remote controller cable to the indoor unit For installing the remote con
22222WIRELESS REMOTE CONTROLLER MODEL : UTY - LNHUM / AR-RAH1U FEATURES ●●Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. ●●Can be used jointly with wired remote controllers . ●●Easy to change custom code (4 patterns). Built-in timers zz Select from four different timer programs (ON / OFF / PROGRAM / SLEEP). Program timer zz The program timer operates the ON and OFF timer once within a 24 hour period.
FUNCTIONS (UTY-LNHUM) 11 MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. custom code change. (Max 4 types) 16 22 MIN.HEAT button 33 Set temp. button ( ▲ / ▼ ) 44 ECONOMY button 55 SLEEP button Sets the indoor temp./ Sets R.C. signal code. Pressed to select sleep timer. 66 FAN button 77 START/STOP button Selects the fan speed (AUTO, HIGH, MED, LOW, QUIET).
FUNCTIONS (AR-RAH1U) 11 MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. custom code change. (Max 4 types) 15 22 MIN.HEAT button 33 Set temp. button ( ▲ / ▼ ) 44 ECONOMY button 55 SLEEP button Sets the indoor temp./ Sets R.C. signal code. Pressed to select sleep timer. 1 6 3 7 2 4 8 5 9 FAN button 77 START/STOP button 88 SET button (Vertical) 99 SWING button Selects the fan speed (AUTO, HIGH, MED, LOW, QUIET).
SYSTEM DIAGRAM Signal transmitter Signal receiver window ●● Control signal might not be recognized in following cases: (i) A curtain or a wall, etc. exists between transmitter and receiver. (ii) There is an instant-start type (inverter type, etc.) fluorescent lamp in the room. ●● Air conditioner might not work correctly when strong light hits the signal receiver window. Shut off the direct sunlight and also make illuminator far away from the receiver window. DIMENSIONS Controller zz Unit : in.
PACKING LIST Name and shape Quantity Installation manual 1 Operating manual 1 Remote controller holder 1 Tapping screw 2 Battery [ 1.5V (R03 / AAA) ] 2 Application Use as remote controller holder For remote controller holder installation For remote controller SPECIFICATIONS Weight : oz. (g) 3 (85) [w/o batteries] CONTROL SYSTEM 6-11/16 (170) x 2-3/16 (56) x 3/4 (19) CONTROL SYSTEM Dimensions [H x W x D]: in. (mm) - (05 - 29) - 5.
MODEL: AR-RED1U FEATURES ¾¾5 Mode timer setup (ON / OFF / WEEKLY / PROGRAM / SLEEP) are possible. ¾¾Easy operation. ¾¾Easy to change custom code (4 patterns) by button operation. Built-in timers zz Select from five different timer programs (ON / OFF / WEEKLY / PROGRAM / SLEEP). Weekly timer zz Weekly timer can be easily set by wireless remote controller. ON, OFF can be set up to 4 times in 1 day and up to 28 times in 1 week.
FUNCTIONS (AR-RED1U) SENSOR button Signal Transmitter MODE button FAN button MIN. HEAT button TEMP.
SYSTEM DIAGRAM Signal receiver window Signal transmitter ●● Control signal might not be recognized in following cases: (i) A curtain or a wall, etc. exists between transmitter and receiver. (ii) There is an instant-start type (inverter type, etc.) fluorescent lamp in the room. ●● Air conditioner might not work correctly when strong light hits the signal receiver window. Shut off the direct sunlight and also make illuminator far away from the receiver window. DIMENSIONS Controller zz [Unit: in.
PACKING LIST Name and shape Quantity Remote controller holder 1 Tapping screw 2 Battery [ 1.5V (LR03 / AAA) ] 2 Application Use as remote controller holder For remote controller holder installation For remote controller SPECIFICATIONS Weight: oz.(g) 4.3 (122) [w/o batteries] CONTROL SYSTEM 8-1/16 (205) × 2-3/8 (61) × 11/16 (17) CONTROL SYSTEM Dimensions [H x W x D]: in.(mm) - (05 - 33) - 5.
MODEL: AR-REG1U FEATURES 4 mode timer setup available (ON / OFF / PROGRAM / SLEEP). Easy operation. Easy to change custom code (max. 4 custom codes) by button operation. REG1U Simple function setting zz Setting of the air conditioner selection function is performed by remote controller. Built-in timers zz Select from four different timer programs (ON / OFF / PROGRAM / SLEEP).
FUNCTIONS (AR-REG1U) Signal transmitter MODE button FAN button MIN. HEAT button ECONOMY button SWING button TEMP.
SYSTEM DIAGRAM Signal receiver window Signal transmitter ●● Control signal might not be recognized in following cases: (i) A curtain or a wall, etc. exists between transmitter and receiver. (ii) There is an instant-start type (inverter type, etc.) fluorescent lamp in the room. ●● Air conditioner might not work correctly when strong light hits the signal receiver window. Shut off the direct sunlight and also make illuminator far away from the receiver window. DIMENSIONS Controller zz [Unit: in.
PACKING LIST Name and shape Quantity Remote controller holder 1 Tapping screw 2 Battery [ 1.5V (LR03 / AAA) ] 2 Application Use as remote controller holder For remote controller holder installation For remote controller SPECIFICATIONS Weight: oz.(g) 4.3 (122) [w/o batteries] CONTROL SYSTEM 8-1/16 (205) × 2-3/8 (61) × 11/16 (17) CONTROL SYSTEM Dimensions [H x W x D]: in.(mm) - (05 - 37) - 5.
22222IR RECEIVER UNIT MODEL : UTY - LRHUM FEATURES Duct type indoor unit can be controlled with wireless remote controller if the IR receiver unit is used. FUNCTIONS Wireless remote controller IR Receiver CONTROL SYSTEM MANUAL AUTO SIGNAL RECEIVER Refer to 2-4.WIRELESS REMOTE CONTROLLER for details. SYSTEM DIAGRAM ATTACHMENT RANGE zz 1) L L 1) 1) Connection cable length L Cable A (standard accessory) : 16ft. (5 m) Cable C (Optional parts) : 33ft.
ELECTRICAL WIRING Connected to CN13 of PCB PCB CN13 Connection cable B [L = 7-7/8in. (0.2m)] ...Standard accessory Connection cable A [L = 16ft. (5m)]...Standard accessory Connection cable C [L = 33ft. (10m)]...Optional service parts 2-3/8in. x 4-3/4in. (60mm x 120mm) hole Connected to Connection cable Connected to IR Receiver Unit IR Receiver Unit DIMENSIONS Unit : in. (mm) 2-3/8 (60) /16 Rear View CONTROL SYSTEM 3-5 Side View (83 .
PACKING LIST Quantity Application Installation manual 1 Operating manual 1 Cover 1 For covering receiver unit Insulation 1 For protecting PCB from dust Connection cable A [16ft. (5m)] 1 For connecting PCB of indoor unit to receiver unit Connection cable B [7-7/8in. (0.
22222REMOTE SENSOR UNIT MODEL : UTY - XSZX FEATURES New amenity space can be offered by installing the Remote sensor. ELECTRICAL WIRING CONTROL SYSTEM Cable Remote sensor INSTALLATION When the cable is attached to the wall zz ●●Remove the material covering the wiring penetration (thin material) in the cover of the sensor unit with a pair of cutters. The cable passes through this hole. ●●Now the remote sensor on the wall using the screws. Screw (M4 x 16mm) 1-9/16 (40) [Unit : in.
When the cable is buried in the wall zz ●●Remove the material (thinner than the surrounding material) in the wiring hole in the remote sensor using a pair of cutters. ●●Drill a hole in the wall for the cable. ●●Seal the area around the cable penetration with putty. 13/16 (20) 1316 (20) [Unit : in.(mm)] 2-3/16 (55) 1/16 (1) Screw (M4 x 16mm) Ø1/4 - Ø3/8 (Ø6 - Ø10) Mounting hole dimensions Finish zz CONTROL SYSTEM DIMENSIONS [Unit: in.(mm)] 2-3/4(70.
22222 GROUP CONTROL METHOD REMOTE CONTROLLER GROUP Wired, Simple and Wireless Remote Controllers can be used jointly in the following combinations. CONTROL SYSTEM CONTROL SYSTEM Example of combination for "Remote controller group" - (05 - 43) - 5.
22222COMPARISON TABLE OF CONTROLLERS Central Remote Controller Item Simple Remote Controller Wireless Remote Controller UTY-DMMUM UTY-RNNUM UTY-RSNUM Max. controllable indoor units Start/Stop Operation mode setting Fan speed setting Room temp. setting Test operation Up/down air direction flap setting Right/left air direction flap setting RC prohibition Min.
Hybrid Flex Inverter System 6. SYSTEM DESIGN DTR_BMU004E_02--CHAPTER06 2013.12.
CONTENTS 6. SYSTEM DESIGN 1. SYSTEM DESIGN.......................................................................... 06 - 01 1-1. SYSTEM OUTLINE................................................................................. 06 - 01 1-2. REFRIGERANT SYSTEM....................................................................... 06 - 02 1-3. WIRING SYSTEM.................................................................................... 06 - 07 1-4. MOUNTING POSITION..........................................
CONTENTS 6. SYSTEM DESIGN 5-9. SIMPLE REMOTE CONTROLLER......................................................... 06 - 89 5-10. DUCT STATIC PRESSURE SETTING.................................................... 06 - 92 6. CHECK RUN................................................................................... 06 - 93 6-1. PRECAUTIONS & PREPARATION........................................................ 06 - 93 6-2. CHECK RUN CHECK ITEMS AND PROCEDURE................................. 06 - 95 6-3.
