30LPAS1 Technical Manual
Table Of Contents
- DESIGN & TECHNICAL MANUAL
- Part 1. INDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Wiring diagrams
- 4. Capacity table
- 5. Fan performance
- 6. Operation noise (sound pressure)
- 7. Safety devices
- 8. External input and output
- 9. Group connection
- 10. Remote controller
- 11. Function settings
- 12. Accessories
- 13. Optional parts
- Part 2. OUTDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Installation space
- 4. Refrigerant circuit
- 5. Wiring diagrams
- 6. Capacity compensation rate for pipe length and height difference
- 7. Additional charge calculation
- 8. Airflow
- 9. Operation noise (sound pressure)
- 10. Electrical characteristics
- 11. Safety devices
- 12. External input and output
- 13. Function settings
- 14. Accessories
- 15. Optional parts
- Part 1. INDOOR UNIT
7. Additional charge calculation
7-1. Models: AOUH30LPAS1 and AOUH36LPAS1
Refrigerant type R410A
Factory charge amount
lb oz 4 lb 10 oz
g 2,100
ยข Refrigerant charge
Total pipe length
ft 65 or less 99 131 165 (Max.)
0.43 oz/ft
(40 g/m)
m 20 or less 30 40 50 (Max.)
Additional charge
lb oz 0 14 oz 1 lb 12 oz 2 lb 10 oz
g 0 400 800 1,200
- 71 -
7-1. Models: AOUH30LPAS1 and AOUH36LPAS1
7. Additional charge calculation
OUTDOOR UNIT
AOUH30-36LPAS1
OUTDOOR UNIT
AOUH30-36LPAS1