Note -
In the case of a dual power feed, connect the power cords in their original positions by
referring to the record that you made before the start of maintenance.
Note -
In the case of a dual power feed, connect the power cords in their original positions by
referring to the record that you made before the start of maintenance.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
2.
Power on the physical partition requiring maintenance.
For details, see "6.3 Powering On the Physical Partition Requiring Maintenance."
3.
Close the rack door.
27.6.4 Inactive/Cold maintenance
1.
Connect all the power cords to the PSU backplane unit or power supply unit
of the chassis requiring maintenance.
For details, see "6.5.1 Installing the power cord."
2.
Return to the operation of the XSCF firmware replacefru command to confirm
that the XSCF DUAL control cable has been incorporated into the system.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
3.
Power on the physical partition requiring maintenance.
For details, see "6.3 Powering On the Physical Partition Requiring Maintenance."
4.
Close the rack door.
27.6.5 System-stopped maintenance
1.
Connect all the power cords to the PSU backplane unit or power supply unit
of the chassis requiring maintenance.
For details, see "6.5.1 Installing the power cord."
2.
Return to the operation of the XSCF firmware replacefru command to confirm
that the XSCF DUAL control cable has been incorporated into the system.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
3.
Power on all the physical partitions.
For details, see "6.3 Powering On the Physical Partition Requiring Maintenance."
4.
Close the rack door.
Chapter 27 Maintaining the XSCF DUAL Control Cables 423