SPARC Enterprise T5120 and T5220 Servers Site Planning Guide TM Manual Code C120-H027-03EN Part No.
Copyright © 2009 Sun Microsystems, Inc., 4150 Network Circle, Santa Clara, California 95054, U.S.A. All rights reserved. FUJITSU LIMITED provided technical input and review on portions of this material. Sun Microsystems, Inc. and Fujitsu Limited each own or control intellectual property rights relating to products and technology described in this document, and such products, technology and this document are protected by copyright laws, patents and other intellectual property laws and international treaties.
Copyright © 2009 Sun Microsystems, Inc., 4150 Network Circle, Santa Clara, California 95054, Etats-Unis. Tous droits réservés. Entrée et revue tecnical fournies par FUJITSU LIMITED sur des parties de ce matériel. Sun Microsystems, Inc. et Fujitsu Limited détiennent et contrôlent toutes deux des droits de propriété intellectuelle relatifs aux produits et technologies décrits dans ce document.
Contents Preface vii SPARC Enterprise T5120 and T5220 Servers Site Planning Guide Physical Specifications 2 Minimum Clearance for Service Access Environmental Specifications Power Source Requirements Acoustic Noise Emissions 3 4 5 8 Agency Compliance Specifications 9 Operating Environment Requirements Electrical Power 1 9 10 Ambient Temperature 10 Ambient Relative Humidity Airflow Considerations 10 11 v
vi SPARC Enterprise T5120 and T5220 Servers Site Planning Guide • July 2009
Preface This guide provides the specifications and site requirements you need when planning the installation of the SPARC Enterprise™ T5120 and T5220 servers. For Safe Operation This manual contains important information regarding the use and handling of this product. Read this manual thoroughly. Use the product according to the instructions and information available in this manual. Keep this manual handy for further reference.
Related Documentation The latest versions of all the SPARC Enterprise Series manuals are available at the following Web sites: Global Site (http://www.fujitsu.com/sparcenterprise/manual/) Japanese Site (http://primeserver.fujitsu.
Title Description Manual Code SPARC Enterprise T5120 and T5220 Servers Service Manual How to run diagnostics to troubleshoot the server, and how to remove and replace parts in the server C120-E463 SPARC Enterprise T5120 and T5220 Servers Administration Guide How to perform administrative tasks that are specific to the servers C120-E464 Integrated Lights Out Manager 2.0 User’s Guide Information that is common to all platforms managed by Integrated Lights Out Manager (ILOM) 2.
Note – Product Notes are available on the website only. Please check for the recent update on your product. Fujitsu Welcomes Your Comments If you have any comments or requests regarding this document, or if you find any unclear statements in the document, please state your points specifically on the form at the following URL. For Users in U.S.A., Canada, and Mexico: (https://download.computers.us.fujitsu.com/) For Users in Other Countries: (http://www.fujitsu.com/global/contact/computing/sparce_index.
SPARC Enterprise T5120 and T5220 Servers Site Planning Guide This guide provides specifications and site planning requirements for the SPARC Enterprise T5120 and T5220 servers. This guide contains the following sections.
Physical Specifications TABLE 1 SPARC Enterprise T5120 Server Physical Specifications Description U.S. Metric Width 16.75 in. 425 mm Depth 28.125 in. 714 mm Height 1.746 in. 44 mm Weight, approximate (without PCI cards and rackmounts) 40 lb 18 kg TABLE 2 SPARC Enterprise T5220 Server Physical Specifications Measure U.S. Metric Width 16.75 in. 425 mm Depth 28.125 in. 714 mm Height (2 rack units) 3.49 in.
Minimum Clearance for Service Access TABLE 3 Minimum Clearances Needed for Service for Both Servers Description Clearance Clearance, front of system 36 in. (91 cm) Clearance, rear of system 36 in.
Environmental Specifications TABLE 4 Environmental Specifications for Both Servers Specification Operating Nonoperating • Sea level to 2953 ft (900m): 41°F to 95°F (5°C to 35°C) -40° F to 149° F (-40°C to 65°C) Temperature • Above 2953 ft (900m): Decrease the maximum allowable temperature by 1.
Power Source Requirements Both the SPARC Enterprise T5120 and T5220 servers have two autoranging power supplies. To ensure redundant operation of the power supplies, connect the two power cords to separate circuits. Server models that run on DC input power require that you build power cables and connect to DC input power as specified in the SPARC Enterprise T5120 and T5220 Server Installation Guide. Use the specifications only as a planning guide.
TABLE 6 SPARC Enterprise T5120 Server (8-Disk Capable) Power Specifications General Specifications AC Input Models DC Input Models Operating input voltage range (input voltage tolerance +/- 10%) 100 to 240 VAC, 50-60 Hz -48 to -60 VDC Maximum operating input current Maximum operating input current At 100 VAC: 7.3A At 200 VAC: 3.7A At -48 VDC: 16.3A Maximum operating input power At 100 VAC: 697.4 W At -48 VDC: 651.4 W Maximum heat dissipation 2379.5 BTU/hour (2510.5 KJ/hour) 2222.
TABLE 7 SPARC Enterprise T5220 Server (8-Disk Capable) Power Specifications Maximum Server Configuration Specifications Under Nominal Temperature and Voltage Conditions (8 core, 1.6 GHz processor, with sixteen 4 GB FBDIMMs, 8 HDDs, 6 PCIe I/O cards) Idle input power 471.5 W 440.4 W Peak input power running SpecJBB 807.4 W 754.1 W Minimum Server Configuration Specifications Under Nominal Temperature and Voltage Conditions (4 core, 1.
Note – The maximum operating input current values are based on P / (V * 0.95), where P=maximum operating input power, V=input voltage. Example: 662 / (110 * 0.95) = 6.33 A at 110 VAC. You can use this equation to calculate the maximum operating input current for your specific input voltage. Related Information ■ “Acoustic Noise Emissions” on page 8 Acoustic Noise Emissions Declared noise emissions for both the SPARC Enterprise T5120 and T5220 servers are in accordance with ISO 9296 standards.
Agency Compliance Specifications Refer to the SPARC Enterprise T5120 and T5220 Servers Safety and Compliance Guide for a full list of agency compliance specifications. Related Information ■ “Operating Environment Requirements” on page 9 Operating Environment Requirements The operating environment requirements are the same for both the SPARC Enterprise T5120 and T5220 servers.
Electrical Power Good practice is to connect each power supply to a separate circuit. This redundancy enables the system to remain operational if one of the circuits fails. Consult your local electrical codes for any additional requirements. Related Information ■ “Ambient Temperature” on page 10 Ambient Temperature An ambient temperature range of 21˚C (69.8˚F) to 23˚C (73.4˚F) is optimal for server reliability. At 22˚C (71.6˚F) it is easy to maintain safe relative humidity levels.
Related Information ■ “Ambient Relative Humidity” on page 10 Airflow Considerations ■ Ensure unobstructed airflow through the chassis. ■ Ensure that inlet air enters at the front of the server and exits from the back. ■ Ensure that the server ventilation openings used for intake and outflow of air provide an open area that is at least 60% of the open area perforations across the front and rear of the server.
12 SPARC Enterprise T5120 and T5220 Servers Site Planning Guide • July 2009