Server User Manual

Caution -
To completely shut down the system, all the power cords must be
removed. If the power cords are not removed, an electrical failure may occur.
XSCF>
showlogs error
XSCF>
replacefru
24.2.3 Precautions for replacement
Note the following points when replacing a crossbar cable (electrical):
Replace crossbar cables (electrical) in pairs.
24.3 Enabling the Removal of a Crossbar
Cable (Electrical)
This section describes the preparations that must be completed prior to removing the
crossbar cables (electrical). The preparation procedure differs depending on the
maintenance type as follows:
Inactive/Cold maintenance
System-stopped maintenance
24.3.1 Inactive/Cold maintenance
1.
Open the rack door.
2.
Log in to the XSCF shell.
3.
Execute the showlogs command to identify the component requiring
maintenance.
For details, see "3.3.5 Checking log information."
4.
Confirm the hardware and software configurations.
For details, see "4.2 Confirming the System Configuration."
5.
Pow er off the physical partition requiring maintenance.
For details, see "5.3 Powering Off the Physical Partition Requiring Maintenance."
6.
Execute the replacefru command to release the chassis requiring maintenance
from the system.
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual
December 2013382