Server User Manual

XSCF>
showlogs error
XSCF>
replacefru
Note -
Inthecaseofadualpowerfeed,makeanoteofthelocationsofthepowercords
before disconnecting them to ensure that they are reinstalled correctly.
Caution -
Before you handle any components, wear a wrist strap to ground any static
electricity. If you perform this procedure without a wrist strap, individual
components or the overall system may be damaged. For details, see "1.5 Notes
Regarding Static Electricity."
maintenance.
For details, see "3.3.5 Checking log information."
4.
Confirm the hardware and software configurations.
For details, see "4.2 Confirming the System Configuration."
5.
Power off all the physical partitions.
For details, see "5.3 Powering Off the Physical Partition Requiring Maintenance."
6.
Execute the replacefru command to release the chassis requiring maintenance
from the system.
For details, see "5.1 Releasing an FRU from the System with the replacefru
Command."
7.
Remove all the power cords from the PSU backplane unit or power supply
unit of the chassis requiring maintenance.
For details, see "5.5.2 Removing the power cord."
26.4 Removing an XSCF BB Control Cable
This section describes the procedure for removing the XSCF BB control cables.
Enable removal of the XSCF BB control cables before attempting to remove them. For
details, see "26.3 Enabling the Removal of an XSCF BB Control Cable."
1.
Remove the XSCF BB control cable from the SPARC M10-4S or the crossbar
box.
Pull out an XSCF BB control cable while pushing the lock release buttons (A in
the figure) on the both sides of the cable.
Chapter 26 Maintaining the XSCF BB Control C ables 407