Server User Manual

XSCF>
showlogs error
XSCF>
replacefru
Note -
In the case of a dual power feed, make a note of the locations of the power cords
before disconnecting them to ensure that they are reinstalled correctly.
10.3.5 System-stopped maintenance
1.
Open the rack door.
2.
Log in to the XSCF shell.
3.
Execute the showlogs command to identify the component requiring
maintenance.
For details, see "3.3.5 Checking log information."
4.
Confirm the hardware and software configurations.
For details, see "4.2 Confirming the System Configuration."
5.
Stop the entire system.
For details, see "5.4 Stopping the Entire System."
6.
Execute the replacefru command to release the chassis requiring maintenance
from the system.
For a single-chassis configuration, you do not have to release the chassis.
Proceed to step 7.
For details, see "5.1 Releasing an FRU from the System with the replacefru
Command."
7.
Remove all the power cords from the PSU backplane unit of the chassis
requiring maintenance.
For details, see "5.5.2 Removing the power cord."
10.4 Removing a Power Supply Unit
This section describes the procedure for removing a power supply unit. Enable the
removal of the power supply unit before attempting to remove it. For details, see
"10.3 Enabling the Removal of a Power Supply Unit."
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual
December 2013198