Server User Manual
Note -
Reinstall the cables in their original positions by referring to the notes that you made
prior to the start of maintenance.
Note -
After connecting the cables, use the hook-and-loop fastener to bundle and fix the
cables to the cable support at the rear.
XSCF>
switchscf -t Active
Thecablestobereconnectedareasfollows.
■
Serial cable
■
LAN cable
■
USB device
17.6 Restoring the System
This section describes the procedure for restoring the system after installing the XSCF
unit. The restoration procedure differs depending on the maintenance type as follows:
■
Active/Hot maintenance
■
Inactive/Hot maintenance
■
System-stopped maintenance
17.6.1 Active/Hot maintenance
1.
Check that the XSCF STANDBY LED on the operation panel is on.
For the location of LEDs, see "2.3.3 LEDs on each component."
2.
Return to the operation of the XSCF firmware replacefru command to confirm
that the XSCF unit has been incorporated into the system.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
3.
Execute the switchscf command to switch the standby XSCF to the master
XSCF.
Execute the command if the chassis requiring maintenance has been switched to
the standby XSCF.
4.
Close the rack door.
17.6.2 Inactive/Hot maintenance
1.
Return to the operation of the XSCF firmware replacefru command to confirm
Chapter 17 Maintaining the XSCF Unit of the Crossbar Box 315