111SYSTEM DESIGN 11111SYSTEM OUTLINE Branch box 3 (Secondary) Indoor units Circuit breaker (over current) Earth leakage breaker Power supply Branch box 2 (Secondary) Circuit breaker (over current) Earth leakage breaker Power supply Branch box 1 (Primary) Circuit breaker (over current) Outdoor unit Earth leakage breaker Central remote controller Circuit breaker (over current) Power supply SYSTEM DESIGN SYSTEM DESIGN Power supply Earth leakage breaker ) : Transmissi
11111REFRIGERANT SYSTEM CONNECTABLE UNIT WITHIN 1 REFRIGERANT SYSTEM Unit Quantity Remarks Outdoor unit 1 unit Indoor unit 2 to Max. 8 units Connectable indoor unit capacity : 80% to 130% Branch box 1 to Max. 3 units One Branch box of primary type is always necessary Caution zz SYSTEM DESIGN SYSTEM DESIGN ●●When all indoor units are operating at maximum capacity, individual indoor unit operate at a slightly lower capacity.
EXAMPLE OF REFRIGERANT SYSTEM Example 1 (OK) zz Branch box 1 (Primary type) Outdoor unit Capacity ratio 88% Indoor unit 1 Indoor unit 2 Model Outdoor unit AOU48 Indoor unit 1 ARU24 Indoor unit 2 ARU18 Branch box 1 UTP-PU03A Capacity (Btu/h) 48000 24000 18000 - Total capacity (Btu/h) 48000 42000 - Connectable indoor unit capacity (Btu/h) Min. Max.
Example 3 (OK) zz Outdoor unit Indoor unit 1 Model Outdoor unit AOU48 Indoor unit 1 ARU18 Indoor unit 2 ARU12 Indoor unit 3 ARU9 Indoor unit 4 ARU9 Indoor unit 5 ARU9 UTP-PU03A Branch box 1 Branch box 2 UTP-PU03B Branch box 1 Branch box 2 (Primary type) (Secondary type) Indoor unit 2 Capacity (Btu/h) 48000 18000 12000 9000 9000 9000 - Indoor unit 3 Total capacity (Btu/h) 48000 57000 Indoor unit 4 Capacity ratio 119% Indoor unit 5 Connectable indoor unit capacity (Btu/h) Min. Max.
Example 5 (Not good) zz Branch box 1 (Primary type) Outdoor unit Indoor unit 1 Model Outdoor unit Indoor unit 1 AOU48 ARU24 Branch box 1 UTP-PU03A Capacity (Btu/h) 48000 Total capacity (Btu/h) 48000 24000 - 24000 - Connectable indoor unit capacity (Btu/h) Min. Max.
Example 7 (Not good) zz Outdoor unit Indoor unit 1 Branch box 1 Branch box 2 Branch box 3 (Primary type) (Secondary type) (Secondary type) Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7 Capacity ratio 138% Model Outdoor unit AOU48 Indoor unit 1 ARU12 Indoor unit 2 ARU9 Indoor unit 3 ARU9 Indoor unit 4 ARU9 Indoor unit 5 ARU9 Indoor unit 6 ARU9 Indoor unit 7 ARU9 Branch box 1 UTP-PU03A Branch box 2 UTP-PU03B Branch box 3 UTP-PU03B Capacity (Btu/h) 48000 12
11111WIRING SYSTEM MAXIMUM WIRING LENGTH Maximum wiring length Transmission line Between outdoor unit and branch box ft (m) 246 (75) Between branch box and indoor unit 246 (75) Between branch box and branch box 246 (75) Between branch box and Central remote controller 1640 (500) Between indoor unit and Wired R.C. or Simple R.C.
11111MOUNTING POSITION OUTDOOR UNIT For the air conditioner to operate satisfactorily, install it as outlined in installation manual. Outdoor unit mounting position zz ●●A position where satisfies the mounting space described in “3-3 Installation space". ●●A position where the unit can be installed horizontally. ●●A position with enough space for performing pipe work, service and maintenance.
INDOOR UNIT For the air conditioner to operate satisfactorily, install it as outlined in installation manual. Indoor unit mounting position zz ●●Decide the mounting position with the customer ●●Install the unit level on a strong wall, floor, ceiling which is not subject to vibration. ●●The inlet and outlet ports should not be obstructed. The air should be able to blow all over the room. ●●Install the unit where the connection pipe can be easily installed.
222PIPING DESIGN 22222 IMPORTANT ITEMS WHEN USING NEW REFRIGERANT (R410A) R410A operates at higher pressure and has less solubility with mineral oil than traditional R22 refrigerant. Therefore, the lubricant and a part of pipe material are different. Some special tools are necessary. REFRIGERANT PIPING MATERIAL AND WALL THICKNESS It is necessary to use seamless copper tubes for refrigerant use. Thickness of tubes are shown in table below. Endurance pressure of the pipe must be 609 psi (4.2 MPa).
WORK FLOW (EXAMPLE) Preparations Prepare schedule of works Refrigerant check ●● Always check the refrigerant to be used. ●● Always use the specified refrigerant. ●● Prepare materials / tools matched to the refrigerant. Operation chart preparation Start of work Indoor unit installation Refrigerant piping work Drain piping work ●● Use copper tube of the specified material and thickness to meet endurance pressure of the pipe. (609 psi (4.
22222PIPING LIMITATION LIMITATION a c b H2 e d H3 l i Allowable height difference Allowable pipe length (actual pipe length) SYSTEM DESIGN f j m k g H4 h Limitation ft (m) Diagram Total pipe length 377 (115) or less Total Between outdoor unit and the farthest indoor unit 230 (70) or less a+b+c+m Between outdoor unit and branch boxes 180 (55) or less a+b+c+d+e 197 (60) or less f+g+h+i+j+k+l+m Between 10 to 49 (3 to 15) f, g, h, i, j, k, l, m Total Between branch box and ind
CAUTION Keep the "piping limitation" for correct operation.
22222PIPE SIZE PIPE DIAMETER, RECOMMENDED MATERIAL AND WALL THICKNESS Nominal Diameter (in) 1/4" 3/8" 1/2" 5/8" 3/4" Outside Diameter (mm) 6.35 9.52 12.70 15.88 19.05 Material JIS H3300 C1220T-O or equivalent *1 Wall Thickness *2 (mm) 0.8 0.8 0.8 1.0 1.2 2 *1: Allowable tensile stress ≥ 33 (N/mm ) *2: Endurance pressure of the pipe must be 609 psi (4.2 MPa). Please select the pipe size in accordance with local rules.
Pipe size table "A" zz (Between outdoor unit and first separation tube) Outside diameter mm (in.) Liquid pipe Gas pipe 3/8" (9.52) 5/8" (15.88) Pipe size table "B" zz (Between first separation tube and second separation tube) Outside diameter mm (in.) Liquid pipe Gas pipe 3/8" (9.52) 5/8" (15.88) Pipe size table "C" zz (Between separation tube and branch box) Outside diameter mm (in.) Liquid pipe Gas pipe 3/8" (9.52) 5/8" (15.
22222SELECTION OF PIPE HEAT INSULATING MATERIAL ●●Always insulate the refrigerant pipe to prevent condensation and water droplets by the refrigerant pipe. ●●Decide the thickness of the heat insulating material by referring to the recommended minimum thickness in Table 1. (For installation condition T=90°F DB (32°C DB),humidity≤70%, humidity≤75%, humidity≤80%, humidity≤85%) ●●When the outdoor unit is installed in a higher position than the indoor unit, fill the connecting part gap with putty, etc.
22222ADDITIONAL CHARGE CALCULATION ●●The outdoor unit is charged refrigerant at the factory. ●●Additional refrigerant required to be charged on site depending on pipe length. ●●The additional refrigerant charge amount is calculated according to the following formula. ●●Round up the calculated result to two decimal places. CALCULATION OF ADDITIONAL CHARGE REFRIGERANT Diameter of liquid pipe unit: in. (mm) ø1/4 (6.35) ø3/8 (9.52) Additional amount for pipe length unit: oz./ft. (g/m) 0.224 (21) 0.
