Server User Manual
Note -
Check that the power supply unit is fully inserted and that the lever is fixed.
XSCF>
showstatus
XSCF>
showhardconf
18.6 Restoring the System
This section describes the procedure for restoring the system after installing a power
supply unit. The restoration procedure differs depending on the maintenance type as
follows:
■
Active/Hot maintenance
■
Inactive/Hot maintenance
■
System-stopped maintenance
18.6.1 Active/Hot maintenance
1.
Connect the power cords to the power supply unit requiring maintenance.
For details, see "6.5.1 Installing the power cord."
2.
Confirm that the LED (green) of the power supply unit is on.
3.
Return to the operation of the XSCF firmware replacefru command to confirm
that the power supply unit has been incorporated into the system.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
4.
Execute the showstatus command to confirm that the power supply unit is
operating normally after the completion of maintenance.
5.
Execute the showhardconf command to check the hardware configuration
and the status of each component.
6.
Close the rack door.
18.6.2 Inactive/Hot maintenance
1.
Connect the power cords to the power supply unit requiring maintenance.
For details, see "6.5.1 Installing the power cord."
2.
Confirm that the LED (green) of the power supply unit is on.
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual
・
December 2013324