Instruction Manual FCX-CII SERIES TRANSMITTERS Differentiel pressure Transmitter (FKK ...4) Pressure Transmitter (FKP...4) Pressure Transmitter with remote seal (FKP...E) Absolute Pressure Transmitter (FKH...E) Fuji Electric France S.A.
INTRODUCTION INTRODUCTION Thank you very much for your purchase of the Fuji FCX-CII Series Transmitter. This instruction manual covers the FCX-CII series transmitter and contains information about the installation, piping, wiring, operation and maintenance of the FCX-CII series (FKK...4 • FKP...4 • FKP...E). • First read this instruction manual carefully until an adequate understanding is required, and then proceed to installation, operation and maintenance of the FCX-CII Series transmitter.
CAUTION ON SAFETY First of all, read this “Caution on Safety” to ensure correct operation of the transmitter. • The cautionary descriptions listed here contain important information about safety, so they should be observed without fail. Those safety precautions are classified into ranks “DANGER” and “CAUTION”. DANGER Wrong handling may cause a dangerous situation, in which there is a risk of death or heavy injury.
Wiring DANGER • On explosion-proof type transmitter, its wiring work must be performed according to the required laws and regulations. Incorrect wiring may cause explosion, fire or other serious accidents. CAUTION • Before making wiring work, be sure to turn OFF the main power to prevent electric shocks. • Use wiring materials of correct rating to prevent fire accidents. • Connect a power source of correct rating to prevent fire accidents.
CAUTION ON USE Be sure to observe the following Instructions Storage for a long period Store the transmitter in a dry room at normal temperature and humidity. Keep protection caps in place at the conduit connection and process connection. For installation, select an appropriate place Site at location with minimal vibration, dust and corrosive gas At a place allowing an adequate space for checkup Site at location large enough to allow maintenance and checking.
CONTENTS INTRODUCTION ................................................................................................................................. i CAUTION ON SAFETY ...................................................................................................................... ii CAUTION ON USE ............................................................................................................................. iv CONFIRMATION OF YOUR SPECIFICATION .......................................
1 OUTLINE The FCX-CII series transmitter detects the differential pressure or pressure of various fluids, converts it into a current signal of 4 to 20 mA DC and transmits it. All the adjustment functions are incorporated in the transmission unit for making adjustments easily and exactly. Transmitter settings (such as range and damping time constant, etc.) can be changed from an HHC (Hand Held Communicator).
2 OPERATING PARTS AND THEIR FUNCTIONS FCX-CII Series transmitter Transmission unit Process connection Detecting unit Analog indicator connector Transmission unit Digital indicator connector Vent/drain plug Conduit connection Terminal unit Indicator (Digital) (Analog) CK+ OUT DISP FIX % ZERO abs 0 CK– Terminal unit Zero/span adjustment screw % 10 20 40 60 80 0 – + Description of FCX-CII Series transmitter Part name Description Detecting unit Detects pressure, differential pressure
Mode indicating function of digital indicator OUT DISP % FIX ZERO abs Mode indication Mode % When not indicated When indicated % output Actual scale External zero adjustment possible External zero adjustment impossible DISP Digital indicator Digital indicator proportional display OUT output ZERO FIX display Proportional output Measurement mode Fixed current mode Sampling status (Flicker) abs – N Absolute pressure Gage pressure Output value < Zero Output value (a part of unit indica
3 OPERATION AND SHUTDOWN 3.1 Preparation for operation Before operating the transmitter, be sure to perform the following checks and procedures. Note that adjustment is required in a non-hazardous area for zero point check of intrinsically safe explosionproof and flameproof transmitters, do not open terminal cover and do not use HHC. Use the transmitter indicator and the external adjustment screw. Preparation procedure (1) Check for liquid or gas leakagefrom the process connection, etc.
Zero point check Turn on the power to the transmitter. Check the output signal of the transmitter by connecting a DC ammeter across CK+ and CK– of the terminal block. After ten minutes or longer, adjust the transmitter output current to 4 mA (zero adjustment). (See below.) (1) Zero adjustment Zero point of the transmitter is adjustable by the zero screw on the electronics housing with the zero adjustment screw.
