Caution -
To completely shut down the system, all the power cords must be
removed. If the power cords are not removed, an electrical failure may occur.
XSCF>
showlogs error
XSCF>
replacefru
XSCF>
showlogs error
fan unit. The preparation procedure differs depending on the maintenance type as
follows:
Active/Hot maintenance
Inactive/Hot maintenance
System-stopped maintenance
19.3.1 Active/Hot maintenance
1.
Open the rack door.
2.
Log in to the XSCF shell.
3.
Execute the showlogs command to identify the component requiring
maintenance.
For details, see "3.3.5 Checking log information."
4.
Confirm the hardware and software configurations.
For details, see "4.2 Confirming the System Configuration."
5.
Execute the replacefru command to release the fan unit requiring maintenance
from the system.
For details, see "5.1 Releasing an FRU from the System with the replacefru
Command."
19.3.2 Inactive/Hot maintenance
1.
Open the rack door.
2.
Log in to the XSCF shell.
3.
Execute the showlogs command to identify the component requiring
maintenance.
For details, see "3.3.5 Checking log information."
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual