Server User Manual

XSCF>
showstatus
XSCF>
showhardconf
Note -
In the case of a dual power feed, connect the power cords in their original positions by
referring to the record that you made before the start of maintenance.
Switch the mode switches of BB-ID#00 and #01 to Locked mode.
-
For a building block configuration (with crossbar box)
Switch the mode switches of BB-ID#80 and #81 to Locked mode.
12.
Execute the showstatus command to confirm that the CPU memory unit is
operating normally after maintenance.
If there is no problem, nothing is displayed.
13.
Execute the showhardconf command to check the hardware configuration
and the status of each component.
Confirm that no asterisk (*) is displayed in front of each component.
14.
Close the rack door.
7.6.3 System-stopped maintenance
When the system is configured without a hardware RAID
1.
Connect all the power cords to the PSU backplane unit of the chassis
requiring maintenance.
For details, see "6.5.1 Installing the power cord."
2.
Return to the operation of the XSCF firmware replacefru command to confirm
that the chassis has been incorporated into the system.
For details, see "6.1 Incorporating an FRU into the System with the replacefru
Command."
For a single-chassis configuration, you do not have to incorporate the chassis.
Proceed to step 4.
3.
Execute the diagxbu command to diagnose the crossbar cables.
Diagnosis is performed when the system board of the chassis connected with the
crossbar cables is not incorporated into the physical partition, or when the
physical partition into which the chassis is incorporated is powered off.
The example below specifies the following:
00: BB-ID of the chassis to start the diagnosis
01: BB-ID of the destination where the chassis to start the diagnosis is connected
Fujitsu M10-4/Fujitsu M10-4S/SPARC M 10-4/SPARC M10-4S Service Manual
December 2013152