3.2 Operation (1) Operation of pressure transmitter Open the valve slowly to apply a pressure. When a pressure is applied, the transmitter is set in the operating status. Open (2) Operation of differential pressure transmitter Set the operating status by manipulating the manifold valve. Stop valve on the low pressure side Make sure the equalizing valve is open. Open Equalizing valve Stop valve on the high pressure side Open the stop valve on the high pressure side slowly.
Open Finally, open the stop valve on the low pressure side slowly. Check of operating status Use a field indicator, receiving instrument or HHC to check the operating status. 3.3 Shutdown (1) Shutdown of pressure transmitter Close the valve slowly to stop applying a pressure. The transmitter is set in the measurement stop status.
(2) Shutdown of differential pressure transmitter Set the shutdown status by manipulating the manifold valve. Turn off power supply. Close the stop valve on the high pressure side (H side) slowly. Close Open Open the equalizing valve. Close Close the stop valve on the low pressure side (L side) slowly. Important Before a long shutdown, discharge the process fluid and drain completely from the transmitter. This is to protect the transmitter from freezing, corrosion, etc.
4 ADJUSTMENT OF SMART TYPE To operate the FCX-CII series transmitter, the HHC is used for each adjustment. 4.1 Adjustment with HHC Startup and usage of the Hand Held Communicator (HHC) are detailed in the instruction manual for HHC. Please refer to this manual before commencing adjustment. Important After adjustment of the transmitter, it should be kept energized for about 10 seconds to write the adjustment results into memory. 4.1.
4.1.2 Outline of HHC operation The following shows the flow of the key, explained for FXW Version 6.0 (FXW 1- A3). FXW prior to Version 6.0 are not available of operation of FCX-CII series transmitter. In this case, the user is requested to contract our office for ROM version up. Classification Display symbol Key symbol Referential page MENU 11 1 TAG No. INC 1: TAG No 2 Type INC 2: TYPE 3 Display of serial No. INC 3: SERIAL No.
4.1.3 Operating procedure In case of a flameproof transmitter, never connect the HHC to the terminal block of transmitter in hazardous area installations. TAG N°.
TYPE Menu 1 : TAG N° INC • 2: TYPE FKCXXXXX-XXXXX CHNG < INC > < CHANGE > 1 INC 2-1: TYPE CHANGE FKCXXXXX-XXXXX < ENT > < CL > ENT CL 2-1: TYPE CHANGE FKCXXXXX-XXXXX CHNG OK?< ENT/CL > after setting ENT To Menu 3 : SERIAL N° • 2 CL 3 • 2-2: TYPE WRITE FKCXXXXX-XXXXX 4 • • • Type of field device is displayed and changed (ex. of differential pressure transmitter). After TAG N°. is displayed, press the key to display TYPE image.
Industrial value unit Available unit for FCX-C2 Menu N°3 : SERIAL N° mmH2 O cmH 2 O mH 2 O g/cm 2 kg/cm2 Pa hPa kPa MPa mbar bar psi inH 2 O ftH 2 O mmAq cmAq mAq mmWC cmWC mWC mmHg cmHg mHg inHg < Torr > < atm > INC 4: UNIT kPa < INC > INC < CHNG > 1 CHNG 4-1: UNIT CHANGE kPa (NEXT MPa) < INC > < ENT > < CL > 2 CL INC ENT < UNIT CHANG > 4-1: UNIT CHANGE kPa (NEXT MPa) CHNG OK? < ENT/CL > 3 CL ENT 4-1: UNIT WRITE kPa 4 INC Not suitable unit display To menu N° 5 : RANGE LIMIT 4-1: UNIT WRITE Pa NOT
Range limit Menu N°4 : UNIT Indicates the maximum measuring range of this transmitter. INC 5: RANGE LIMIT × × × kPa Range change (LRV, URV) < INC > INC CHNG 6: RANGE LRV ±× × × . × kPa URV ±× × × . × kPa < INC > < CHANGE > 1 INC 6-1: RANGE CHANGE LRV ±× × × . × kPa URV ±× × × . × kPa < LRV > < URV > < CL > LRV CL 6-2: RANGE CHANGE LRV ±× × × . × kPa URV ±× × × . × kPa < LRV > < URV > < CL > CL 2 3 URV CL 6-2: RANGE CHANGE LRV ±× × × . × kPa URV ±× × × .