22222EXAMPLE OF PIPING DESIGN EXAMPLE 1 a b c Outdoor unit Separation tube Separation tube d Branch box f Branch box g 1 (7000Btu) e h 2 (7000Btu) 3 (7000Btu) Indoor unit Indoor unit Indoor unit i Branch box j 4 (7000Btu) k 5 (7000Btu) 6 (7000Btu) Indoor unit Indoor unit Indoor unit l m 7 (7000Btu) 8 (7000Btu) Indoor unit Indoor unit System configuration (Indoor units) zz Total Capacity (Btu) 1 2 3 4 5 6 7 8 Model name ASU7 ASU7 ASU7 ASU7 ASU7 ASU7 ASU7 AS
Limitation check zz Example ft (m) 259 Total pipe length Total (80) 115 Between outdoor unit and the farthest indoor unit a+b+c+m (35) 121 Between outdoor unit and branch boxes a+b+c+d+e (37) 138 Total f+g+h+i+j+k+l+m (43) Between branch box and indoor unit 16 to 26 Each unit f, g, h, i, j, k, l, m (5 to 8) 23 Between outdoor unit and the first separation tube a (7) Diagram Limitation ft (m) Judge Less than 377 (115) OK Less than 230 (70) OK Less than 180 (55) OK Less than 197 (60) OK Between 10
EXAMPLE 2 a c Outdoor unit Separation tube d Branch box f Branch box g 1 (18000Btu) h 2 (7000Btu) 3 (7000Btu) Indoor unit Indoor unit Indoor unit i j 4 (9000Btu) k 5 (7000Btu) 6 (7000Btu) Indoor unit Indoor unit Indoor unit System configuration (Indoor units) zz 1 2 3 4 5 6 Model name ASU18 ASU7 ASU7 ASU9 ASU7 ASU7 Capacity (Btu) 18000 7000 7000 9000 7000 7000 7 8 Total Capacity (Btu) 55000 Capacity ratio zz (Total indoor unit capacity) / (Total outdoor unit c
Limitation check zz Diagram Total pipe length Total Between outdoor unit and the farthest indoor unit a+c+k Between outdoor unit and branch boxes a+c+d Total f+g+h+i+j+k Between branch box and indoor unit Each unit Between outdoor unit and the first separation tube f, g, h, i, j, k a Example ft (m) 234 (72) 121 (37) 138 (42) 96 (30) 16 (5) 23 (7) Limitation ft (m) Judge Less than 377 (115) OK Less than 230 (70) OK Less than 180 (55) OK Less than 197 (60) OK Between 10 to 49 (3 to 15) OK
EXAMPLE 3 c Outdoor unit Branch box f g 1 (24000Btu) h 2 (18000Btu) 3 (7000Btu) Indoor unit Indoor unit Indoor unit System configuration (Indoor units) zz 1 2 3 4 Model name ASU24 ASU18 ASU7 Capacity (Btu) 24000 18000 7000 5 6 7 8 Total Capacity (Btu) 49000 Capacity ratio zz (Total indoor unit capacity) / (Total outdoor unit capacity) = (49000) / (48000) = 102.
Limitation check zz Diagram Total pipe length Total Between outdoor unit and the farthest indoor unit c+h Between outdoor unit and branch box c Total f+g+h Between branch box and indoor unit Each unit Between outdoor unit and branch box (When there is no separation tube) f, g, h c Example ft (m) 275 (84) 197 (60) 148 (45) 127 (39) 39 to 49 (12 to 15) 148 (45) Limitation ft (m) Judge Less than 377 (115) OK Less than 230 (70) OK Less than 180 (55) OK Less than 197 (60) OK Between 10 to 49
EXAMPLE 4 a b c Outdoor unit Separation tube Separation tube d Branch box e Branch box f Branch box i 1 l 2 3 (18000Btu) (18000Btu) (24000Btu) Indoor unit Indoor unit Indoor unit System configuration (Indoor units) zz 1 2 3 4 Model name ASU18 ASU18 ASU24 Capacity (Btu) 18000 18000 24000 5 6 7 8 Total Capacity (Btu) 60000 Capacity ratio zz (Total indoor unit capacity) / (Total outdoor unit capacity) = (60000) / (48000) = 125.
Limitation check zz Diagram Total pipe length Total Between outdoor unit and the farthest indoor unit Between outdoor unit and branch boxes a+b+c+l a+b+c+d+e Total f+i+l Between branch box and indoor unit Each unit Between outdoor unit and the first separation tube f, i, l a Example ft (m) 290 (89) 180 (55) 173 (53) 117 (36) 39 (12) 23 (7) Limitation ft (m) Judge Less than 377 (115) OK Less than 230 (70) OK Less than 180 (55) OK Less than 197 (60) OK Between 10 to 49 (3 to 15) OK Greate
333INSTALLATION 33333OUTDOOR UNIT OPENING A KNOCKOUT HOLE CAUTION ●●Be careful not to deform or scratch the panel while opening the knock out holes. ●●To protect the piping insulation after opening a knock out hole, remove any burrs from the edge of the hole. It is recommended to apply rust prevention paint to the edge of the hole. ●●Pipes can be connected from 4 directions, front, lateral side, rear side and bottom. (Fig.
PIPE CONNECTION CAUTION ●●Be sure to install the pipe against the port on the indoor unit and the outdoor unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged. ●●Do not remove the flare nut from the outdoor unit pipe until immediately before connecting the connection pipe. ●●After installing the piping, make sure that the connection pipes do not touch the compressor or outer panel.
Handling precautions for the valves zz ●●Mounted part of Blank cap is sealed for protection. ●●Fasten blank cap tightly after opening valves. Blank cap [in. (mm)] 1/4 (6.35) 3/8 (9.52) 1/2 (12.70) 5/8 (15.88) 3/4 (19.05) Tightening torque [lbf· ft (N·m)] 14.8 to 18.4 (20 to 25) 14.8 to 18.4 (20 to 25) 18.4 to 22.1 (25 to 30) 22.1 to 25.8 (30 to 35) 25.8 to 29.5 (35 to 40) Operating the valves ●●Use a hexagon wrench [size 3/16 in. (4 mm)].
33333SEPARATION TUBE PIPE CONNECTION CAUTION ●●Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is improper, the flare nut cannot be tighten smoothly. If the flare nut is forced to turn, the threads will be damaged. ●●Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe. ●●Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to tighten the flare nut correctly.
Straight pipe length zz to branch box to branch box ●●When connecting the main piping, do not bend it near the connection section. ●●If the main pipe must be bent due to unavoidable circumstances, ensure that the linear section is 5-7/8 in. (150 mm) or more. Straight pipe=5-7/8in. (150 mm) or more R to outdoor unit HEAT INSULATION INSTALLATION After connection the pipes, use the supplied heat insulation to insulate them.
33333BRANCH BOX INSTALLATION THE UNIT WARNING ●●Perform installation in a location which can properly withstand the weight of the unit. Failure to install in a robust location or a faulty installment may cause the equipment to fall, a water leakage, electric shock or fire. ●●During installation, secure the hanger bolt so it does not come off. CAUTION ●●Be sure to provide adequate maintenance space when installing the unit above the ceiling.
(5) R emove the control box as shown in the figure, (6) A ttach the control box to the main unit as and then change the positioning to the opposite shown in the figure. side. Remove the control box by lifting up and out through slots To the opposite side The lead wire runs here Control box Insert and fix the control box using the slots (7) Attach the bottom panel and secure it with the (8) Secure the control box with the screws screws (4 pieces). (4 pieces).
Fix the unit (When hanging from the ceiling) zz CAUTION ●●Do not hang from the ceiling when performing a vertical installation. (1) Secure the hangers (accessories) with the screws [2 pieces, Ø 3/16 x 3/8 in. (4 x 10 mm), accessories]. (4 places) Screw Hanger (4 places) (2) Secure the attachment section with the hanging bolt. (Use M8 or M10 for the hanging bolt) (3) Secure the hangers with hexagonal nuts (field supply) and the washers (accessories) as shown in the figure below.
Fix the unit (For wall installation) zz (1) Secure the hangers (accessories) with the screws [2 pieces, Ø 3/16 x 3/8 in. (4 x 10 mm), accessories]. (4 places) • Install the unit with its top side facing upwards. (1) S ecure the hangers (accessories) with the screws [2 pieces, Ø 3/16 x 3/8 in. (4 x 10 mm), accessories]. 4 places) • Install the unit with the control box facing upwards.
PIPE CONNECTION WARNING ●●Be sure to perform flare connection. It causes a malfunction and a fire of this unit when connecting the pipes other than flare connection (brazing etc.). (1) Detach the caps and plugs from the pipes. CAUTION ●●Be sure to apply the pipe against the port on the unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
PIPING INSULATION (1) Install the coupler heat insulation (large and small) and insulation (long and short) on each pipe as shown in the figures below. (2) Attach the butting surface with no gap to eliminate any gap between the insulations. (3) During the pipe insulation work, prevent air from getting inside the insulation with an adhesive tape (field supply).
444WIRING DESIGN 44444ELECTRICAL WIRING PRECAUTION FOR ELECTRICAL WIRING Regulation on wire diameter and selecting circuit breaker size differ from locality. Install in accordance with local rules and regulations. Warning ●●Do not turn on the power until all installation work is complete. ●●Before starting work, check that power is not being supplied to the unit. ●●Connect the connection cable firmly to the terminal board. Imperfect installation may cause a fire.
WIRING SYSTEM LAYOUT For installation of the outdoor unit, branch boxes, and indoor units, follow the instructions in the installation manual for each unit.
44444POWER SUPPLY CABLE WIRING POWER SUPPLY CABLE SPECIFICATIONS Use a separate power supply for the outdoor unit and branch box. Note: *1: Selected sample (Select an appropriate diameter of cable and the kind of cable according to each country and a local rule. ) *2: I t is a total value of connected indoor units and branch box. (Refer to "3.OUTDOOR UNIT & BRANCH BOX" and "4.INDOOR UNITS") *3: Selected sample (Select the one that the rush current when the power supply is turned on can be endured.
POWER SUPPLY CABLE WIRING Caution ●●Except for EMERGENCY, never turn off main as well as sub breaker of the indoor units during operation. It will cause compressor failure as well as water leakage. ●●First, stop the indoor unit by operating the control unit or external input device and then cut the breaker. ●●Make sure to operate through the control unit or external input device. ●●When the breaker is designed, locate it at a place where the users cannot start and stop in the daily work.
