Server User Manual
Note -
See the procedure for system-stopped maintenance for inactive/cold maintenance in a
single-chassis configuration.
Caution -
To completely shut down the system, all the power cords must be
removed. If the power cords are not removed, an electrical failure may occur.
Note -
Active/hot maintenance is supported only for a redundant configuration.
XSCF>
showlogs error
XSCF>
replacefru
10.3 Enabling the Removal of a Power
Supply Unit
This section describes the preparations that must be completed prior to the removal
of a power supply unit. The preparation procedure differs depending on the
maintenance type as follows:
■
Active/Hot maintenance
■
Active/Cold maintenance
■
Inactive/Hot maintenance
■
Inactive/Cold maintenance
■
System-stopped maintenance
10.3.1 Active/Hot maintenance
1.
Open the rack door.
2.
Log in to the XSCF shell.
3.
Execute the showlogs command to identify the component requiring
maintenance.
For details, see "3.3.5 Checking log information."
4.
Confirm the hardware and software configurations.
For details, see "4.2 Confirming the System Configuration."
5.
Execute the replacefru command to release the power supply unit requiring
maintenance from the system.
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual
・