Damping adjustment When process input changes excessively, an appropriate damping time constant should be set. Menu N°6 : RANGE CHNG 7: DAMPING 0.3SEC 7-1: < INC > < CHANGE > INC DAMP CHANGE 0.3SEC < ENT > < CL > 1 CL after setting 2 CL Input time constant value under display 2 , time constant can be changed. ENT 7-1: DAMP CHANGE 1.2SEC CHNG OK? < ENT/CL > 3 ENT 7-2: DAMP WRITE 1.
Output mode LIN/ (a) D (DP) 8: 8 OUTPUT MODE XMTR:DP OUT=LIN < INC > < CHANGE > CHNG INC 8-1: MODE CHANGE XMTR : DP OUT=LIN < INC > < ENT > < CL > 1 8-1: MODE CHANGE XMTR : GP OUT=LIN < ENT > < CL > 2 ENT CL *1
Burnout direction CHNG 9:BURNOUT NOT USED (HOLD) < INC > < CHANGE > 9-1: BURNOUT < 1 > NOT USED < 2 > OVER SCALE < 3 > UNDER SCALE 2 1 INC 1 or 2 or 3 Selection of burnout direction (ex) 3 9-2: BURNOUT CHANGE UNDER SCALE < ENT > < CL > A : CALIBRATE CL 3 CL ENT 9-2: BURNOUT CHANGE UNDER SCALE CHNG OK? < ENT/CL > ENT CL 9-5: BURNOUT Saturate Current 3.8-20.8mA < CL > CL 6 4 9-4: BURNOUT UNDER SCALE Y.YmA < CHANGE > < CL > 5 CHNG CL 9-5: BURNOUT CHNG UNDER SCALE Y.
Zero/span adjustment LRV < Zero adjustment > A: CALIBRATE A-1: < INC > < LRV > < URV > 1 INC CALIBRATE LRV ×××.××% ×××.× kPa < ENT > < CL > Zero and span are adjustable by applying an actual pressure. When pressing under display 1 the screen for zero adjustment 2 appears, and that for span adjustment 5 appears when pressing . Under display 2 , after applying actual pressure equal to zero point, press two times. Zero adjustment will be over.
Calibration of output circuit (D/A) G OUT B: The output circuit (D/A) should be calibrated by the following procedure when necessary. OUTPUT ADJ < INC > < CHANGE > CHNG INC B-1: OUTPUT SET 0mA < LRV/URV/ENT/CL > LRV 1 URV ENT B-1: OUTPUT SET 4.000mA CL (Input of XX.XXXmA at 1 ) B-1: OUTPUT SET 20.000mA B-1: OUTPUT SET XX.XXXmA CHANGE OK? < ENT/CL > CHANGE OK? < ENT/CL > CHANGE OK? < ENT/CL > 2 ENT CL 7 ENT CL 8 CL ENT (OTHERS) < OTHERS > (4 , 20mA) B-2: OUTPUT MODE XX.
Indication of measured data B DATA C: C-1: DATA < INC > < ENT > INC DATA XXX. X %FLOW XXXXX kPa < CHANGE > < CL > CHNG ENT : "FLOW" is displayed when output mode is square root extraction mode. : " flicker" is displayed when the communication between transmitter and HHC is normal. The measured value can be indicated. For more information about operating procedure, refer to the instruction manual of HHC. CL C-1: DATA XXX.
[Contents of message] As a result of self-diagnosis, the message below is appeared on the LCD display of HHC, when there are trouble in the transmitter. For each error, its cause and remedy are suggested. Indication on digital indicator Message Cause Remedy CELL FAULT (C1) Replacement of detecting unit FL-1 Error of detecting unit EEPROM (AMP) FLT FL-2 EEPROM error on amplifier side Replacement of amplifier EEPROM (CELL) FLT FL-3 EEPROM error on cell side CELL FAULT (C9)(*1) TEMP. ALARM T.
