LOAD REGULATION CHARACTERISTICS
NO.
LOAD
CONDITION
OUTPUT LOAD
12V
+3.3V +5V +12V1 +12V2 -12V +5Vsb
1
COND.1 X X X X X 2 .5A
2
COND.2 X X X X X 0A
3
COND.3 0.5A 0.3A 0.5A 0.5A 0A 0A
4
COND.4 24A 0.5A 4A 4A 0.1A 2A
5
COND.5 6A 15A 8A 0.5A 0A 2.5A
6
COND.6 0.5A 4A 16A 0.5A 0.1A 2.5A
7
COND.7 0.5A 4A 0.5A 16A 0.1A 2.5A
8
COND.8 7.5A 5A 9A 9A 0.2A 1.5A
9
COND.9 24A 6A 1A 11A 0.3A 0A
10
COND.10 0.5A 8A 12.5A 12.5A 0.,3A 1A
11
COND.11 12.52A 8.94A 10.44A 10.44A 0.25A 2.09A
3.2 REMOTE ON/OFF CONTROL
The power supply shall accept a logic open collector level which will disable/
enable all the output voltage (exclude + 5V standby).
As logic level is low, outputs voltage were enabled.
As logic level is high, outputs voltage were disabled.
Note: 1. Logic high level: 2.0-5.25V while sourcing 0.2mA maximum.
2. Logic low level: 0-0.5V while sinking 1.6mA maximum.
3. Rise Time: 15ms maximum (10%-90%).
3.3 OUTPUT VOLTAGE HOLD-UP TIME
15.0 mS minimum : at 230V / 50 Hz. (80%LOAD COND.8)
3.4 OPERATION AT NO LOAD
The power supply shall be capable of being operated with no load on any or
all outputs without damage. For no load on +3.3V & +5V, the output shall not
exceed +4.3V & +6.5Vdc and the power supply may shutdown and require
by remote-control or remove AC power restart.
3.5 PROTECTION
3.5.1 Over-voltage protection
In the event of an over-voltage condition on +3.3 & +5Vdc &+12V the
power supply shall shutdown and require remote control or remove the AC
mains input to reset the system.
+5V : 6.5V (maximum)
+3.3V : 4.3V (maximum)
+12V : 15.5V (maximum)