Example 3 (Branch box & indoor unit) zz Disconnect SW Indoor units Branch box Disconnect SW Branch box Disconnect SW Junction box Circuit breaker (over current) Branch box Branch box - Indoor unit Power supply 1ø 208/230 V 60 Hz SYSTEM DESIGN SYSTEM DESIGN Earth leakage breaker - (06 - 41) - 6.
WIRING RULES Example 1 (Not good) zz Power cable Branch box Power cable Do not connect the power cable directly to indoor units. SYSTEM DESIGN SYSTEM DESIGN Always supply power to indoor units from a branch box. - (06 - 42) - 6.
44444TRANSMISSION LINE TRANSMISSION WIRING SPECIFICATIONS Use ●●Between Outdoor unit to Branch box ●●Between Branch box to Branch box ●●Between Branch box to Indoor unit Cable size ●●Between Central remote controller to Branch box Remarks 14 AWG 208/230V 60Hz 3Wire + ground 22 AWG Sheathed PVC cable Polar 3core TRANSMISSION WIRING LIMITATION Central remote controller l a c b d e f Branch box 2 (secondary) g h Outdoor unit - Branch box (primary) a Branch box (primary) - Branch box (se
WIRING METHOD Practical transmission wiring method is shown below. Each terminal has to be connected the following rules. Example 1 Single-phase 208/230V 60Hz Max.26.5A Power supply cable Outdoor unit Central remote controller BRANCH BOX 1 2 3 Breaker1 Breaker1: Earth leakage breaker Breaker2 Breaker2: Circuit breaker (over current) Select the disconnect switch appropriately depending on the loads (total current value of connected units).
WIRING RULES Example 1 (Not good) zz Transmission line Branch box (secondary) Do not connect outdoor unit to secondary type branch box. Always connect primary type branch box to outdoor unit. Example 2 (Not good) zz Transmission line SYSTEM DESIGN Branch box (primary) SYSTEM DESIGN Branch box (primary) Do not interconnect primary type branch boxes. Only 1 primary type branch box can be connected in 1 multi system.
44444CONTROLLER CABLE WIRING WIRING SPECIFICATIONS Model type Connection to Central remote controller Branch box Wired Remote Controller Indoor unit Simple Remote Controller Indoor unit IR Receiver Unit Indoor unit Wire Remote controller cable Cable size Specification 22 AWG Remote controller cable 22 AWG Connection cable - Sheathed PVC cable Polar 3core [16 ft. (5 m) cable attached] SYSTEM DESIGN SYSTEM DESIGN Caution ●●Install in accordance with local rules and regulations.
WIRING RULES Example 1 (good) zz Branch box (primary) Branch box 2 (secondary) Branch box 3 (secondary) Central remote controller line Central remote controller One Central remote controller can be connected any branch box in 1 refrigerant system. Branch box (primary) Central remote controller line Branch box 2 (secondary) Central remote controller Branch box 3 (secondary) Central remote controller Do not connect two or more Central remote controllers in 1 refrigerant system.
Example 3 (Not good) zz Branch box (primary) Central remote controller line Central remote controller Central remote controller line Do not connect Central remote controller to outdoor unit or indoor unit. Always connect branch box to Central remote controller.
Example 5 (Not good) zz Branch box (primary) Do not connect a wired remote controller or simple remote controller to branch box. Connect them to each indoor unit. Example 6 (Not good) zz Wired remote controller Branch box 2 (secondary) Simple remote Remote controller line controller SYSTEM DESIGN SYSTEM DESIGN Branch box 1 (primary) Remote controller line Do not connect a wired remote controller or simple remote controller to multiple indoor units.
555FUNCTION SETTINGS 55555OUTDOOR UNIT SWITCH POSITION LED lamp LED981 POWER / MODE LED961 7 Segment LED Lamp LED982 ERROR LED962 MODE / EXIT SELECT ENTER CHECK SW931 SW932 SW933 SW934 Outdoor unit printed circuit board Push button ●●Set the functions of an outdoor unit with the push buttons (SW931, SW932 and SW933) while observing the 7-segment LED lamps (LED961 and LED962) on the printed circuit board.
FUNCTION SETTING 1111After verifying that the system is normally, press the MODE/EXIT button (SW931) once. LED961 LED962 LED961 LED962 2222Press the SELECT button (SW932), and display “F2” on the LED962. (Monitoring mode) LED961 LED962 *1 (Setting mode) LED961 (Function mode) LED962 LED961 LED962 (Error history mode) LED961 (The display of the LED962 changes each time when the SELECT button is pressed.
5555Again, referring to the Settings List shown below, press the SELECT button (SW932), and display the code number of the function you want to set on the LED962. Ex.) To select the Emergency Stop function LED961 LED962 LED961 LED962 Next, press the ENTER button (SW933), and confirm the selection of the function you want to set. LED961 LED961 LED962 LED962 A flashing display on the LED962 changes to an illuminated display. This completes FUNCTION SETTING.
SETTINGS LIST LED962 LED961 Setting Mode CODE No. CODE No. 1 1 Cooling capacity shift Setting Function 0 0 Standard 0 1 High power mode 1 0 2 High power mode 2 Factory setting l Remarks Use it when becoming cooling capacity shortage. Use High power mode 2 when becoming cooling capacity shortage in High power mode 1. This mode selects the pattern of the stop function to be operated by the external input terminal (CN934).
55555INDOOR UNIT (setting by jumper wire) Note: This function is Slim Duct type only. SWITCH POSITION Slim Duct type zz JM3 JM2 JM1 JUMPER WIRE SETTING Drainage function setting (JM1) zz u JM1 Drainage function Connect Valid Disconnect Invalid SYSTEM DESIGN SYSTEM DESIGN (u...Factory setting) Auto louver grille setting (JM2) zz When Auto louver grille kit (optional parts) is attached, set the Auto louver grille setting to "Valid". (u...
55555INDOOR UNIT (setting by wireless remote controller) The function settings of the control of the indoor unit can be changed by this procedure ●● according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the “FUNCTION SETTING” according to the ●● installation conditions using the remote controller. The settings may be selected between the following two: Function Number or Setting ●● Number.
5555555UTY-LNHUM/AR-RAH1U SWITCHING SELECTION OF FUNCTION SETTING MODE (2) Press and hold the “FAN” and the “ SET TEMP. p ” buttons. While holding these 2 buttons, press the "RESET" button. FAN SET TEMP. ( ) RESET Function setting mode display (3) Press the “ SET TEMP. p ” or “ SET TEMP. q ” buttons to select the signal code that matches the setting with the indoor unit. By selecting the appropriate signal code, the communication between the indoor unit and the wireless RC become possible.
BUTTON NAME AND FUNCTION ●●During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to FUNCTION DETAILS MODE button Setting number - Start the function setting mode - Changes the display digits Refer to FUNCTION DETAILS FAN button START/STOP button Transmits function setting Switches between the setting number (bottom line) and function number (top line) TIMER MODE button Transmits function mode SET TEMP.
FUNCTION SETTING (5) Press the “MODE” button to access the function setting mode. (6) Press the “ p ” or the “ q ” buttons to select the function number. Each time the “MODE” button is pressed, it switches between the one's place and the ten's place positions. Change digit (7) Press the FAN button to proceed to setting the number. (Press the FAN button again to return to the function number selection.) (8) Press the “ p ” or the “ q ” buttons to select the setting number.
COMPLETION OF FUNCTION SETTING MODE (11) Press the “RESET” button. RESET After pressing the RESET button, please set the signal code again if b,c,d setting. SETTING UP EACH INDOOR UNIT RESET THE POWER AFTER SETTING UP FUNCTION OF ALL INDOOR UNITS Important ●●If the reset is not performed, function can not be read in normally. ●●After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes. After the 2 minutes has passed, power can be restored.
REMOTE CONTROLLER SIGNAL CODE SETTING In function setting, please change to the setting that signal code setting of Wireless remote controller is the same as indoor unit according to the following content when you change signal code setting of indoor unit. 1. Press the "START/STOP" button until only 2. Press the "MODE" button for at least five the clock is displayed on the remote controller seconds to display the current signal code display. (initially set to A). SYSTEM DESIGN SYSTEM DESIGN 3.
5555555AR-RED1U SWITCHING SELECTION OF FUNCTION SETTING MODE (2) Press and hold the "POWERFUL" and "SET TEMP. buttons, press the "RESET" button. " buttons. While holding these 2 POWERFUL SET TEMP. ( ) RESET SYSTEM DESIGN SYSTEM DESIGN Function setting mode display - (06 - 61) - 6.
BUTTON NAME AND FUNCTION ●●During function setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to FUNCTION DETAILS Setting number Refer to FUNCTION DETAILS MIN HEAT button POWERFUL button Changes the display digits Switches between the setting number (bottom line) and function number (top line) SET TEMP.
FUNCTION SETTING (3) Press the " " or the " " buttons to select the function number. Each time the "MIN HEAT" button is pressed, it switehes between the one's place and the ten's place positions. Change digit Change digit (4) Press the "POWERFUL" button to proceed to the setting number. (Press the "POWERFUL" button again to return to the function number selection.) (5) Press the " " or the " " buttons to select the setting number.
COMPLETION OF FUNCTION SETTING MODE (8) Press the "RESET" button. RESET SETTING UP EACH INDOOR UNIT RESET THE POWER AFTER SETTING UP FUNCTION OF ALL INDOOR UNITS Important ●●If the reset is not performed, function can not be read in normally. ●●After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes. After the 2 minutes has passed, power can be restored.