Lock of adjustment function CHNG F: XMTR EXT. SW F-1: ENABLE < INC > < CHANGE > INC 1 XMTR EXT. SW < 1 > INHIBIT < 2 > ENABLE < 1 > < 2 > < CL > 2 CL 1 F-2: CL XMTR EXT. SW CHANGE INHIBIT < ENT > < CL > 3 ENT F-2: XMTR EXT. SW CHANGE INHIBIT CHNG OK? < ENT/CL > ENT F-3: The zero adjustment function can be locked by the transmitter adjust screw. 4 CL XMTR EXT.
2 G : XMTR DISPLAY ±YYYYYY=XMTR DISPLAY at 4mA ±YYYYYY/±ZZZZZZ ±ZZZZZZ=XMTR DISPLAY UUUUUUU at 20mA < INC > < CHANGE > UUUUUUU=XTMR DISPLAY CHNG CHNG INC UNIT Note1) 0.00-100.00%LIN 0.0-100.0% LIN 3 G-1: DISP. CHANGE 0-100% LIN < 1 > % DISPLAY 0.00-100.00%FLOW < 2 >ACTUAL DISP. 0.0-100.0% FLOW < 1 > < 2 > < CL > 0-100% FLOW CL 1 2 1 G : XMTR DISPLAY or % DISPLAY X.XX-XXX.XX%YYYY Note 1 < INC > < CHANGE > INC H : LINEARISE 1 or 2 4 A G-2: DISP.
A 11 G-2 : DISP. CHANGE LRV: 4mA=±YYYYYY URV: 20mA=±ZZZZZZ < LRV >< URV > LRV 12 URV CL 3 G-2 : DISP. CHANGE LRV: 4mA=±YYYYYY URV: 20mA=±ZZZZZZ < ENT >< URV > ENT URV CL G-2 : DISP. CHANGE LRV: 4mA=±YYYYYY URV: 20mA=±ZZZZZZ SET OK?< ENT > ENT 16 13 11 13 14 Already set value of transmitter CL 15 G-2 : DISP. CHANGE LRV: 4mA=±YYYYYY URV: 20mA=±ZZZZZZ < ENT >< URV > ENT URV CL 11 12 G-2 : DISP.
When setting of % Flow in %display or Flow unit in actual scale display, low flow cut point and low flow cut mode are displayed ( 22 or 23 ). When, in the OUTPUT MODE (Menu No. 8), OUT = SQR is set, already set low flow cut point and low flow cut mode are displayed ( 23 ). With OUT = LIN set, the present low flow cut point and low flow cut mode are displayed ( 22 ). Then, enter , and the setting can be renewed. B OUT=SQR at Menu No.8 OUT=LIN at Menu No.8 22 23 G-8 : LOW CUT G-8 : LOW CUT POINT=XX.
Programmable linearization function H: LINEARIZE INVALID < INC > < CHNG > 1 CHNG INC CL H-1: CHNG LINEARIZE INVALID < INC > < CHNG > < CL > CL H-2: LINEARIZE < 1 > INVALID < 2 > EFFECTIVE < 1 > < 2 > < CL > 2 INC 19 2 CL CL H-2: LINEARIZE H-3: LINEARIZE CHANGE EFFECTIVE CHNG OK? < ENT/CL > POINT 0 < INC > < CHNG > < CL > 3 CHNG 20 ENT H-3: LINEARIZE CHANGE POINT 0 < ENT > < CL > 21 CHNG ENT H-2: In the case where POINT XX has been set 4 CL Input the value of point and press ENT
6 CL 2 H-4: LINEARIZE H-4: CV1 XXX.XX% < INC> < CNG/ENT/CL > 17 H-4: 18 LINEARIZE INC Next parameter H-4: CL CV2 XXX.XX% < INC> < CNG/ENT/CL > 8 INC INC 13 17 LINEARIZE DEC CV14 Important 14 INC CL for display 18 CV3 18 CV14 XXX.XX% < INC> < CNG/ENT/CL > for display 17 CV2 LINEARIZE CV3 XXX.
