Server User Manual

Note -
See the procedure for system-stopped maintenance for inactive/cold maintenance in a
single-chassis configuration.
Caution -
To completely shut down the system, all the power cords must be
removed. If the power cords are not removed, an electrical failure may occur.
XSCF>
showlogs error
XSCF>
replacefru
11.3 Enabling the Removal of a Fan Unit
This section describes the preparations that must be completed prior to removing a
fan unit. The preparation procedure differs depending on the maintenance type as
follows:
Active/Hot maintenance
Active/Cold maintenance
Inactive/Hot maintenance
Inactive/Cold maintenance
System-stopped maintenance
11.3.1 Active/Hot maintenance
1.
Open the rack door.
2.
Log in to the XSCF shell.
3.
Execute the showlogs command to identify the component requiring
maintenance.
For details, see "3.3.5 Checking log information."
4.
Confirm the hardware and software configurations.
For details, see "4.2 Confirming the System Configuration."
5.
Execute the replacefru command to release the fan unit requiring maintenance
from the system.
For details, see "5.1 Releasing an FRU from the System with the replacefru
Command."
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual
December 2013208