REMOTE CONTROLLER SIGNAL CODE SETTING In function setting, please change to the setting that signal code setting of Wireless remote controller is the same as indoor unit according to the following content when you change signal code setting of indoor unit. 3. Press the SET TEMP. " " or the " " button to change the signal code between "A→b→c →d". 4. Press the "MODE" button again to return to the clock display. The signal code will be changed. SYSTEM DESIGN 2.
5555555AR-REG1U SWITCHING SELECTION OF FUNCTION SETTING MODE (2) Press and hold the "POWERFUL" and "SET TEMP. buttons, press the "RESET" button. " buttons. While holding these 2 POWERFUL SET TEMP. ( REG1U RESET ) REG1U SYSTEM DESIGN SYSTEM DESIGN Function setting mode display - (06 - 66) - 6.
BUTTON NAME AND FUNCTION ●●During function setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to FUNCTION DETAILS Setting number Refer to FUNCTION DETAILS MIN HEAT button POWERFUL button Changes the display digits Switches between the setting number (bottom line) and function number (top line) SET TEMP.
FUNCTION SETTING (3) Press the " " or the " " buttons to select the function number. Each time the "MIN HEAT" button is pressed, it switehes between the one's place and the ten's place positions. Change digit Change digit (4) Press the "POWERFUL" button to proceed to the setting number. (Press the "POWERFUL" button again to return to the function number selection.) (5) Press the " " or the " " buttons to select the setting number.
COMPLETION OF FUNCTION SETTING MODE (8) Press the "RESET" button. RESET REG1U SETTING UP EACH INDOOR UNIT RESET THE POWER AFTER SETTING UP FUNCTION OF ALL INDOOR UNITS Important ●●If the reset is not performed, function can not be read in normally. ●●After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes. After the 2 minutes has passed, power can be restored.
REMOTE CONTROLLER SIGNAL CODE SETTING In function setting, please change to the setting that custom code setting of Wireless remote controller is the same as indoor unit according to the following content when you change custom code setting of indoor unit. 3. Press the SET TEMP. " " or the " " button to change the custom code between A→b→c →d. 4. Press the "MODE" button again to return to the clock display. The custom code will be changed. SYSTEM DESIGN 2.
55555INDOOR UNIT (setting by wired remote controller) The function settings of the control of the indoor unit can be changed by this procedure ●● according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the “FUNCTION SETTING” according to the ●● installation conditions using the remote controller. The settings may be selected between the following two: Function Number or Setting ●● Number.
SWITCHING SELECTION OF FUNCTION SETTING MODE 2) To activate the function setting mode, hold down the three buttons of SET TEMP. V, SET TEMP. Λ and FAN at the same time for 5 seconds or longer. Function setting mode initial display BUTTON NAME AND FUNCTION ●●During address setting mode, indoor unit reject the any operation command from remote controller. Function number SYSTEM DESIGN Remote controller address Setting number It fixes to 00. Refer to FUNCTION DETAILS SET TEMP.
FUNCTION SETTING 3) Pressing the SET TIME < button or the SET TIME > button, to select the function number. Function number 4) Pressing the SET TEMP. V button or the SET TEMP. Λ button, to select the setting number. The display flashes during setting number selection. Setting number Ex.) Function number : 30, Setting number : 01 NOT GOOD ●● When the data was not set up on the indoor unit (-- is displayed.) ●● Set up the data again according to the procedure in step 3), 4) above.
COMPLETION OF FUNCTION SETTING MODE 6) To clear the function setting mode and return to the regular display, hold down the three buttons of SET TEMP. V, SET TEMP. Λ and FAN at the same time. Normal mode display * If no key entry is made for 60 seconds, even though none of the above buttons is pressed, the function setting mode will automatically be cleared.
55555INDOOR UNIT (setting by simple remote controller) The function settings of the control of the indoor unit can be changed by this procedure ●● according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the "FUNCTION SETTING" according to the ●● installation conditions using the remote controller. The settings may be selected between the following two: Function Number or Setting ●● Number.
SWITCHING SELECTION OF FUNCTION SETTING MODE 2) To activate the function setting mode, hold down the three buttons of SET TEMP. q, SET TEMP. p and FAN at the same time for 5 seconds or longer. Function setting mode initial display BUTTON NAME AND FUNCTION ●●During function setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to FUNCTION DETAILS Refer to FUNCTION DETAILS Remote controller address It fixes to 00.
FUNCTION SETTING 3) P ress the FAN button so that the "Function number" display flashes. Then, press either the SET TEMP. p button or the SET TEMP. q button to set up the function number. Function number 4) Press the FAN button so that the "Setting number" display flashes. Then, press either the SET TEMP. p button or the SET TEMP. q button to set up the setting number. Setting number Ex.
COMPLETION OF FUNCTION SETTING MODE 6) Press the three buttons of SET TEMP. p, SET TEMP. q and FAN at the same time for 5 seconds or longer. The function setting mode will be cleared and the regular display will be restored. Normal mode display * If no key entry is made for 60 seconds, even though none of the above buttons is pressed, the function setting mode will automatically be cleared.
55555FUNCTION DETAILS Compact cassette Slim duct Wall mounted Floor 1) Filter sign 2) Ceiling height - - - 3) Outlet directions - - - 4) Vertical airflow direction range control - - - 5) Static pressure - - 6) Room temperature control for cooling 7) Room temperature control for heating 8) Auto restart 9) Room temperature sensor switching 10) Remote controller custom code 11) External input control
4) Vertical airflow direction range control In a concealed installation, change the setting to "Fixed" (02) to restrict the movement of the upper air outlet so that the airflow is only towards the horizontal direction. Setting description Standard (Setting prohibited) Fixed (Concealed) Function number 23 (... Factory setting) Setting value 00 01 02 5) Static pressure Select appropriate static pressure according to the installation conditions. Setting description 0 in.WG (0 Pa) 0.04 in.
8) Auto restart Enable or disable automatic system restart after a power outage. Setting description Yes No Function number 40 (... Factory setting) Setting value 00 01 * Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or external input device.
13) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. Setting description Disable Enable Function number 49 (... Factory setting) Setting value 00 01 *00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting on the remote controller..
55555CENTRAL REMOTE CONTROLLER DIP Switch SW1 Memory backup setting SW2 Prohibited SW3 Prohibited SW4 Prohibited SW5 Prohibited SW6 Prohibited SWITCH POSITION DIP Switch ON ON OFF 1 2 3 4 5 6 SYSTEM DESIGN SYSTEM DESIGN Front case (back side) - (06 - 83) - 6.
DIP SWITCH SETTING SW1 setting zz ●●Memory backup setting Set to ON to use batteries for the memory backup. If batteries are not used, all of settings stored in memory will be deleted if there is a power failure. (u...Factory setting) u SW1 Memory backup OFF Invalidity ON Validity SW2 setting forbidden zz (u...Factory setting) SW2 u OFF Fixed at OFF ON Setting forbidden SW3 setting forbidden zz SYSTEM DESIGN SYSTEM DESIGN (u...
SW5 setting forbidden zz (u...Factory setting) SW5 u OFF Fixed at OFF ON Setting forbidden SW6 setting forbidden zz (u...Factory setting) OFF Fixed at OFF ON Setting forbidden SYSTEM DESIGN u SYSTEM DESIGN SW6 - (06 - 85) - 6.
55555WIRED REMOTE CONTROLLER DIP Switch 1 SW1 Prohibited SW2 Dual remote controller setting SW3 Prohibited SW4 °F / °C switch SW5 Prohibited SW6 Memory backup setting * Do not use DIP Switch 2 SWITCH POSITION Wired remote controller zz Front case (back side) OFF ON DIP Switch 2 (All switches fixed at OFF) DIP Switch 1 ON SYSTEM DESIGN SYSTEM DESIGN 1 2 3 4 5 6 - (06 - 86) - 6.
DIP SWITCH 1 SETTING SW1 setting prohibited zz (u...Factory setting) SW1 u OFF Fixed at OFF ON Setting prohibited SW2 setting zz ●●Dual remote controller setting Set the remote controller SW2 according to the following table. Number of remote controller u (u...Factory setting) Secondary Primary unit unit SW2 SW2 1 (Normal) OFF - 2 (Dual) OFF ON Indoor unit 1 2 3 1 2 3 Primary unit Remote controller cable 1 2 3 Secondary unit Remote controller SW3 setting prohibited zz (u...
SW5 setting prohibited zz (u...Factory setting) SW5 u OFF Fixed at OFF ON Setting prohibited SW6 setting zz ●●Memory backup setting (Wired remote controller only) Set to ON to use batteries for the memory backup. If batteries are not used, all of settings stored in memory will be deleted if there is a power failure. (u...Factory setting) u SW6 Memory backup OFF Invalidity ON Validity SYSTEM DESIGN SYSTEM DESIGN Never turn it ON in the case of simple remote controller. - (06 - 88) - 6.
55555SIMPLE REMOTE CONTROLLER DIP Switch SW1 Prohibited SW2 Dual remote controller setting SW3 °F / °C switch SW4 Prohibited SW5 Prohibited SW6 Prohibited SWITCH POSITION Simple remote controller zz OFF 1 2 3 4 5 6 ON SYSTEM DESIGN SYSTEM DESIGN DIP Switch - (06 - 89) - 6.
