Specifications Sheet

Page 4 / 4 AH_PIS_ ASTG30KMTA
Specifications
Electrical
Power Requirement 240V – 1Ph – 50Hz Outdoor
Fuse Or Circuit Breaker (A) 32 Min Power Cable (mm²) 4.0
Interconnecting Cables 3+E
Compressor
Type Hermetic × 1
Motor (W) 2200
Indoor Coil Outdoor Coil
Type
Copper Tube + Aluminium Fin
Type
Copper Tube + Aluminium Fin
Rows / Stages
Main: 3 × 28, Sub1: 1 × 6,
Sub2: 1 × 4
Rows / Stages
2 x 38
Fin Pitch (mm)
Main: 1.2, Sub: 1.4
Fin Pitch (mm)
1.3
Coating
Hydrophilic Coating
Coating
Blue Fin
Indoor Fan And Motor Outdoor Fan And Motor
Fan Type
Cross flow fan × 1
Fan Type
Propeller fan × 1
Motor (W)
80
Motor (W)
100
Refrigeration System
Refrigerant Type R32
Charge g 1650
Maximum Line Length / Height m 50 / 30
Pre-Charged Length m 20
Additional Charge g/m 45
Connection Method Flared
Expansion Control Electronic Expansion Valve
Safety Devices
T
ype
of p
r
otection
Protection form
Circuit protection
Current fuse (Near the terminal) 250 V, 25 A
Current fuse (Filter PCB) 250 V, 10 A
Current fuse (Main PCB) 250 V, 3.15 A
Fan motor protection
Thermal protection
Activate
150±15
°C
- Fan motor
stop
Reset
120±15
°C -
Fan motor
restart
Compressor protection
Terminal protection program
(Compressor temp.)
Activate
120
°C
- Compressor
stop
Reset
80
°C -
Compressor
restart
Thermal protection program
(Discharge temp.)
Activate
110°C -
Compressor
stop
Reset
After 7
minutes,
Compressor
restart
High pressure protection
Pressure switch
Activate
4.2±0.1
MPa
- Compressor
stop
Reset
3.2±0.15
MPa,
Compressor
restart
Low pressure protection
Pressure sensor
Activate
0.12
MPa
, Compressor
stop
Reset
0.15
MPa
, Compressor
restart
* Specifications and design are subject to change without notice. Please check with your dealer.