Server User Manual

Caution -
To completely shut down the system, all the power cords must be
removed. If the power cords are not removed, an electrical failure may occur.
Note -
Active/hot maintenance is supported only for a redundant configuration.
XSCF>
showlogs error
XSCF>
replacefru
of a power supply unit. The preparation procedure differs depending on the
maintenance type as follows:
Active/Hot maintenance
Inactive/Hot maintenance
System-stopped maintenance
18.3.1 Active/Hot maintenance
1.
Open the rack door.
2.
Log in to the XSCF shell.
3.
Execute the showlogs command to identify the component requiring
maintenance.
For details, see "3.3.5 Checking log information."
4.
Confirm the hardware and software configurations.
For details, see "4.2 Confirming the System Configuration."
5.
Execute the replacefru command to release the power supply unit requiring
maintenance from the system.
For details, see "5.1 Releasing an FRU from the System with the replacefru
Command."
6.
Remove the pow er cord from the power supply unit requiring maintenance.
For details, see "5.5.2 Removing the power cord."
18.3.2 Inactive/Hot maintenance
1.
Open the rack door.
2.
Log in to the XSCF shell.
3.
Execute the showlogs command to identify the component requiring
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual
December 2013320