Rerange (Set LRV/URV calibration) I: RERANGE (application to level measurement) at change of level (LRV/URV) Functions of RERANGE can be made with FXW Version 6.0 or upward. < INC > < CHNG > 1 CHNG INC I-1: RERANGE < LRV > < URV > < CL > I-2: CL 2 CL LRV I-2: RERANGE LRV 0.00% < ENT > < CL > ENT RERANGE URV 100.00% < ENT > < CL > 3 CL ENT I-3: RERANGE CHANGE LRV .
4.2 Zero Adjustment by the external screw Zero point of the transmitter is adjustable by the outside screw with the mode setting switch in the housing set at zero position. The figure shown below is an example of “Mode setting switch” is attached. (1) Set the mode setting switch to zero position.
4.3 Span adjustment by the external screw The measuring range for each transmitter is determinated according to its type. Span is changed by the outside screw with the mode setting switch in the housing set at span position. The figure shown below is an example of “Mode setting switch” is attached. (1) Set the mode setting switch to span position. Mode setting switch Set switch to “zero” for zero calibration (2) Apply standard input pressure corresponding to new Upper Range Value.
4.4 Local adjustment unit with LCD display 1. Outline When local adjustment unit with LCD display (Parts number is *ZZPFCX4-A055) is installed in the FCX-CII transmitter, some functions are available without HHC (Hand Held Communicator). Name of each part in local adjustment unit with LCD display and their functions are indicated below. Mode setting switch Damping setting switch LOCAL/COMM. changing switch LCD display Table 1.
2.Selection of transmitter adjustment method LOCAL/COMM. Changing switch decides the method of FCX-CII transmitter adjustment. If switch is set to “COMM.” side, adjustment of transmitter is carried out by HHC. This method is explained in instruction manual. If switch is set to “LOCAL” side, adjustment of transmitter is carried out by Mode setting switch and Damping setting switch. This method is explain below. 3.
3.2 Span adjustment (Change Upper Range Value) The measuring range for each transmitter is determined according to its type. The span is changed by the external adj. screw when the mode setting switch is set at “1” or ”6" position. (1) Set the mode setting switch to “1” or ”6” position. (2) Apply standard input pressure corresponding to new Upper Range Value. (3) Adjust output to 20.00mA by turning the external adj. screw.
5 MAINTENANCE 5.1 Periodic inspection In order to ensure the measurement accuracy and long life of the transmitter, it is essential to inspect the transmitter periodically according to the operating conditions. Visual inspection Visually inspect each part of the transmitter for damage, corrosion, etc. If you detect any material which may cause corrosion, it should be cleaned off. Check of cover and O-ring The transmitter has a water and dust-proof construction.
5.2 Troubleshooting If an abnormality occurred in the process or transmitter, action should be taken with reference to the table below. Symptom Cause Remedy Repair the valve so that it opens/closes normally. (1) The manifold valve does not open/close normally. (2) Pressure leak is occurring. (3) Process piping is improper. (4) Process pipe is clogged. (5) Power supply voltage and/or load resistance is improper. Output current overshoots scale (exceeds 20mA). Repair a leak. Make correct piping.
5.3 Replacement of parts If the transmitter requires a replacement part, drain process fluid from the transmitter, disconnect it from the process and carry out replacement in an instrument room. DANGER When removing an explosion-proof transmitter, turn OFF the main power, then disconnect the piping and wiring. Do not remove it when the power is ON to prevent serious accident such as explosion, fire, etc.
Replacement of detecting unit Transmission unit Detecting unit Flexible printed circuit board Hexagonal socket bolt Replacing procedure (1) Remove the electronics unit according to “Replacement of electronics unit”. (2) Remove the hex. socket bolts from the electronic housing. Pull the electronics housing straight forward and away from the detecting unit. (3) Replace the detecting unit with a new one of the same type. (4) Fit the transmission unit to the detecting unit and tighten it.
