FUJITSU Server PRIMEQUEST 2000 Series Hardware Installation Manual C122-H007-01EN
Preface Preface This manual describes the functions and features of the PRIMEQUEST 2000 series. The manual is intended for system administrators. For details on the regulatory compliance statements and safety precautions, see the PRIMEQUEST 2000 Series Safety and Regulatory Information (C122-E171XA). Errata and addenda for the manual The PRIMEQUEST 2000 Series Errata and Addenda (C122-E182EN) provides errata and addenda for the manual.
Preface Revision History Edition 1 Date 2014-02-18 Revised location (type) (*1) - Description - *1: Chapter, section, and item numbers in the "Revised location" column refer to those in the latest edition of the document. However, a number marked with an asterisk (*) denotes a chapter, section, or item in a previous edition of the document.
Preface Product operating environment This product is a computer intended for use in a computer room environment. For details on the product operating environment, see the following manual: PRIMEQUEST 2000 Series Hardware Installation Manual (C122-H007EN) Safety Precautions Alert messages This manual uses the following alert messages to prevent users and bystanders from being injured and to prevent property damage.
Preface List of important alert items This manual does not contain important alert items. Warning labels Never remove the warning labels.
Preface Warning label location (PCI_Box) v C122-H007-01EN
Preface Notes on Handling the Product About this product This product is designed and manufactured for standard applications. Such applications include, but are not limited to, general office work, personal and home use, and general industrial use. The product is not intended for applications that require extremely high levels of safety to be guaranteed (referred to below as "safety-critical" applications).
Preface Note on erasing data from hard disks when disposing of the product or transferring it Disposing of this product or transferring it as is may enable third parties to access the data on the hard disk and use it for unforeseen purposes. To prevent the leakage of confidential information and important data, all of the data on the hard disk must be erased before disposal or transfer of the product. However, it can be difficult to completely erase all of the data from the hard disk.
Preface Manual How to use this manual This manual contains important information about the safe use of this product. Read the manual thoroughly to understand the information in it before using this product. Be sure to keep this manual in a safe and convenient location for quick reference. Fujitsu makes every effort to prevent users and bystanders from being injured and to prevent property damage. Be sure to use the product according to the instructions in this manual.
Preface Title Description Manual code PRIMEQUEST 2000 Series Lists the messages that may be displayed when a problem occurs C122-E178EN Message Reference during operation and describes how to respond to them. PRIMEQUEST 2000 Series Describes REMCS service installation and operation C122-E180EN PRIMEQUEST 2000 Series Defines the PRIMEQUEST 2000 series related terms and C122-E179EN Glossary abbreviations.
Preface Title Description MegaRAID SAS Software Manual code Provides technical information on using RAID controllers. None Refer to the manual from the SVS-ServerView Suite ServerBooks DVD(Manual)2 supplied with the product or from the following URL: The Fujitsu Technology Solutions manuals server http://manuals.ts.fujitsu.com/ MegaRAID SAS Device Driver Provides technical information on using RAID controllers.
Preface Inside, Celeron, Celeron Inside, Itanium, Itanium Inside, Pentium, Pentium Inside, Xeon, Xeon Phi, Xeon Inside, Ultrabook are trademarks or registered trademarks of Intel Corporation. - Ethernet is a registered trademark of Fuji Xerox Co., Ltd. in Japan and is a registered trademark of Xerox Corp. in the - VMware is a trademark or registered trademark of VMware, Inc. in the United States and other countries. - Novell and SUSE Linux Enterprise Server are trademarks of Novell, Inc.
Preface - The PDF file of this manual is intended for display using Adobe® Reader® in single page viewing mode at 100% zoom. This manual shall not be reproduced or copied without the permission of Fujitsu Limited.
Preface Contents Preface................................................................................................................................................................................................................ i CHAPTER 1 Installation Data....................................................................................................................................................................1 1.1 Configuration Contents of Device ...........................................
Preface A.2.2 Requirements for mounting in a third party's rack.......................................................................................................................
Preface Figures FIGURE 1.1 PRIMEQUEST 2400E/2800E front view ...........................................................................................................................1 FIGURE 1.2 PRIMEQUEST 2400E/2800E rear view ............................................................................................................................2 FIGURE 1.3 PRIMEQUEST 2400E/2800E top view.................................................................................................................
Preface FIGURE 2.24 200 V Redundant Power Feed Configuration (Single power feed, Redundant Power Feed) Power Distribution Box Connection...................................................................................................................................................................................... 29 FIGURE 2.25 200 V Dual Power Feed Configuration with Power Distribution Box Connection ....................................................... 29 FIGURE 2.
