ETERNUS DX60/DX80/DX90 Disk storage system User Guide
86
Copyright 2010 FUJITSU LIMITED
P3AM-3042-06ENZ0
Chapter 5 Installation
This chapter describes the ETERNUS DX60/DX80/DX90 installation procedure.
Before installing the device, make sure to check the "ETERNUS DX60/DX80/DX90 Disk storage
system Safety Precautions".
5.1 Installation Preparation
5.1.1 Placement Area
Installation area
Refer to the placement area of the rack to install the device.
Installation condition
Refer to "Instructions for installation" in "ETERNUS DX60/DX80/DX90 Disk storage system
Safety Precautions" and set the device in a location where all the requirements are satisfied.
Air conditioning
The inside of the ETERNUS DX60/DX80/DX90 is cooled down by taking air through the front
side and blowing it out the back. Place other devices so that the front of the ETERNUS DX60/
DX80/DX90 is not exposed to their exhaust air.
Refer
"ETERNUS DX60/DX80/DX90 Disk storage system Safety
Precautions"
MPORTAN
The speed of the ETERNUS DX60/DX80/DX90 fans is stepped up and
down in response to the ambient temperature.
When the ambient temperature reaches a high level, the fan will rotate at a
higher speed, which will increase the noise level. Up to 25°C the noise level
should not exceed about 43.5dB, but higher temperatures or abnormal fan
situations can result in noise levels over 43.5dB, and seclusion in a
dedicated server room is generally recommended.