DIP SWITCH 1 SETTING SW1 setting prohibited zz (u...Factory setting) SW1 u OFF Fixed at OFF ON Setting prohibited SW2 setting zz ●●Dual remote controller setting Set the remote controller SW2 according to the following table. Number of remote controller u (u...Factory setting) Secondary Primary unit unit SW2 SW2 1 (Normal) OFF - 2 (Dual) OFF ON Indoor unit 1 2 3 1 2 3 Primary unit Remote controller cable 1 2 3 Secondary unit Remote controller SW3 setting prohibited zz (u...
SW5 setting prohibited zz (u...Factory setting) SW5 u OFF Fixed at OFF ON Setting prohibited SW6 setting prohibited zz (u...Factory setting) OFF Fixed at OFF ON Setting prohibited SYSTEM DESIGN u SYSTEM DESIGN SW6 - (06 - 91) - 6.
555555 DUCT STATIC PRESSURE SETTING MODELS : ARU7RLF, ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF The air flow setting other than the default value of 0.1inWG (25 Pa) may be changed to the required external static pressure. Setting of the air flow can be changed with the wireless remote controller, wired remote controller, and simple remote controller. How to set air flow (external static pressure) ●●Wireless remote controller Air flow is set by function number 26 (static pressure).
666CHECK RUN This operation allows the air conditioner to automatically check the status of the outdoor unit and check for wiring mistakes. Installation mistakes and positions where errors are occurring are shown by the outdoor unit display indicators. * The Check run time is used only as a guide.This time differs depending on the surrounding temperature conditions.
RESTRICTIONS APPLICABLE WHEN PERFORMING THE CHECK RUN SYSTEM DESIGN SYSTEM DESIGN ●●When the Check run starts, all indoor units connected to the outdoor unit will start to run automatically. During the Check run, you cannot check the operation of the indoor units separately. After the Check run, check the operation of the indoor units separately in normal operation.
66666CHECK RUN CHECK ITEMS AND PROCEDURE Use the following procedure to perform the Check run. Check Item 1. Turn on 1.1 Check power communications Procedure ▪ The power is on to the outdoor unit, connected branch boxes, and indoor units. When an error occurred ▪ Automatically determined after the power is turned on. ▪ The error codes can be checked using the ENTER button. ▪ T he determination takes about 2 minutes. (During this time, the outdoor unit 7 seg. displays are all lit.
66666CHECK RUN EXAMPLES : Wiring : Piping EXAMPLE1 When the number of piping is more than the number of wiring.
EXAMPLE3 When connection destination does not match.
EXAMPLE4 When connection destination does not match.
EXAMPLE5 When connection destination does not match Branch box 1 (Primary) Branch box 2 (Secondary) INDOOR UNIT A INDOOR UNIT B INDOOR UNIT C INDOOR UNIT A INDOOR UNIT B Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Branch box 3 (Secondary) INDOOR UNIT C INDOOR UNIT A Indoor unit 6 Indoor unit 7 INDOOR UNIT B INDOOR UNIT C Indoor unit 8 [Display (Check run ends)] LED981 POWER MODE LED961 Branch box 1 Indoor unit B to Switching every 2 seconds LED982 ERROR
66666RELOCATION AND INCREASE OF UNIT Perform the following operation when the number of indoor unit/branch box is changed or circuit board of branch box/outdoor unit are exchanged. The air conditioner doesn't work normally if the following operation is not performed. OPERATION METHOD 1) Turn on both the power supplies of the outdoor unit and the branch boxes. 2) Press the "MODE/EXIT" button of the outdoor unit when all units are in stop operation state.
777EXTERNAL INPUT & OUTPUT 77777 OUTDOOR UNIT Connector Low noise mode ― CN931 External input priority mode ― CN932 Peak cut mode ― CN933 Stop operation mode ― CN934 ― Error status CN951 ― Compressor status CN952 ― Base heater CN206 Remarks See external input/output settings for details. SYSTEM DESIGN Output SYSTEM DESIGN Input - (06 - 101) - 6.
7777777 EXTERNAL INPUT ON/OFF of the "Low noise mode", "External input priority mode", "Peak cut mode", and "Stop operation mode" functions can be enable with an external field device. LOW NOISE MODE ••The following reduces the operating sound of the outdoor unit from the normal sound. The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial timer or ON/OFF switch to a connector on the outdoor control PC board.
EXTERNAL INPUT PRIORITY MODE ••It is possible to switch to cooling operation or heating operation by using external input. Circuit diagram example zz Outdoor unit control PC board Connected unit Ex.) Switch Connector 1 2 Contact capacity : 24VDC or more, 10mA or more. *33ft. (10m) Signal Field supply * Make the distance from the PC board to the connected unit within 33ft. (10m). ••Use the following parts and construct a circuit as shown above.
PEAK CUT MODE ••Operation that suppressed the current value can be performed by means of the following onsite work. The air conditioner is set to the Peak cut mode when closing the contact input of a commercial ON/OFF switch to a connector on the outdoor control PC board. Circuit diagram example zz Outdoor unit control PC board Connected unit Ex.) Switch Connector 1 2 Contact capacity : 24VDC or more, 10mA or more. *33ft.
STOP OPERATION MODE ••It is possible to switch to Batch stop or Emergency stop and Normal operation by using external input. Circuit diagram example zz Outdoor unit control PC board Connected unit Ex.) Switch Connector 1 2 Contact capacity : 24VDC or more, 10mA or more. *33ft. (10m) Signal Field supply * Make the distance from the PC board to the connected unit within 33ft. (10m). ••Use the following parts and construct a circuit as shown above.
●●When function setting is "Emergency stop" mode ON OFF Input signal Emergency stop Command Normal Air conditioner Operation Stop ON Remote controller ON ON Remote control operation invalidity Parts (Optional) zz SYSTEM DESIGN External connect kit UTY-XWZXZ3 SYSTEM DESIGN Parts name Model name - (06 - 106) - 6.
7777777EXTERNAL OUTPUT ERROR STATUS OUTPUT ••An air conditioner error status signal is produced when a malfunction occurs. Circuit diagram example zz Outdoor unit control PC board Connected unit Connector 1 Vcc + 2 Vcc Power supply + Load *33ft. (10m) - 1) Power supply ●Voltage (Chart sign=Vcc) : DC 24V or less 2) Load ● Load : DC 500mA or less is recommended Signal Field supply * Make the distance from the PC board to the connected unit within 33ft. (10m).
COMPRESSOR STATUS OUTPUT ••Compressor operation status signal is produced when the compressor is running. Circuit diagram example zz Outdoor unit control PC board Connected unit Connector 1 Vcc + 2 Vcc Power supply 1) Power supply ●Voltage (Chart sign=Vcc) : DC 24V or less 2) Load ● Load : DC 500mA or less is recommended + Load *33ft. (10m) - Signal Field supply * Make the distance from the PC board to the connected unit within 33ft. (10m).
BASE HEATER •• A base heater is a heating element that may be installed to melt the ice that may accumulate in the condenser drain pan. •• This output signal is produced when the outdoor temperature drops down to 36°F (2°C), and releases at 39°F (4°C). Circuit diagram example zz connected unit P.C.B 1 Connector *1 Base heater *2 AC240V 2 3 4 *1: Connect to pin 1 and pin 3. No connection pin2 and pin4. *2: The allowable Input Power is 25W or less. connected unit P.C.
77777INDOOR UNIT EXTERNAL INPUT Indoor unit type Control input Operation status output ● ● ● ● Compact Cassette Slim Duct EXTERNAL OUTPUT Fresh air control Auxiliary heater output output ● ● Error status output ― ● Wall Mounted ● ● ― ― Floor ● ● ― ― ― ― ● (ASU9RLS2, ASU12RLS2, ASU15RLS2 ASU7RLF1 ASU9RLF1 ASU12RLF1) ● 7777777 EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) Connector Compact Cassette Slim Duct CN102 CN102 ASU7RLF ASU9RLF ASU12RLF CN303 Wall Mount
●●When function setting is "Operation/Stop" mode ON Input signal Indoor unit OFF Operation Stop ●●When function setting is "Forced stop" mode Input signal ON OFF Command Forced stop Normal Indoor unit Operation Stop Remote controller ON ON ON Remote control operation invalidity Compact Cassette Slim Duct UTY-XWZX UTD-ECS5A Parts name Model name (UTY-XWZX) Parts name Model name Wall Mounted ASU7RLF ASU9RLS2 ASU7RLF1 ASU9RLF ASU12RLS2 ASU9RLF1 ASU12RLF ASU15RLS2 ASU12RLF1 External connec
7777777EXTERNAL OUTPUT OPERATION STATUS OUTPUT Connector Compact Cassette Slim Duct CN103 CN103 ASU7RLF ASU9RLF ASU12RLF CN304 Wall Mounted ASU9RLS2 ASU7RLF1 ASU12RLS2 ASU9RLF1 ASU15RLS2 ASU12RLF1 CNB01 ASU18RLF ASU24RLF CN16 Floor AGU9RLF AGU12RLF AGU15RLF CN20 An air conditioner operation status signal can be output. Circuit diagram example zz Indoor unit control PC board *1 Connected unit Connector 24V DC 1 Ex.)Relay unit V 2 Ex.)Display Relay power supply 33ft. (10m) *2 Relay spec.
FRESH AIR CONTROL OUTPUT Compact Cassette Slim Duct Wall Mounted Floor CN6 CN6 ― ― Connector A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation. Circuit diagram example zz Indoor unit control PC board Connected unit Ex.) Fan Ex.) Relay unit 12 V Connector Relay power supply 1 on/off 2 *33ft. (10m) Relay spec.: Rated 12V DC, 50mA to less.