Replacement of the internal parts of detecting unit In case of differential transmitter (code symbol : FKK/FDK) : Nut Seal diaphragm O-ring Measurement chamber detecting cover Seal tape Seal tape Bolt Replacing procedure (1) Remove four hexagon socket head bolts with a torque wrench, etc.. (2) Disassembly gives access to the casing covers, O-rings, hexagon socket head bolts and nuts. (3) After disassembly, replace the faulty part with a new one.
Replacement of field indicator 1. Replacement of analog indicator Analog indicator Transmitter cover Replacing procedure (1) Detach the transmitter cover. (2) Remove the analog indicator. (3) Pull out the connector extending from the analog indicator. (4) Connect the connector of a new analog indicator to the electronics section. (See the figure below.) (5) Then, mount the analog indicator at the electronics section. (6) Attach the transmitter cover.
2. Replacement of digital indicator Digital indicator Transmitter cover Digital indicator mounting board Replacing procedure (1) Detach the transmitter cover. (2) Remove two fixing screws which fasten the digital indicator and separate the indicator. (3) Pull out the leading end of the flexible PC board extending from the digital indicator after raising the slider (white knob) in the electronics section. (See the figure below.
5.4 Adjustment after replacement of unit Adjustment After completion of the assembly work mentioned above, use the following procedures for adjustment and setting. Adjustment should be performed using the HHC. (1) After replacement of electronics unit (including replacement of internal parts) Step Adjustment item Relevant page 1 Constant current output (output circuit) P19 2 TAG. No.
6 INSTALLATION AND PIPING 6.1 Installation After unpacking, check the delivered items. This transmitter can be mounted on a pipe or on a wall. Note that the bolts (M8) for wall mounting should be supplied by the customer. CAUTION DANGER Important • The transmitter is heavy. Be careful when handling it. • The transmitter should be installed in a place that meets the operating conditions shown in DS sheet or instruction manual. • Install the transmitter according to the instruction manual.
Change of field indicator position CAUTION Avoid the following procedure in an explosionproof area. It is sometimes preferable to mount the indicator on the terminal block side due to installation location. In such a case, the following mounting procedure should be followed for analog indicator. Digital indicator cannot be mounted on the terminal block side. Indicator attached to transmission unit side. ➀ Remove the terminal unit side cover.
Change of transmission unit position CAUTION Avoid the following procedure in an explosionproof area. Wiring is sometimes difficult depending on the installation location. In such a case, it is convenient to carry out the following. Before turning the transmission unit, remove the electronics unit. The transmission unit is secured by 2 hexagonal socket bolts. Loosen the bolts, turn the transmission unit at 90˚ or 180˚ in the clockwise or counterclockwise direction and fix it by the screws.
Change of vent/drain plug position Hold the hexagonal area of the vent/drain plug with a wrench and remove it by turning slowly. Peel the existing seal tape and wind a new seal type. Then, screw the vent/drain plug into the process connection for changing. Process connection Tightening torque: 25N•m (2.5kgf•m) <18ft-lb> Check space Ensure a space of about 500mm against the cover in order to facilitate check, adjustment, etc.
6.2 Piping It is generally recognized that there are appropriate positioning relationship between the transmitter and main process piping for accurate measurement to avoid harmful gas or liquid accumulation. General recognizations are; 1- Mount transmitter below main process piping for liquid or steam measurement. 2- Mount transmitter above main process piping for gas measurement.
Typical examples of piping Manifold valve 1 Flow measurement (in case of gas) Impulse pipe Place the transmitter above the differential pressure source. Stop valve Process pipe Differencial pressure source (orifice) Differencial pressure source (orifice) 2 Flow measurement (in case of liquid) Place the transmitter below the differential pressure source. Process pipe Make piping so that gas in the impulse pipe is not delivered to the transmitter, and incorporate gas reservoirs as required.
Important (1) Protection is required to prevent dust from entering through the atmospheric air inlet after installation of the manifold valve. (2) If process pressure range is narrow (below 10kPa (1000mmH2O)), the following should be considered. • Pressure variation due to wind around atmospheric air inlet • Temperature variation near process taps • Difference in atmospheric pressure between process tap and transmitter location.