Preface Tables TABLE 1.1 Name and Contents of Configuration of Each device..........................................................................................................1 TABLE 1.2 Installation Specifications (PRIMEQUEST 2400E)..............................................................................................................6 TABLE 1.3 Installation Specifications (PRIMEQUEST 2800E).........................................................................................................
CHAPTER 1 Installation Data 1.1 Configuration Contents of Device CHAPTER 1 Installation Data It explains the various data used while installing various drawings for device configuration, device overview, installation specification and layout. 1.1 Configuration Contents of Device It shows the name and contents of configuration of each device. TABLE 1.
CHAPTER 1 Installation Data 1.2 External Overview of Device FIGURE 1.2 PRIMEQUEST 2400E/2800E rear view FIGURE 1.3 PRIMEQUEST 2400E/2800E top view FIGURE 1.
CHAPTER 1 Installation Data 1.2 External Overview of Device PRIMEQUEST 2800B FIGURE 1.5 PRIMEQUEST 2800B front view FIGURE 1.6 PRIMEQUEST 2800B rear view FIGURE 1.
CHAPTER 1 Installation Data 1.2 External Overview of Device FIGURE 1.
CHAPTER 1 Installation Data 1.2 External Overview of Device 1.2.2 External Overview of Device (PCI_Box) Device External Overview (Front view, Rear view, Top view, Right side view) of PCI_Box is shown below. FIGURE 1.9 Front View of PCI_Box FIGURE 1.10 Rear View of PCI_Box FIGURE 1.11 Top View of PCI_Box FIGURE 1.
CHAPTER 1 Installation Data 1.3 Installation Specifications 1.3 Installation Specifications This section explains installation specification of each equipment. 1.3.1 Installation specifications (PRIMEQUEST 2400E) TABLE 1.2 Installation Specifications (PRIMEQUEST 2400E) Item External Width Dimensions Length(*1) [mm(in.
CHAPTER 1 Installation Data 1.3 Installation Specifications *2: Numeric value when each optional device is mounted for maximum number of options. However, rail for mounting rack (5.7kg) and cable type are not included. Mass as per the installation configuration can be calculated using formula as shown below. Device Mass: 78 + (11.1* A) + (2.5* B) + (1.8* C) + (3.
CHAPTER 1 Installation Data 1.3 Installation Specifications 1.3.2 Installation Specifications (PRIMEQUEST 2800E) TABLE 1.3 Installation Specifications (PRIMEQUEST 2800E) Items Dimensions [mm (in.)] Interruptible power source Contents 445(17.52) 782(30.79) 438(17.25) 10U 150(331) 17,712(16,787) High efficiency power supply (*13) 17,388(16,480) Recommended environmental temperature Max. 12(424) At the time of operation (*5) 20 to 80 29 (84.
CHAPTER 1 Installation Data 1.3 Installation Specifications For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to 29°C (41 to 84.2°F) Error of + 100m in the sea level settings of the location of installation is permissible. *6: Downtime is the condition in which the device is packed and maintained. *7: Level of noise which is actually heard varies as per the mounting condition of the position from where the noise is heard or the position of rack.
CHAPTER 1 Installation Data 1.3 Installation Specifications 1.3.3 Installation Specifications (PRIMEQUEST 2800B) TABLE 1.4 Installation Specifications (PRIMEQUEST 2800B) Items Dimensions [mm (in.)] Interruptible power source Contents 445(17.52) 782(30.79) 438(17.25) 10U 143(315) 16,992(16,105) High efficiency power supply (*13) 16,740(15,866) Recommended environmental temperature Max. 12(424) At the time of operation (*5) 20 to 80 29 (84.
CHAPTER 1 Installation Data 1.3 Installation Specifications For 1000 to 1500 m (3281 to 4921 ft) above sea level, temperature range at the time of installation: 5 to 33°C (41 to 91.4°F) For 1500 to 2000 m (4921 to 6562 ft) above sea level, temperature range at the time of installation: 5 to 31°C (41 to 87.8°F) For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to 29°C (41 to 84.
CHAPTER 1 Installation Data 1.3 Installation Specifications 1.3.4 Installation Specifications (PCI_Box) TABLE 1.5 Installation Specifications (PCI_Box) Item Width Depth Length Mass [kg (lb)] (*2) Conditions Max.
CHAPTER 1 Installation Data 1.4 Installation Area *7: Level of noise which is actually heard varies as per the mounting condition of the position from where the noise is heard or the position of rack. *8: Level of noise and level of acoustic power changes according to the environmental temperature *9: Downtime is the condition in which the device is installed. However, the power is switched off. *10: Value at the time of operations. *11: Value of 1 input cable *12: Value of 1 device 1.