AUXILIARY HEATER OUTPUT Compact Cassette Slim Duct Wall Mounted Floor - CN10 ― ― Connector A signal is outputed from Connector when indoor fan and compressor turn on under heating operation. Tr-Ts * Signal output performance specifications are as OFF Tr-Ts = -2°F( -1°C) shown on the right Tr-Ts = -6°F( -3°C) Ex. When Set Temperature(Ts) is 72°F(22°C) ON ▪ and Room Temperature(Tr) increase above Tr-Ts = -20°F( -10°C) 52°F(12°C), signal output is on.
ERROR STATUS OUTPUT Compact Cassette Slim Duct ― ― Connector ASU7RLF ASU9RLF ASU12RLF ― Wall Mounted ASU9RLS2 ASU7RLF1 ASU12RLS2 ASU9RLF1 ASU15RLS2 ASU12RLF1 CNB02 ASU18RLF ASU24RLF ― Floor AGU9RLF AGU12RLF AGU15RLF CN21 An air conditioner error status signal can be output. Circuit diagram example zz Indoor unit control PC board *1 Connector 24V DC 1 V 2 Connected unit Ex.)Relay unit Ex.)Display Relay power supply 10m *2 Relay spec.: Max.24V DC, 10mA to less than 500mA.
888DRAIN CONNECTION 88888OUTDOOR UNIT CAUTION Perform drain work in accordance with this Manual, and ensure that the drain water is properly drained. If the drain work is not carried out correctly, water may drip down from the unit, wetting the furniture. When the outdoor temperature is 32°F (0 °C) or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold weather.
88888INDOOR UNIT GENERAL RULES OF DRAIN PROCESS ●●Install the drain pipe with downward gradient (1/100 or more) and so there are no rises in the pipe. ●●Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride) so that there is no leakage. ●●Support the drain pipe with supporters each 5 to 7 ft. (1.5 to 2.0 m) ●●Do not perfrom air bleeding. ●●Always heat insulate the indoor side of the drain pipe.
SLIM DUCT TYPE Ceiling concealed setting zz Supporter Drain hose Drain cap Arrange the drain hose lower than this position 5 to 7ft. (1.5 to 2.0m) Not good Trap Air bleeding Rise Floor standing concealed setting zz Not good Trap - (06 - 118) - SYSTEM DESIGN SYSTEM DESIGN Drain cap Rise 6.
Gap of 5 to 7ft. (1.5-2.0 m) Supporter Max. 12 in. (300 mm) 28 in. (700 mm) or less Locally arranged pipe PVC pipe (Local arrangement) (3/4 inch) Horizontal or upward gradient Not good Air bleeding Rise Trap CAUTION ●●Drain lift-up pipe restrictions: (1) Lift-up height ≤ 28 in. (700 mm) (from ceiling) (2) Drain hose (pipe) length ≤ 12 in. (300 mm) (between indoor unit and lift-up pipe) SYSTEM DESIGN SYSTEM DESIGN ●●When a dimensions exceed the above restrictions will cause water leakage.
WALL MOUNTED TYPE (ASU7RLF1, ASU9RLF1, ASU12RLF1, ASU7RLF, ASU9RLF, ASU12RLF, ASU9RLS2, ASU12RLS2, ASU15RLS2) Installation method of Drain cap For left outlet piping, cut off the piping outlet cutting groove with a hacksaw. No gap No gap Remove the drain cap by pulling at the projection at the end of the cap with pliers, etc. And remove the insulation.
CENTRAL DRAIN PROCESS 4 in. (100 mm) or more When converging multiple drain pipes , install according to the procedure shown below. 4 in. (100 mm) or more T-joint converging drain pipes SYSTEM DESIGN SYSTEM DESIGN Select converging drain pipes whose diameter is suitable for the operating capacity of the unit. - (06 - 121) - 6.
DRAIN INSULATION ●●Please confirm water flows into Drain pan of the indoor unit, and drain is done normally when the connection of Drain hose is completed. ●●Please check whether there is water leak part in the Drain piping. ●●Please insulate it from heat by the heat insulator of enough thickness so that there is no dewy when the confirmation ends. ●●Fix the drain pipe on to the wall with saddle.
999STANDARD ACCESSORIES 99999OUTDOOR UNIT The following installation parts are supplied. Use them as required. Do not discard any accessories until the installation work has been completed. Name and shape Installation manual Q'ty Application 1 Drain pipe 1 For outdoor unit drain piping work 7 For outdoor unit drain piping work Drain cap Wire clamper 3 Conduit plate For binding power cable and connection cable For conduit fixed SYSTEM DESIGN SYSTEM DESIGN 1 - (06 - 123) - 6.
99999INDOOR UNIT COMPACT CASSETTE TYPE INDOOR UNIT ACCESSORIES Installation manual Coupler heat insulation (Small) Coupler heat insulation (Large) Special nut A (Large flange) Special nut B (Small flange) SYSTEM DESIGN Template (Carton top) Q'ty Application Name and shape Connector cover 1 1 Tapping screw (M5 × 12mm) For indoor side pipe joint (Liquid pipe) Tapping screw (M4 × 12mm) For indoor side pipe joint (Gas pipe) L angle For installing indoor unit Hook wire 4 1 Hose band 1 2 F
SLIM DUCT TYPE Name and shape Operating manual Q'ty Application Name and shape Filter (Small) Q'ty Application 2 1 (AR9/ 12/24) Installation manual Filter (Big) 1 Installation template 1 2 (AR18) For positioning the indoor unit 1 (AR24) Drain hose Washer For installing indoor unit 1 For installing drain pipe (3/4 inch) 8 Hose band Coupler heat insulation (Small) SYSTEM DESIGN Cable tie 1 For indoor side pipe joint (Large pipe) 1 Drain hose insulation B 1 For indoor side pipe j
WALL MOUNTED TYPE (ASU7RLF1, ASU9RLF1, ASU12RLF1) Name and shape Operating manual Installation manual Q'ty Q'ty Application .
WALL MOUNTED TYPE (ASU9RLS2, ASU12RLS2, ASU15RLS2) Name and shape Operating manual Installation manual Q'ty Q'ty 1 Application It is used when the diameter of gas pipe is Ø12.70 or more. It is necessary when using AS15.
FLOOR TYPE (AGU9RLF, AGU12RLF, AGU15RLF) Installation manual Q'ty Q'ty Application 1 Air cleaning filter 1 1 Cloth tape 1 9 2 For indoor unit installation Wireless remote controller For indoor unit installation Battery For wall hook bracket installation Wireless remote controller holder 1 2 1 2 SYSTEM DESIGN Tapping screw (M3 x 12mm) Name and shape Cable tie 1 Wall hook bracket Tapping screw (M4 x 25mm) Application SYSTEM DESIGN Name and shape Operating manual - (06 - 128) -
1111 OPTIONAL PARTS INSTALLATION 111111 FRESH AIR INTAKE KIT MODEL : UTZ-VXAA FEATURE •• It can be taken in fresh air of up to 10% of “high” air volume of the indoor unit by attaching Fresh Air Intake Kit to cassette type indoor unit.
SPECIFICATIONS Dimension (HxWxD) %(for High) 10 in. (mm) Pcs ø 3-15/16 (100) 1 4-3/4 x 22-7/16 x 22-7/16 (120 x 570 x 570) 6-1/2 x 23-1/16 x 23-1/16 (165 x 585 x 585) 8 ( 3.5 ) 12 ( 5.5 ) in. (mm) lbs. (kg) SYSTEM DESIGN Weight Net Gross Net Gross UTZ-VXAA SYSTEM DESIGN Model name Fresh air Max. fresh air intake intake volume Connection duct type - (06 - 130) - 6.
PRECAUTION About fresh air intake kit zz ••The Fresh Air Intake Kit can be installed onto cassette type air conditioners. •• The volume of ventilated air provided by the Fresh Air Intake Kit may be unable to fulfill ventilation regulations in all countries. On such occasions we ask that this kit be used along with Energy recovery ventilators. •• When intaking outside air please ensure correct air-conditioning design as based on airconditioning load calculations.
DIMENSIONS Unit : in. (mm) Min.17-11/16 (450) 4-1/4 (108) 3-15/16 (100) 7-15/16 (201) 22-7/16 (570) 12-15/16 (328) 12-3/16 (310) 15-11/16 (398) 1-3/4 (45) Ceiling opening space 10-1/8 (257) 22-7/16 (570) 26-7/8 (683) 5-7/8 to 7-7/8 (150 to 200) Inspection hatch (SIDE VIEW) 4-3/4 (120) SYSTEM DESIGN 15-6/16 (390) SYSTEM DESIGN (TOP VIEW) (SIDE VIEW) •• When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) - (06 - 132) - 6.
0.80 (200) Unit : in. (mm) 0.60 (150) 0.40 (100) 0.20 (50) 450 (17-11/16) (0) 0 (0) 29 (50) 59 88 (100) (150) Air flow [CFM (m3/h)] 118 (200) Measurement position of shown in the graph SYSTEM DESIGN 0 SYSTEM DESIGN Static pressure of Fresh air intake kit [in.WG (Pa)] AIR FLOW - (06 - 133) - 6.
