Server User Manual
Note -
Reconnect the cables of the external interface in their original positions by referring to
the notes that you made prior to the start of maintenance.
Note -
See the procedure for system-stopped maintenance for inactive/cold maintenance in a
single-chassis configuration.
Note -
Use the DR of the system board on a physical partition for active/cold maintenance.
For the XCP and Oracle VM Server for SPARC/SRU versions that correspond to the DR, see
the latest Product Notes.
Note -
Active/cold maintenance can be performed only for a building block configuration.
Note -
In the case of a dual power feed, connect the power cords in their original positions by
referring to the record that you made before the start of maintenance.
■
LAN cable
13.
Lift the cable support to fix it.
For details, see "6.5.2 Fixing the cable support."
15.6 Restoring the System
This section describes the procedure for restoring the system after installing the
operation panel. The restoration procedure differs depending on the maintenance
type as follows:
■
Active/Cold maintenance
■
Inactive/Cold maintenance
■
System-stopped maintenance
15.6.1 Active/Cold maintenance
1.
Connect all the power cords to the PSU backplane unit of the chassis
requiring maintenance.
For details, see "6.5.1 Installing the power cord."
2.
Return to the operation of the XSCF firmware replacefru command to confirm
that the chassis has been incorporated into the system.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
3.
Execute the diagxbu command to diagnose the crossbar cables.
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual
・
December 2013292