CHAPTER 1 Installation Data 1.5 Flow of Cooling Air and Exhaust Air of Installation 1.5 Flow of Cooling Air and Exhaust Air of Installation Here, the flow of the cooling air and the exhaust of each device are explained. Note Flow of cooling air and exhaust air should be considered while studying the installation of a device. If device is installed without considering them, it may get affected by inhaling the exhaust air from the other device.
CHAPTER 1 Installation Data 1.6 Installation Environment 1.6 Installation Environment This section describes the installation environment of the base cabinet and PCI_Box. 1.6.1 Dust Suspended Particles 3 Suspended particles in a computer room should not exceed 0.15mg/m . A computer is designed in such a way that it withstands the suspended particles. This value is permissible in an ordinary office.
CHAPTER 2 Connected Information 2.1 Connection summary CHAPTER 2 Connected Information This section describes the connection summary of cable and cable used in PRIMEQUEST 2000 series. 2.1 Connection summary This section shows the Device connection summary of PRIMEQUEST 2000 series. FIGURE 2.
CHAPTER 2 Connected Information 2.2 Connection of signal cable TABLE 2.1 Notes for Device connection Number *1 Configured part SB Description PRIMEQUEST 2400E PRIMEQUEST 2800E/2800B *2 IOU PRIMEQUEST 2400E/2800E/2800B *3 MMB PRIMEQUEST 2400E/2800E PRIMEQUEST 2800B *4 PCI_Box PRIMEQUEST 2400E/2800E PRIMEQUEST 2800B 2.2 Maximum 2 units can be mounted Maximum 4 units can be mounted Maximum 4 units of IOU_1GbE or IOU_10GbE can be mounted.
CHAPTER 2 Connected Information 2.2 Connection of signal cable External interface connection (PRIMEQUEST 2400E in base cabinet) External interface connection figure of PRIMEQUEST 2400E in base cabinet is shown in the section below. The figure below is uncovered front surface (face). The front cover must be attached in normal operation. FIGURE 2.2 External interface connection figure of (PRIMEQUEST 2400E (Front surface)) FIGURE 2.
CHAPTER 2 Connected Information 2.2 Connection of signal cable External interface connection (PRIMEQUEST 2800E in base cabinet) External interface connection figure of PRIMEQUEST 2800E in base cabinet is shown in the section below. This figure is uncovered front surface (face). The front cover must be attached in normal operation. FIGURE 2.4 External interface connection figure of (PRIMEQUEST 2800E (Front surface)) FIGURE 2.
CHAPTER 2 Connected Information 2.2 Connection of signal cable External interface connection (PRIMEQUEST 2800B in base cabinet) External interface connection figure of PRIMEQUEST 2800B in base cabinet is shown in the section below. This figure is uncovered front surface (face). The front cover must be attached in normal operation. FIGURE 2.6 External interface connection figure of (PRIMEQUEST 2800B (Front surface)) FIGURE 2.
CHAPTER 2 Connected Information 2.2 Connection of signal cable Details of external interface (MMB) FIGURE 2.8 Details of external interface (MMB) Details of external interface (IOU_1GbE/IOU_10GbE) FIGURE 2.9 Details of external interface (IOU_1GbE) FIGURE 2.10 Details of external interface (IOU_10GbE) Details of external interface (DU) FIGURE 2.
CHAPTER 2 Connected Information 2.3 Power cable connection Details of external interface (PCI_Box) FIGURE 2.12 Details of external interface (PCI_Box) PCIC:PCI slot LNKC:LINK card 2.3 Power cable connection Input power system of PRIMEQUEST 2000series and PCI_Box is described in this section. 2.3.1 Power Supply Cable Connection (PRIMEQUEST 2400E) Input power system diagram of PRIMEQUEST 2400E is as shown below.
CHAPTER 2 Connected Information 2.3 Power cable connection 100 V Redundant Power Feed Configuration (Single power feed, Redundant Power Feed) It is necessary to arrange four PSUs, two FANUs and four power supply cables (100 V NEMA 5-15P) for 100V redundant power feed configuration (single power feed, redundant power feed). FIGURE 2.
CHAPTER 2 Connected Information 2.3 Power cable connection 200 V Redundant Power Feed Configuration (with single power feed, redundant power feed) with Power Distribution Box Connection It is necessary to arrange three PSUs, three FANUs, three Power cables (200 V IEC60320 C20) and two power distribution box (200 V IEC60320 C19×3type) for of 200 V Redundant Power Feed Configuration (single power feed, redundant power feed).
CHAPTER 2 Connected Information 2.3 Power cable connection 2.3.2 Power Cables Connections (PRIMEQUEST 2800E/2800B) This section shows the figure of input power of PRIMEQUEST 2800E/2800B. Standard Configuration of 200 V (Single power feed and no Redundant Power Feed) with Power Distribution Box Connection It is necessary to arrange three PSUs, three FANUs, three power cables (200 V IEC60320 C20) and two power distribution box (200 V IEC60320 C19×3type) for 200 V standard configuration.