FRESH AIR CONTROL OUTPUT ••You can control duct fan by synchronization with fan operation of indoor unit. ••Wire for fresh air control output is supplied with Fresh Air Intake Kit. ••Extended length of the wire : For Single & Multi split system : Max. 33ft. (10m) Connection diagram zz ••For Relay Output voltage : DC12V ± 2V Permissible current : 15mA P.C.
ACCESSORY PARTS Name and shape Installation manual Q'ty Application Name and shape Extension wire for receiver kit 1 Chamber 1 Wire cover Air joint for connection duct Wire (External output ) Cover for extension wire Wire (External output ) 1 Screw 4 Extension wire for louver Bolt Extension wire for louver Cable tie 1 1 For connect indoor unit to relay of duct fan (For single or multi) 1 For connect indoor unit to relay of duct fan (For VRF) 4 2 Application Extension wire for recei
INSTALLATION Mounting of indoor unit zz ●●Please refer to the installation manual provided with the indoor unit for mounting. ●●Please refer to the diagram below for installation height. ●●When installing this product to existing indoor units, please adjust the installation height of the indoor units to height 9-1/16 to 9-1/4 in. (230 to 235 mm) Unit : in.
Chamber installation zz Fit the four-sided holes of the chamber together with the hook fittings of the Fresh Air Intake Kit (in two places), and secure the attached chamber in place with screws provided. Ø3-15/16 (100) Unit : in. (mm) screw x 2 hook fittings SYSTEM DESIGN SYSTEM DESIGN ●●When using the “UTZ-KXGC” kit for high humidity, please first cut off and remove the heat insulation as shown in the figure.
Duct installation zz ●●Please fasten the connecting parts of the ducts with band, and wrap with vinyl tape to ensure no air leaks. [Carry out the work to ensure no air leakage at a pressure of 0.80in.WG (200 Pa)] ●●Please do not construct the duct in the manner of below.
Installation of cassette grille zz 1) Please connect extension wires for use with louvers, or extension wire for optical receiver after provisional attaching of the cassette grille. 2) Tie the wires together with the fasteners provided and insert into the hole of the Fresh Air Intake Kit. 3) Install the wire-cover provided on the Fresh Air Intake Kit. 4) Please install cassette grille according to the installation instruction sheet provided.
1111 REFRIGERANT CONCENTRATION PRECAUTIONS The system designer and installer are to ensure that the system adheres to all local regulations regarding refrigerant leakage. 111111 INTRODUCTION Designing HFI systems requires special attention to codes and standards relating to Refrigeration Concentration Limit (RCL). The RCL is intended to “reduce the risks of acute toxicity, asphyxiation and flammability hazards in normally occupied, enclosed spaces”.
111111 CHECKING CONCENTRATION LIMIT Check concentration limit following steps , and take appropriate measures depending on the situation. Calculate amount of refrigerant [lbs. (kg)] per refrigerant system. Amount of refrigerant per refrigerant system Amount of factory charged refrigerant + Amount of additional refrigerant Amount of refrigerant added to system based on pipe length, pipe size and indoor units.
111111 REFRIGERATION CONCENTRATION COUNTERMEASURES When the concentration limit is exceeded, the designer will need to change the original design or use one of the countermeasures below to reduce potential exposure to refrigerant. Always consult local codes to ensure proper design. ●●Countermeasure 1 Provide opening for ventilation. Provide 0.15% or more opening to floor space both above and below or provide opening without door. (0.15% floor opening based on standard ceiling height of 8.8 ft. (2.
1111 INSTALLATION PRECAUTIONS 111111 INDOOR UNIT INSTALLATION PRECAUTIONS Note: T he information listed below are general precautions. Some models also include items that do not apply. PLACES WHERE USE PROHIBITED ●●Places where there is the danger of combustible gas leakage. ●●Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is generated ●●Places where there is a lot of oil splash and steam (kitchen, machinery room, etc.
[Installation precautions] When inside the ceiling is high temperature and high humidity Contents When the indoor unit is installed where the inside of the ceiling is 30°C (86°F) RH80% or greater, the dew point temperature of the outer perimeter may become higher than the cabinet surface temperature and moisture will condense on the surface of the cabinet and water drops may fall inside the room. →Refer to Fig.
[Installation precautions] When installing duct type in ceiling chamber system In the case of the ceiling chamber system (duct is not installed at indoor unit inlet side and room air is sucked into the indoor unit through the inside of the ceiling), the thermistor inside the indoor unit may not correctly detect the room temperature. Heating operation: Room is not heated because the indoor unit is easily turned off by the thermostat.
111111 OUTDOOR UNIT INSTALLATION PRECAUTIONS Note: T he information listed below are general precautions. Some models also include items that do not apply.
Hybrid Flex Inverter System 7. OPTIONAL PARTS DTR_BMU004E_02--CHAPTER07 2013.12.
CONTENTS 7. OPTIONAL PARTS 1. SEPARATION TUBE...................................................................... 07 - 01 2. BRANCH BOX................................................................................ 07 - 02 3. CONTROLLER............................................................................... 07 - 04 4. CASSETTE GRILLE....................................................................... 07 - 05 5. OTHERS..............................................................................
111SEPARATION TUBE MODEL : UTP- SX248A Unit: in. (mm) Port diameters zz Liquid pipe Gas pipe Q'ty ø 3/8 (9.52) Q'ty ø 5/8 (15.88) 1 1 Heat insulation zz For liquid pipe Q'ty For gas pipe 1 Q'ty 1 Dimensions zz 3-9/16 (90) 3-5/32 (80) OPTIONAL PARTS Gas pipe OPTIONAL PARTS Liquid pipe 15-3/16 (386) 14-13/16 (376) - (07 - 01) - 7.
222BRANCH BOX Model UTP-PU03A UTP-PU03B Type Primary Secondary DIMENSION 8-7/16 (214) 6-7/8 (174) Unit : in.
ACCESSORIES Q'ty Application Name and Shape Washer Q'ty 8 1 Tapping screw Coupler heat insulation (large) Coupler heat insulation (small) 4 4 Insulation (long) For indoor and outdoor side pipe joint (liquid pipe) (M4×25) 8 3 4 For suspending the Branch box from ceiling Insulation (short) 3 Insulation Hanger 8 Tapping screw For use on the section where the insulation fits onto this equipment (indoor unit side) For use on the section where the insulation fits onto this equipment (outdoor
333CONTROLLER LINE UP Indoor units Type Wall mounted ASU7RLF1 ASU7RLF ASU9RLS2 ASU18RLF ASU9RLF1 ASU9RLF ASU12RLS2 ASU24RLF ASU12RLF1 ASU12RLF ASU15RLS2 Model Compact Cassette Slim Duct Floor Central remote controller UTY-DMMUM *1 *1 *1 *1 *1 *1 *1 Wired Remote Controller UTY-RNNUM *4 *2 *3 Simple Remote Controller UTY-RSNUM *4 *2 *3 UTY-LNHUM - - - - - AR-RAH1U - - - - - - AR-RED1U - - - - - - AR-
444CASSETTE GRILLE LINE UP Type Cassette grille Indoor units Model Compact Cassette Slim Duct Floor UTG-CCGF - - Wall mounted ASU7RLF1 ASU7RLF ASU9RLS2 ASU18RLF ASU9RLF1 ASU9RLF ASU12RLS2 ASU24RLF ASU12RLF1 ASU12RLF ASU15RLS2 - - - - PARTS OPTIONAL PARTS Model : UTG-CCGF OPTIONAL PARTS Cassette grille - (07 - 05) - 7.
555OTHERS LINE UP Indoor units Wall mounted Type Model Compact Cassette Slim Duct Floor ASU7RLF1 ASU7RLF ASU9RLS2 ASU9RLF1 ASU9RLF ASU12RLS2 ASU12RLF1 ASU12RLF ASU15RLS2 ASU18RLF Outdoor unit ASU24RLF Air outlet shutter plate UTR-YDZB - - - - - - - Insulation kit for high humidity UTZ-KXGC - - - - - - - Fresh air intake kit UTZ-VXAA - - - - - - - External control set UTD-ECS5A - - - - - - - External connect kit UTY-XWZX - - - *1 -
PARTS Air outlet shutter plate Models : UTR-YDZB Insulation kit for high humidity Model : UTZ-KXGC Insulation Kit For Compact Cassette type For Compact Cassette type Fresh air intake kit Model : UTZ-VXAA External control set (x1) (x2) (x1) (x2) For Compact Cassette type External connect kit For Slim Duct type Model : UTY-XWZX External connect kit Model : UTY-XWZXZ3 (x1) For Compact Cassette, Wall Mounted (ASU7RLF, ASU9RLF, ASU12RLF, ASU18RLF, ASU24RLF) type External connect kit (For B
PARTS Communication kit Model : UTY-XCBXZ1 For Wall Mounted (ASU7RLF, ASU9RLF, ASU12RLF) type Communication kit Communication kit Model : UTY-XCBXZ2 For Wall Mounted (ASU7RLF1, ASU9RLF1, ASU12RLF1) type Model : UTY-TWBXF OPTIONAL PARTS OPTIONAL PARTS For Wall Mounted (ASU9RLS2, ASU12RLS2, ASU15RLS2) type - (07 - 08) - 7.
Hybrid Flex Inverter System FUJITSU GENERAL LIMITED 1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan URL : http://www.fujitsu-general.com Copyright© 2010-2013 Fujitsu General Limited. All rights reserved. Product specifications are subject to change without notice. Printed in Japan 2013.12.