Cautions on impulse piping • For liquid, the impulse pipes should have an upward slope of 1/10 or more between the process connection and the transmitter to prevent accumulation of gas, etc. in the detecting unit. • For gas, the impulse pipes should have a downward slope of 1/10 or more between the process connection and transmitter to prevent accumulation of moisture, etc. in the detecting unit.
6.2.2 Piping of pressure transmitter type : FKP Removal of protective cap The process connection port of the transmitter is fitted with a protective cap. Before piping, remove the cap carefully. When removing the cap, carefully protect the threaded portion and sealing face from damage. Connection of transmitter and impulse pipe • Impulse pipe should directly be screwed into the transmitter.
Typical examples of piping 1 Gas measurement Manual valve Impulse pipe 0 10 0 Place the transmitter above the pressure source. 20 40 60 80 Stop valve Pressure source 2 Liquid measurement Process pipe Pressure source Stop valve Impulse pipe 0 10 0 Place the transmitter below the pressure source. Make piping so that gas in the process pipe is not delivered to the transmitter, and incorporate gas reservoirs as required.
6.2.3 Piping of level transmitter type : FKP for open tank Seal on mounting flange face When mounting the flange on the pressure side, a gasket should be inserted as follows. Transmitter flange Process side flange 0 10 0 20 40 60 80 Gasket Important On the projection type, be sure to use a gasket with an internal diameter larger than the flange to prevent the gasket form touching the seal diaphragm.
Caution of installation • Restriction on H1 Liquid level is not proportional to the transmitter output at some points inside the seal diaphragm. Therefore, H1 should be set higher than the value shown in the table below. • In order to prevent vibration, the transmitter body should be installed at a vibration-free place. • Do not shock the seal diaphragm by hitting hard object against it, for example. • Take care not to apply an excessive force to the flange during connection.
7 WIRING Cautions on wiring (1) Application of a voltage exceeding 60 V DC or 40 V AC (exceeding 32 V DC or 23 V AC when arrester equipped) between “+” and “–” terminals may result in damage to the transmitter. (2) Use a shielded cable for the transmission line where possible. (3) Avoid installation of signal cable and power cable in same conduit or cable tray in order to prevent increased noise. Also, do not bring the signal cable close to large electrical equipment.
Terminal block connection diagram Tighten the terminal screws (M4 x10) to a torque of approximately 1.5 N•m (15 kgf•cm) <11ftlb> so that the wires will not loosen. After connection, fasten the cover until it does not turn. Terminal – CK – + CK + 10.5 ~ 45 V DC (Analog type) 16.
Things convenient to know beforehand When using conduit connection at the top For wiring from the top conduit connection, use the following procedure. (1) Remove the screw plug of the top conduit connection. (2) Screw the removed screw plug into the bottom conduit connection. (3) Insert the cable from the top and connect it. Hexagon key wrench Flash screw Important • The unused conduit connection is of great importance to flameproofing and moisture prevention.
7.3 Grounding CAUTION The transmitter must be grounded. Otherwise, it may cause electric shocks or incorrect operation. Grounding terminals are provided at two places (at the inside of terminal box and on the side of conduit connection). By any of the methods given below, ground the transmitter in compliance with the relevant stipulation in the standard on explosionproof installation (for example, grounding resistance 100 Ω or less by one of the methods given below).
8 SPARE PARTS A-5 A-41 A-6 A-39 A-40 A-12 A-2 58 A-20A A-11A A-24A A-13A A-10 A-40 12 28 A-12A A-31A B-14 A-5A A-5 B-16 B-9 A-3 B-8 A-1 B1~5 B-12 B-16 C1~4 B-17 C-17 C-7 This diagram shows main parts of the differential pressure transmitter, pressure transmitter. For details, contact our office.
No. Parts No.
