30LPAS1 Technical Manual
Table Of Contents
- DESIGN & TECHNICAL MANUAL
- Part 1. INDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Wiring diagrams
- 4. Capacity table
- 5. Fan performance
- 6. Operation noise (sound pressure)
- 7. Safety devices
- 8. External input and output
- 9. Group connection
- 10. Remote controller
- 11. Function settings
- 12. Accessories
- 13. Optional parts
- Part 2. OUTDOOR UNIT
- 1. Specifications
- 2. Dimensions
- 3. Installation space
- 4. Refrigerant circuit
- 5. Wiring diagrams
- 6. Capacity compensation rate for pipe length and height difference
- 7. Additional charge calculation
- 8. Airflow
- 9. Operation noise (sound pressure)
- 10. Electrical characteristics
- 11. Safety devices
- 12. External input and output
- 13. Function settings
- 14. Accessories
- 15. Optional parts
- Part 1. INDOOR UNIT
13) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to “External heater output” in Chapter 8-4. "Details of function" on page 21.
Function number Setting value Setting description Factory setting
66
00 -4.0 °F (-20 °C) ♦
01 -0.4 °F (-18 °C)
02 3.2 °F (-16 °C)
03 6.8 °F (-14 °C)
04 10.4 °F (-12 °C)
05 14.0°F (-10 °C)
06 17.6 °F (-8 °C)
07 21.2 °F (-6 °C)
08 24.8 °F (-4 °C)
14) Outdoor temperature zone boundary temperature B
Setting required if changing of the outdoor temperature setting for heat pump only zone is required
when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit. For details,
refer to “External heater output” in Chapter 8-4. "Details of function" on page 21.
Function number Setting value Setting description Factory setting
67
00 42.8 °F (6 °C) ♦
01 14.0 °F (-10 °C)
02 17.6 °F (-8 °C)
03 21.2 °F (-6 °C)
04 24.8 °F (-4 °C)
05 28.4°F (-2 °C)
06 32.0 °F (0 °C)
07 35.6 °F (2 °C)
08 39.2 °F (4 °C)
09 42.8 °F (6 °C)
10 46.4 °F (8 °C)
11 50.0 °F (10 °C)
12 53.6 °F (12 °C)
13 57.2 °F (14 °C)
14 60.8 °F (16 °C)
15 64.4 °F (18 °C)
15) Standby time for auxiliary equipment operation
Sets the standby time until the auxiliary equipment operation starts during primary equipment opera-
tion.
For details, refer to Chapter 8-4. "Details of function" on page 21.
Function number Setting value Setting description Factory setting
71
00 Disable ♦
01 1 minute
02 2 minutes
• •
• •
• •
98 98 minutes
99 99 minutes
- 54 -
11-1. Function settings by using remote controller
11. Function settings
WALL MOUNTED
ASUH30-36LPAS
WALL MOUNTED
ASUH30-36LPAS