CHAPTER 2 Connected Information 2.3 Power cable connection 200 V Redundant Power Feed Configuration (single power feed, redundant power feed) with Power Distribution Box Connection It is necessary to arrange four PSUs, two FANUs, four Power cables (200 V IEC60320 C20) and two power distribution boxes (200 V IEC60320 C19×3type) for 200 V Redundant Power Feed configuration (with single power feed, redundant power feed).
CHAPTER 2 Connected Information 2.3 Power cable connection 200 V Dual Power Feed Configuration with Power Distribution Box Connection It is necessary to arrange six PSUs, six power cables (200 V IEC60320 C20) and four power distribution boxes (200 V IEC60320 C19×3type) for 200 V dual power feed configuration. When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution panel. See “2.
CHAPTER 2 Connected Information 2.3 Power cable connection 100 V Redundant Power Feed Configuration (single power feed, redundant power feed) It is necessary to arrange two PSUs and two power cables (100 V NEMA 5-15P) for 100 V redundant power feed configuration (single power feed, redundant power feed). FIGURE 2.
CHAPTER 2 Connected Information 2.3 Power cable connection 200 V Redundant power feed configuration (single power feed, redundant power feed) power distribution box connection It is necessary to arrange two PSUs, two power cables (200 V IEC60320 C14) and power distribution box (200 V IEC60320 C13×4type) for 200 V redundant power feed configuration (single power feed, redundant power supply). FIGURE 2.
CHAPTER 2 Connected Information 2.4 Connection Specifications of Input Power 2.4 Connection Specifications of Input Power This section describes the connection specifications of Input power of the base cabinet or PCI_Box of PRIMEQUEST 2000 series. 2.4.1 Input Power Connection Specifications (Base Cabinet) Following table shows the input power connection specifications of the main unit. TABLE 2.
CHAPTER 2 Connected Information 2.5 Free Access Underfloor Connection of Power Cable 2.4.3 Power Distribution Box and Distribution Panel Following table shows the power supply cable specifications of power distribution box and distribution panel. TABLE 2.
CHAPTER 2 Connected Information 2.6 Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution box) Number (1) (2) (3) (4) Description Free access floor 200 mm (9.8 in) 300 mm (11.8 in) or more Recipient power distribution Remarks The above figure shows an example of 19-inch rack made by Fujitsu Limited mounted with the device. 2.
CHAPTER 2 Connected Information 2.6 Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution box) FIGURE 2.
CHAPTER 3 Notes on Carrying In and Installing the Product 3.1 Elevator Load Conditions CHAPTER 3 Notes on Carrying In and Installing the Product This chapter provides notes on carrying in and installing the PRIMEQUEST 2000 series server. 3.1 Elevator Load Conditions The rack with the device mounted is wider than the average computer. Therefore, to use an elevator to carry in the rack, the rack may need the side boards or doors removed before loading on the elevator.
Appendix A Racks A.1 Rack Mounting Appendix A Racks This appendix provides various information on the mounting racks for the PRIMEQUEST 2000 series and PCI_Box. A.1 Rack Mounting The PRIMEQUEST 2000 series (including peripheral devices) has been developed and its operation guaranteed with the basic assumption that it is mounted in a Fujitsu rack. For safe use of a unit mounted in a Fujitsu rack, contact the distributor where you purchased your product, or your sales representative.
Appendix A Racks A.2 Rack Mounting Requirements Rack mounting requirements The following table lists the requirements for mounting in one rack. Number of mountable units Model Mounting area The bottom of the mounted device must not be below 1U. (*1) PRIMEQUEST 2000 series 3 The top of the mounted device must not be above 1,066 mm from floor. (*2).
Appendix A Racks A.2 Rack Mounting Requirements A.2.2 Requirements for mounting in a third party's rack When mounting the PRIMEQUEST products in a rack manufactured by another company, customers need to confirm on their own responsibility that the rack meets the PRIMEQUEST product specifications and requirements. Note Fujitsu does not guarantee there will be no problems arising from the mounting of the PRIMEQUEST 2000 series server (including peripheral devices) in a rack manufactured by another company.
Appendix A Racks A.2 Rack Mounting Requirements FIGURE A.2 Length of rack Number (1) (2) (3) (4) Description Front cover Front post Rear post Rear cover Width of rack FIGURE A.
Appendix A Racks A.2 Rack Mounting Requirements Format of rack posts FIGURE A.4 Format of rack posts Other conditions Besides structural conditions, the following conditions must also be considered. - Cooling of devices mounted in the rack Install the rack such that the temperature inside the rack satisfies the temperature conditions in “1.3 Installation Specifications”.