Server User Manual
Note -
Check that the XSCF BB control cables are correctly connected and secure.
Note -
After connecting the XSCF BB control cable, use the hook-and-loop fastener to bundle
the cables together and secure them to the rear cable support.
XSCF>
switchscf -t Active
Note -
In the case of a dual power feed, connect the power cords in their original positions by
referring to the record that you made before the start of maintenance.
26.6 Restoring the System
This section describes the procedure for restoring the system after installing the XSCF
BB control cables. The restoration procedure differs depending on the maintenance
type as follows:
■
Active/Hot maintenance
■
Active/Cold maintenance
■
Inactive/Hot maintenance
■
Inactive/Cold maintenance
■
System-stopped maintenance
26.6.1 Active/Hot maintenance
1.
Return to the operation of the XSCF firmware replacefru command to confirm
that the chassis has been incorporated into the system.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
2.
Execute the switchscf command to switch the standby XSCF to the master
XSCF.
Execute the command if the chassis requiring maintenance has been switched to
the standby XSCF.
3.
Close the rack door.
26.6.2 Active/Cold maintenance
1.
Connect all the power cords to the PSU backplane unit or power supply unit
of the chassis requiring maintenance.
For details, see "6.5.1 Installing the power cord."