No. Parts No. Part Name Q’ty B-1~5 –––––––– Detecting unit (Differential pressure and Flow) 1 * ZZPFCX4-B080 O-ring 2 Viton * ZZPFCX4-B081 Square section gasket 2 Teflon * ZZPFCX4-B091 Cover 2 SCS14 S B-8 B-9 Material Remarks Contact our office for inquiry Minimum order q’ty 10 pcs. 4th digit of type code * ZZPFCX4-B093 Cover 2 SCS14 T,X * ZZPFCX4-B095 Cover 2 SCS14 V,W B-12A * ZZPFHC1-B122 Vent/drain kit 2 B-14 * ZZPFHC1-B143 Bolt/Nut kit 4 C.S.
A1 BUILT-IN ARRESTER General An arrester is used to protect a transmitter or receiver from an abnormal voltage such as lightning surges induced into signal lines. A built-in type arrester is mounted behind the terminal unit. A nameplate marked “with arrester” is attached to the terminal unit of transmitter with a built-in arrester. Installation The built-in arrester should be used in combination with panel mounting type arrester (type PXC) for distributor protection.
Maintenance ♦ Check of arrester • Measure output current from the transmitter check terminals and output current to flow into transmitter (see figures below). When current is measured with an ammeter connected to CK+ and CK- terminals, the internal resistance of the ammeter should be 12Ω or less. • If the measured two output current are the same, the arrester is normal. • In case the measured values have a difference of 0.1% (0.016mA) or more, the arrester is not functioning.
A2 CALIBRATION Preparation for calibration The transmitter should be calibrated in a calibration room. For calibration of each transmitter, the following devices are required. o Pressure source and pressure measuring equipment (should have as high an accuracy as possible) * Measurable ranges are listed in the table below. o Power supply : DC power supply (24 V DC) or Fuji Electric FC series power supply unit (type PXJ or PXL) o Load resistor : Standard resistor 250 Ω (within ±0.
Calibration procedure (1) Make wiring according to the diagram below. Connect DC power supply (power source), digital voltmeter (measuring device), standard resistance and HHC (Hand Held Communicator): When current is measured with an ammeter connected to CK+ and CK- terminals, the internal resistance of the ammeter should be 12Ω or less. HHC Digital voltmeter DC power supply Load resistance Standard resistance Important For communication with the HHC, a load resistor of 250Ω is necessary.
A3 PARAMETER SETTING PRIOR TO DELIVERY The damping value (time constant), function of zero/span adjust screw, output current mode, indicator scale, cut point, mode below cut point and burnout, have been set prior to delivery as shown in the following. No.
A4 HAZARDOUS LOCATION INSTALLATION INFORMATION This appendix contains one table and four drawings that present installation instruction for the FCX-A/C Series Transmitter in a hazardous location. Refer to these figures when installing or servicing a transmitter mounted in a hazardous location. When installed the apparatus MUST be provided with a voltage limiting device which will prevent the rated voltage of 45V being exceeded.
67 CK– – + – CK– CK+ FXE FXE CK+ + CK+ Shunt Bar CK– CK– – + – FXE FXE – CK– + CK+ n2 Field Indicator (FXE) CK+ + CK– – – CK– + CK+ N = (n1 + n2 ) < = 3 (for IIC, IIB, IIA) FXE FXE <3 = 0.085 0.265 0.715 IIC IIB IIA Capacitance [µF] N Group Ex 440 165 55 < =3 N: Number of field indicator (FXE) < =3 15.6 5.6 1.6 < =3 Inductance [mH] or L/R Ratio [µH/Ω] Fuji Electric Co., Ltd. FCX-A/C Series Transmitter System SYST BAS No.
Fuji Electric France S.A. 46, Rue Georges Besse - Z I du Brézet 63 039 Clermont-Ferrand cedex 2 — FRANCE France : Tél. 04 73 98 26 98 - Fax 04 73 98 26 99 International : Tél. (33) 4 7398 2698 - Fax. (33) 4 7398 2699 E-mail : sales.dpt@fujielectric.fr Fuji Electric can accept no responsibility for possible errors in catalogues, brochures and other printed material. Fuji Electric reserves the right to alter its products without notice.